Bosch Appliances FMR-1000-RCMD Display, Piezo Sounder, Piezo Operation System Status

Page 12

Remote Command CenterOperating en 13

LED

 

System Status

 

 

 

 

Trouble

On

When the panel is initializing

Yellow

 

When the panel registers a trouble condition from a point, or the panel

When inputs or outputs or other elements are bypassed

Flashing 1) – When the panel is not operating

When walk test is in progress

Off

– When no trouble condition exists

When the panel is resetting

1)LED flash rate is 1 Hz (0.5 s on, 0.5 s off).

Table 9.1 LED Operation

Display

The FMR-1000-RCMD Remote Command Center uses an 80-character (4 lines x 20 characters) wide viewing-angle LCD display. The display includes a long-life LED backlight. The backlight is controlled by the panel, or locally turned on upon any key press and turned off after

30-second time-out without key press. Even when AC power is lost, the LED backlight remains lit if a user is operating the keypad.

Piezo Sounder

The FMR-1000-RCMD Remote Command Center has a piezo that provides audible indication of the system status. Refer to Table 9.2 for piezo modes when FMR-1000-RCMD is controlled by the panel:

Piezo Operation

System Status

 

 

Silent

The panel is in a normal state (no alarm, supervisory or trouble

 

condition). The panel was silenced or acknowledged after an off-

 

normal condition.

 

 

Continuous beep

The panel is in fire alarm condition.

 

 

Periodic beep

The panel is in gas alarm condition.

(0.5 s every 2 s)

 

 

 

Periodic beep

The panel is in supervisory condition.

(0.5 s every 4 s)

 

 

 

Periodic beep

The panel is in trouble condition or a communication fault exists

(0.5 s every 10 s)

on the Option Bus.

 

 

Short beep

With every valid key press.

 

 

Table 9.2 Piezo Operation with FMR-1000-RCMD Panel Controlled

In case of multiple piezo activation, the system status with highest priority is indicated. If the Remote Command Center is not controlled by the panel or during a communication fault, refer to Table 9.3 for piezo modes:

Piezo Operation

System Status with FMR-1000-RA Controlled Locally

 

 

Periodic beep

A communication fault exists on the Option Bus.

(0.5 s every 10 s)

 

 

 

Table 9.3 Piezo Operation with FMR-1000-RCMD Controlled Locally

Bosch Security Systems, Inc.

Installation and Operation Guide

F.01U.078.098 3.0 2011.11

Image 12
Contents Remote Command Center FMR-1000-RCMD 01U.078.098 3.0 Bosch Security Systems, Inc Table of Contents Scope of Delivery Device DescriptionDescription 4Mounting Removing the Cover FrameSurface Mounting Inserting the Language Tab on Address Setting on Wiring on Flush Mounting5Wiring Option Bus Circuit Wiring DistanceWiring Connections GNDRemoving the Cover Frame for Service Inserting the Language Tab7Address Setting 8ProgrammingOption Bus DIPOperating LEDs and LCD KeypadLED System StatusDisplay Piezo SounderPiezo Operation System Status Lamp Test 3Keypad OperationsView Status AcknowledgeTroubleshooting Specifications11.1 Electrical 11.2 Mechanics 11.3 Environmental Conditions11.4Trademarks Solución de problemas Especificaciones ÍndiceCableado Aviso Suministro IncluidoDescripción del Dispositivo ¡NOTA4Montaje Extracción de la Cubierta de CarcasaMontaje en Superficie Leyenda Cableado Montaje EmpotradoDistancia del cableado de los circuitos del bus de opciones Conexiones del CableadoTierra Configuración de Dirección Introducción de la Ficha de IdiomaExtracción del Marco de Cubierta de la Carcasa para el Mantenimiento8Programación Dirección deBus de Opciones Operación Teclado LCD y LEDLED Estado del SistemaPantalla Sirena PiezoeléctricaOperación de la Sirena Estado del Sistema Piezoeléctrica Prueba de lámparas Operaciones de TecladoVisualización del Estado ReconocerRecordatorio de Problema SilencioRestablecer EvacuaciónSolución de problemas Especificaciones11.1 Datos eléctricos Sirena Descripción Piezoeléctric11.2 Datos mecánicos 11.3 Condiciones Ambientales11.4 Marcas comerciales Resolução de Problemas Especificações CabeamentoConteúdo do Fornecimento Descrição do DispositivoNota Cuidado4Instalação Removendo a Estrutura de CoberturaInstalação em Superfície Pt Instalação Centro de Comando Remoto Cabeamento Instalação EmbutidaDistância do Cabeamento do Circuito do Barramento de OpçõesTerra Definição do Endereço Removendo a Estrutura de Cobertura para Manutenção8Programação Endereço doBarramento De Opções Operação LEDs e Teclado LCDEstado do Sistema Sirene Piezelétrica Operação Piezelétrica Estado do SistemaTeste de Lâmpada 3Operações do TecladoVisualizar Estado ReconhecidoResolução de Problemas Lembrete de FalhaTeste de evacuação Piezelétrica DescriçãoEspecificações 11.1 Elétricas11.2 Mecânicas SEM Comunicação11.3 Condições Ambientais 11.4 Marcas RegistradasPhillips é uma marca registrada da Phillips Screw Co Bosch Security Systems, Inc