Sears N9MP2050B12B1 Filter Installation using Optional Filter Rack, Addition Of Air Conditioning

Page 36

Mounted Filter Rack

25-20-90

Filter Installation using Optional Filter Rack

When installing or removing a bottom mounted filter, slide the two side filter clips to the back of the furnace BEFORE installing or re- moving. This will allow the filter to clear the front raised edge of the furnace. Insert filter into side clips first and push filter back until it is fully engaged into back clip. When filter is in place, slide clips back into place midway on filter as shown in Figure 36.

Bottom Mounted Filter Rack

25-24-18

Slide filter clips towards back before removing

Refer to Figure 37 and for guidelines to install filters. Furnaces

which require larger filter media and have limited clearances on one side of furnace, require a standoff filter rack, see Figure 37, available from your distributor.

Standoff Filter Rack

UsingOptional

Standoff Filter

Rack

25-21-45a

CAUTION

If filters are only suitable for heating application, advise

homeowner that filter size may need to be increased if air

conditioning is added.

Addition Of Air Conditioning

When a refrigeration coil is used in conjunction with this unit, it must be installed on the discharge side of the unit to avoid con- densation on the heat exchanger. The coil installation instructions must be consulted for proper coil location and installation proce-

dures. With a parallel flow arrangement, dampers must be installed to prevent chilled air from entering the furnace. If ma nual- ly operated dampers are used, they must be equipped with a means to prevent operation of either unit unless the damper is in full heat or full cool position.

A 3" clearance is required on the right side ofthe furnace in order to run the condensate drain line. Copper, iron or plastic tubing may be

used for the condensate drain line.

Downflow Furnace Installation

Non- Combustible Floor Installation

Fabricate a plenum to the dimensions given in Table 11, for the fur-

nace outlet. Plenum should be flanged, approximately 3/4" for sup- port.

Note: The three(3) screws in the top panel of the furnace next to

the duct flange MUST be removed to provide serviceability of the primary heat exchangers in the downflow installation

1.Position plenum through the floor and set the furnace over the opening in the floor. If necessary, grout around the base to seal air leaks between the base and the floor.

Combustible Floor Installation

FIRE HAZARD

Failure to install unit on noncombustible subbase

could result in death, personal injury and/or property damage.

Place furnace on noncombustiblesubbase on

downflow applications, unless installing on non-

combustible floorinq.

;ubbase for Combustible Floor

NOTE: The three(3) screws in the top panel of the furnace next to

the duct flange MUST be removed to provide serviceability of the primary heat exchangers in the downflow installation

Note: When using the subbase for combustible floors, the dis- charge air duct flanges on the furnace MUST be broken down to provide proper fit up to the subbase. Use duct pliers to bend the duct flanges flat onto the furnace casing. DO NOT bend the duct

flanges inward (toward the heat exchangers) as air flow restric- tions may occur.

The Subbase for Combustible Floors MUST be used when a

downflow furnace is set on a combustible floor, even when the fur- nace is installed on a coil box.

1.Cut the opening in the floor according to Table 11. The hole in the floor must be cut to the dimensions listed in Table 11

since the base is equipped with locating tabs that center the base over the opening.

The opening in the base is 11/4 ', shorter and 11/8', narrower than

the recommended size of the opening in the floor. This is done to maintain clearance between the floor and the plenum.

2.Fabricate the plenum to the dimensions given in Table 11.

Note that the dimensions given are outside dimensions.

