For Vertical Runs
The flue system must be supported every eight
(8)feet (2.4M) above the heater flue outlet by wall brackets.
To install support brackets for vertical runs:
•Attach wall brackets to the flue pipe and se- cure the wall bracket to the framing members with nails or screws.
Use wall brackets to support vertical runs every 8 feet (2.4M) above the heater flue outlet.
WALL BRACKET |
WALL STUD |
8 FT. |
(2.4m) |
FLUE |
OUTLET |
1 INCH MIN. |
(25.4mm) |
Figure 13 Installing Support Brackets
4. Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the flue passes.
To install firestops for horizontal runs that pass through either interior or exterior walls:
•Cut a
•Position the firestops on both sides of the hole previously cut and secure the firestops with nails or screws.
•The heat shields of the firestops MUST BE placed towards the top of the hole.
•Continue the flue run through the firestops.
FLUE PIPE |
Figure 14 Hole and Flue Pipe
HEAT SHIELD
TRIM HEAT SHIELD IF TOO LONG, ADD TO SHIELD IF TOO SHORT
EXTERIOR
FIRESTOP
INTERIOR
FIRESTOP
Figure 15 Heat Shield, Interior and Exterior Firestops
For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the flue passes.
To install firestops for vertical runs that pass through ceilings:
•Position a plumb bob directly over the center of the vertical flue component.
•Mark the ceiling to establish the centerpoint of the flue.
15