Desa VSL18NT, VSL18PT installation manual Troubleshooting, Observed Problem Possible Cause Remedy

Page 18

TROUBLESHOOTING

WARNING:Turnoffandunplugheaterandletcoolbeforeservicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle or similar object to clean ODS/pilot. This can damage ODS/pilot unit.

Note: All troubleshooting items are listed in order of operation.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

When ignitor button is pressed,

1. Ignitor electrode positioned

1.

Replace pilot assembly

there is no spark at ODS/pilot

 

wrong

2.

Replace pilot assembly

 

2.

Ignitor electrode broken

 

3.

Ignitor electrode not con-

3.

Reconnect ignitor cable

 

 

nected to ignitor cable

4.

Free ignitor cable if pinched

 

4.

Ignitor cable pinched or wet

 

 

 

 

by any metal or tubing. Keep

 

 

 

 

ignitor cable dry

 

5.

Broken ignitor cable

5.

Replace ignitor cable

 

6.

Bad ignitor

6.

Replace ignitor

When ignitor button is pressed, there is spark at ODS/pilot but no ignition

1.Gas supply turned off or equip- ment shutoff valve closed

2.Control knob not in PILOT position

3.Control knob not pressed in while in PILOT position

4.Air in gas lines when in- stalled

5.Depleted gas supply (propane/ LP gas only)

6.ODS/pilot is clogged

7.Gas regulator setting is not correct

1.Turn on gas supply or open equipment shutoff valve

2.Turn control knob to PILOT position

3.Press in control knob while in PILOT position

4.Continue holding down con- trol knob. Repeat igniting op- eration until air is removed

5.Contact local propane/LP gas company

6.Clean ODS/pilot (see Cleaning and Maintenance, page 17) or replace ODS/pilot assembly

7.Replace gas regulator

18

www.desatech.com

116292-01D

Image 18
Contents What to do if YOU Smell GAS Table of Contents Safety Information Product Identification Product FeaturesLocal Codes UnpackingFollowing are excerpts from National Fuel AIR for Combustion VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining FRESH-AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceCheck GAS Type InstallationVentilation AIR Ventilation Air From Inside BuildingInstalling Glass Panel Installation ItemsInstalling Ignitor Removing Front Panel of HeaterLocating Heater This heater is designed to be mounted on a wallInstalling Heater to Wall Connecting to GAS Supply Installing Bottom Mounting ScrewsPlacing Heater On Mounting Bracket Checking GAS Connections Test Pressures In Excess Of 1/2 Psig 3.5 kPa Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPaOperating Heater Connecting to Electrical SupplyFor Your Safety Read Before Lighting Extension Cord Thermostat Control Operation Lighting Instructions To Turn OFF GAS To Appliance Shutting Off HeaterBurner Flame Pattern Manual Lighting ProcedureInspecting Heater Pilot Flame PatternBurner Pilot AIR Inlet Cleaning MaintenanceODS/PILOT and Burner CabinetTroubleshooting Observed Problem Possible Cause RemedyBurner orifice is clogged Clean burner see Cleaning Goes out when control knob is Control knob not pressedDelayed ignition of burner Manifold pressure is too low ODS/pilot lights but flameSlight smoke or odor during Walls or furniture Cleaners, etc. may turn intoNo power to electric outlet 60Hz outlet Air passageways on heaterMent above For purposes of input adjustment SpecificationsWiring Diagrams LSL18NT, SL18NT and VSL18NT LSL18PT, SL18PT and VSL18PTReplacement Parts AccessoriesTechnical Service Service Publications Service HintsIllustrated Parts Breakdown Models LSL18NT, LSL18PT, SL18NT, SL18PT, VSL18NT and VSL18PTParts List Parts Centrals 116292-01D Warranty Information Keep this WarrantyQUÉ Hacer SI Percibe Olor a GAS Tabla DE Contenido Información DE Seguridad Desempaque Información DECódigos Locales Características DEL ProductoConstrucción inusualmente sellada Aire Para Combustión VentilaciónCómo Proveer LA Ventilación Adecuada Espacio confinado y no confinadoAire Para Ventilación Aire del interior de la construcción para ventilaciónInstalación Verifique EL Tipo DE GASAire del exterior para ventilación Instalación DEL Encendedor Artículos DE InstalaciónDesmontaje DEL Panel Anterior DEL Calentador Instalación del panel de vidrioCorrientes de aire fuertes Ubicación DEL CalentadorInstalación DEL Calentador EN LA Pared Soporte de montajeDoble el anclaje de pared como se muestra en la figura Instalación de los tornillos de montaje Conexión AL Suministro DE GASColocación del calentador en el soporte de montaje InferioresLo suficientemente grande para que Permita el paso del volumen de gasRevisión DE LAS Conexiones DE GAS Adecuado al calentador. Si la tuberíaUsando aire comprimido Cierre del equipoRegule la presión del sistema de tubería de Repare todas las fugas inmediatamenteCable DE Extensión Funcionamiento DEL CalentadorConexión a LA Alimentación Eléctrica Para SU SEGURIDAD, LEA Esto Antes DE EncenderloFuncionamiento DEL Instrucciones DE EncendidoApague el piloto Calentador Funcionamiento DELPatrón DE LA Llama DEL Procedimiento DEEntrada DE Aire AL Piloto DEL Quemador Limpieza Y MantenimientoPiloto CON ODS Y Quemador GabineteLa posición del regulador de gas no es la correcta Solución DE ProblemasProblema Observado Causa Posible Remedio Reemplace el regulador de gasCausa Posible Remedio Línea de gas El problema desapareceráHay aire en la línea de gas Hasta que se elimine el aire Los conductos de aire en elCia anterior LSL18NT, SL18NT y VSL18NT Diagramas DE CableadoEspecificaciones LSL18PT, SL18PT y VSL18PTPublicaciones DE Servicio AccesoriosServicio Técnico Piezas DE RepuestoClasificación Ilustrada DE Piezas Modelos LSL18NT, LSL18PT, SL18NT, SL18PT, VSL18NT Y VSL18PTLista DE Piezas Laporte’s Parts & Service 2444 N th Street Centrales DE PiezasNotas Información DE Garantía Guarde Esta Garantía