[_

440 01 1020 04

Image 36
Contents Table of Contents SingleStageKeep This page for future referenceYES NOE YESSafety Rules Installation FrozenWater Pipe HazardLocation and Clearances Installation Requirements Typical Upflow InstallationTypical Downflow Installation Dimensions & Clearances Leveling Air Openings and Connecting Ducts Combustion Ventilation AirRequirements Venting and Combustion Air Check ExampleUnusually Tight Construction Ventilation AirFor Two Pipe Installation Vent and Combustion Air PipingSingle Pipe N9MP1 Models Direct Vent N9MP2 ModelsTocompensateforoxygenburnedSee.Confined Space Installa Piping Insulation GuidelinesContaminated Combustion Air Vent and Combustion Air Piping GuidelinesSizing Combustion Air and Vent Pipe N9MP1 & *9MPD ModelsVent Termination Clearances Carbon Monoxide POISONING, Fire and Explosion Hazard440O1102004 Clearance Description15cmforappliances10,OOOBTUH3kW,12 CondensateDrain Trap Condensate Drain Trap Freeze ProtectionUpflow Installations Top Vent Upflow Installations Top Vent See FigureUpflowInstallationsVentthru LeftSide Upflow Installations Vent thru Left Side See FigureSwitch Side ViewAll ModelsVentthru RightSide All Models Vent thru Right Side See FigureOnly Inlet 4= Downflow Left Side Vent and Trap SeeFigureDownflow Right Side Vent and Trap Downflow Right Side Vent and Trap See FigurePVC 3/4 Coupling & Clamps 112ID Drain Hose On SomeHorizontal Left Thru Top Horizontal Left-Thru Top SeeHorizontal Left-Side Vent See Figure Horizontal Left-Side VentHorizontal Right thru Top Yellowor black16ID Rubber Tube\\ Relief Tube ExtensionHorizontalRight-SideVent Horizontal Right Side Vent SeeFigureConnecting Tee Trap to Condensate Trap and Main Drain Line Connecting Vent and Combustion Air PipingOpen Tee Tee TrapConnecting Vent Pipes and Termination Proper Sealing Procedure for CombustionVent Pipe Connection Fire HazardUsing Exterior Risers Horizontal TerminationVertical Termination Vent Termination ShieldingMulti Vent Termination Clearances Concentric Vent and Combustion Air Sidewall TerminationSidewall Inlet Vent and Exhaust Air Termination CmbustincncentricRoof -AirTerminationventandManifold Gas Pressure Adjustment Supply PressureGas Supply Pressure IAIternate Input Ratings, USA onlyNatural PressureFor the 50,000, 75,000, 100,000 and 125,000 Btuh Models TaiHigh Altitude Air Pressure Switch General Derating RulesElectrical SHOCK, Fire or Explosion Hazard Changing OrificesGas Piping Requirements Manual shut- offLow Pressure ValveElectrical Wiring InstallationsPower SupplyWiring Humidifier/Electronic Air CleanerFan Delay DIP Switch Settings Fan Timer ConnectionsReduced Furnacelife Hazard Mountedto eithertheleftorrightInstallation Ductwork and FilterSizing InsulationFilter Installation using Optional Filter Rack Downflow Furnace InstallationCombustible Floor Installation Downflow applications, unless installing on nonSubbasesforCombustibleFloorsDimensions FloorDimensionsFurnace Subbase Checks and Adjustments Adjust Pilot BurnerGas SupplyPressure StartupTemperature Rise Check Heating and Continuous BlowerSpeed SameChanging Blower Speed Reduced Furnace Life HazardFurnace Maintenance FIRE, EXPLOSION, or Carbon Monoxide HazardsCirculating Fan G Request Heating W RequestHeating Request with Gas Supply Line Shut Off Gas Valve Diagnostic Codes See Figure Typical Gas Valve HoneywellOFF ThanHoneywell SV9541M Smart Valve Sequence of Operation Honeywell SV9541M Smart Valve Trouble shooting Flashes Flashes + I FlashLED IndicatesConcentric Termination Vent Termination ClearancesConcentric Vent Termination Kit # LED INDICATESCHECK/REPAIRRequiredtocompletetheinstallation TicalterminationispreferredFieldsuppliedpipeandfittingsareRain Cap to Vent Pipe Assembly Concentric Vent and Combustion Air Side TerminationTable for N9MP2 Models 50,000 & 80,000 Btuh Furnaces Roof OverhangConcentric Vent Sidewall Attachment Air Elbow25-22-02 N9MP2075B12B1 N9MP2080F16B1 N9MP2100F14B1 N9MP2100J20B1 N9MP2125J20B1Denotes Brand 25-23-30Model Specifications Specifications N9MP1General Specifications N9MP2 Gas & IgnitionSpecifications 9MPD BlowerDataFor 050 Models 3 Ton Units For 075 Models 3 Ton UnitsFor 100 Models Ton 19 & 22314 Units For 080 Models 4 Ton 19 & 22314 UnitsIlttl Neutral tData UI I BKw25-23-95 Key Description Part Functional125J 100J 125JNon-Functional 1GB14B 20B 12B 16B 14BNo. Non-Functional 16B 14B 20B 12BKey Description N9MP1 N9MP2 OsobPart not Illustrated NAHF002LP9MPD Number 080F12B 075F12B 080J16B 100J14B100J20B 128L20B Capacitor,7.SMfd.,370VParts *gMPD KeyDescription No.Non- FunctionalNumber 050F12B 078F12B 080J16B 100J14B 100J2OB 125L20BPart GMPD Non- FunctionalNumber 050F12B 075F12B 080J16B1013816 + Order from Service Parts 44001 Non- Functional Number050F12B 075F12B 080J16B 100J14B IOOJ20B

9MPD100J20B1, N9MP2100J20B1, 9MPD050F12B1, N9MP1100J20B1, N9MP1125J20B1 specifications

The Sears N9MP1075B12B1, N9MPD125L20B1, N9MP1050B12B1, N9MPD080J16B1, and N9MP2125J20B1 are part of the trusted line of gas furnaces manufactured by Sears, specifically designed to deliver reliable heating solutions for residential applications. These models incorporate cutting-edge technology and robust engineering, making them popular choices among homeowners looking for efficiency and comfort.

One of the main features of these models is their high-efficiency operation. With Annual Fuel Utilization Efficiency (AFUE) ratings exceeding 90%, these furnaces convert a significant portion of fuel into usable heat, thereby reducing energy costs. The N9MP series employs a multi-speed blower system that optimizes airflow for enhanced comfort while minimizing noise levels, ensuring a pleasant indoor environment.

The N9MPD125L20B1 and N9MPD080J16B1 variants highlight their adaptability through dual-stage heating capabilities. This technology allows the furnace to adjust its output based on the thermal demands of the home, preventing energy wastage during milder conditions while providing robust heating during extreme cold spells. The two-stage combustion process not only improves comfort but also contributes to lower greenhouse gas emissions.

Durability is another hallmark of these Sears models. With heavy-duty heat exchangers crafted from high-quality materials, they are built to withstand the rigors of regular use. Additionally, the inclusion of advanced safety mechanisms ensures that the system operates securely, reducing potential risks associated with gas furnaces.

The N9MP2125J20B1 model stands out due to its whisper-quiet operation. Homeowners can enjoy a warm home without the disruptive sound commonly associated with traditional heating systems, thanks to the insulated cabinet design and efficient blower operation.

Furthermore, these models come equipped with user-friendly digital thermostats, which allow precise temperature control and programmable settings, enabling homeowners to tailor their heating needs to fit their lifestyle. The compatibility with smart home systems also adds convenience, enabling users to manage their heating remotely, saving even more energy.

In conclusion, the Sears N9MP1075B12B1, N9MPD125L20B1, N9MP1050B12B1, N9MPD080J16B1, and N9MP2125J20B1 gas furnaces exemplify innovation in heating technology. Their energy-efficient designs, advanced features, and durable construction make them reliable choices for homeowners seeking comfort and sustainability in their heating solutions.