Crown Boiler BSI172, BSI241, BSI276, BSI345, BSI379, BSI103, BSI138, BSI069, BSI207, BSI310 Start

Page 36

Troubleshooting Chart for BSI Boilers Equipped with

Hydrolevel CG400A Low Water Cut-offs and Vent Dampers

Caution: Read page 34 before attempting to use this chart

 

 

 

 

START

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

damper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there an audible

 

 

 

 

 

 

 

 

 

 

open?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

click as R8225 relay

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

calls for heat

 

 

 

 

 

 

 

 

 

 

 

 

pulls in w hen the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermostat calls for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is yellow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED lit on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LWCO?

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

120 volts across

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

24 volts betw een

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

black and w hite

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2 and 2 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transformer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CG400 LWCO?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

leads?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Jumper missing

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 volts across

 

 

 

 

 

 

 

 

 

 

 

 

betw een 1 and P1 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blue and yellow

 

 

 

 

 

 

 

Y

 

 

 

CG400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

w ires inside

 

 

 

 

 

 

 

 

 

 

* Poor connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

N

 

junction box?

 

 

 

 

 

 

 

 

 

 

 

 

betw een transformer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and terminals

1 & 2 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CG400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

24 volts present

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

betw een each

 

 

N

* Boiler off on low w ater

 

 

 

 

 

*Pow er off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure limit

 

 

* Loose probe connection

 

 

 

 

 

*Blow n fuse or

 

 

 

 

 

 

Is 24 volts

 

 

connection and

 

 

 

 

 

 

 

* Poor ground path from

 

 

 

 

 

 

 

 

 

 

 

 

yellow transformer

 

 

 

 

 

 

 

 

 

 

 

 

tripped

 

 

 

 

 

present across

 

 

 

 

 

 

 

 

heat exchanger to CG400

 

 

 

 

 

 

 

 

 

 

 

 

 

connection?

 

 

 

 

 

 

 

 

 

 

 

 

breaker

 

 

 

 

 

 

brow n and

 

 

 

 

 

 

 

 

 

 

case

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Misw ired or

 

N

 

yellow leads on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

loose 120 volt

 

 

R8225 relay?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Boiler off on pressure limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Defective pressure limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disconnect

 

 

 

 

* Defective

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Defective

 

 

 

 

thermostat and

 

 

 

 

R8225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transformer

 

 

 

 

temporarily jump

 

 

 

 

See Note #7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See Note #6 on

 

 

 

 

boiler thermostat

 

 

 

 

on page 34

 

 

 

 

 

 

 

 

 

24 volts present

 

 

Y

 

 

 

 

 

page 34

 

 

 

 

connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

across blue lead on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

together

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R8225 and yellow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transformer leads?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Bad connection in thermostat w iring

*Defective thermostat

* Thermostat misw ired or

Y

misapplied

 

 

Does relay

N

pull in now ?

 

*Loose connection betw een transformer and R8225 coil

N

* Defective R8225

36

35

Image 36
Contents BSI Series Table of Contents Product DescriptionII Specifications BSI SpecificationsIII Before Installing IV Locating the BoilerAir for Combustion and Ventilation For Buildings of Other than Unusually Tight Construction ForBuildingsofUnusuallyTightConstructionBOILERINSTALLEDINCONFINEDSPACE, ALL AIR from Inside ALL AIR from OUTDOORS, Using Openings Into Boiler Room VI Venting Removing an Existing Boiler from a Common Chimney BSI Boilertypicalventsystem Installation and Components VII Gas Piping GasconnectiontoboilerViii System Piping General Piping NotesPipingInstallation Common NEAR-BOILER Piping Mistakes IX Indirect Water Heater Piping Indirectwater Heater BOILER-SIDE PipingWiring Indirect Water Heater Wiring Wiring Indirectwater Heater to Boiler BSI Control System Sequence of Operation Sequence of Operation, Standing PilotVent Damper Note Less Vent GAS Valve BSI379 Honeywell VR8204/VR8304 Series GAS Valves BSI069 Robertshaw XI Start-up and Checkout 2423Standing Pilot Burner Flame For Your Safety Read Before Operating For Your Safety Read Before Lighting For Your Safety Read Before Lighting Position Indicator High Altitude Burners GASVALVEDETAIL-HONEYWELLVR8200ORVR8300STANDINGPILOT XII Service and Maintenance On a continuous basisOn at least a weekly basis On an annual basisPage Heat Exchanger Cleaning Procedure Xiii Troubleshooting Start END Start END Standing Pilot Ignition System Troubleshooting Chart Intermittent Ignition System Troubleshooting Chart XIV Parts Page KEY # Page Boilers only Page Appendix a Knockdown Boiler Assembly Instructions Before InstallingFIGUREA1 BASE, Heat EXCHANGER, Flue Collector Assembly Gas Valve Installation Figure A2 Jacket Installation Electrical Wiring Connections Complete InstallationFigure A3 Tapping Locations see Text for Tapping Uses Crown

BSI069, BSI345, BSI207, BSI172, BSI241 specifications

Crown Boiler Company is renowned for its high-quality heating solutions, with a diverse range of models designed to meet various residential and commercial needs. Among their popular offerings are the BSI series, which includes the BSI379, BSI138, BSI310, BSI276, and BSI103 models. Each of these boilers comes with distinct features, technologies, and characteristics that cater to different applications and preferences.

The Crown Boiler BSI379 is a powerful and efficient boiler designed for residential use. It features a stainless steel heat exchanger that enhances durability and improves heat transfer efficiency. The BSI379 operates on natural gas, providing a high thermal efficiency rating which helps to reduce energy costs. With a compact design, it can fit conveniently in various installations, making it a versatile choice for homeowners.

The BSI138 model is another excellent option for smaller residential spaces. It is equipped with advanced technology that allows for quiet operation and minimal environmental impact. This boiler also offers a straightforward control interface, making it easy for homeowners to adjust settings according to their heating needs. The BSI138's lightweight construction and small footprint allow for flexible installation options.

Moving on to the BSI310, this model is designed for medium to larger-sized homes. It features an electronic ignition system that ensures reliable start-up while minimizing gas consumption. The BSI310 also incorporates multiple safety features, including pressure relief valves and limit controls, enhancing user safety during operation. Its robust design ensures efficient heating even in the coldest months.

The BSI276 model is characterized by its sealed combustion design, which improves indoor air quality by preventing drafts and ensuring that all combustion air is drawn from outside. This model is ideal for energy-conscious homeowners seeking environmentally friendly options. Its high-efficiency rating translates to significant energy savings over time, making it a financially wise investment.

Finally, the BSI103 is an entry-level model that retains the quality and reliability associated with Crown Boilers. It is particularly suited for smaller homes or apartments and offers ease of use and maintenance. The BSI103 combines affordability with efficiency, providing a cost-effective heating solution without compromising on performance.

In summary, the Crown Boiler BSI series, comprising the BSI379, BSI138, BSI310, BSI276, and BSI103, showcases a blend of innovative technologies and features. With options suitable for various household sizes and energy needs, Crown Boiler continues to deliver reliable heating solutions that cater to modern homeowners’ demands for efficiency, safety, and convenience. Each model's unique characteristics ensure that users can find the perfect boiler to meet their heating requirements.