7. Ductwork and Filter

CARBON MONOXIDE POISONING HAZARD.

Failure to properly seal duct could result in death and/or personal injury.

Do NOT draw return air from inside a closet or utility room where furnace is located. Return air duct

MUST be sealed to furnace casing.

Side Return Air Cutout

=Height of Cutout for 16" x 25" Filter

AB 22112"141/2"Width of Cutout for 16" x 25" Filter _ rll

Installation

NOTE: Design and install air distribution system to comply with Air

Conditioning Contractors of Arnerica manuals andlor NFPA pam- phlets 90A and 90B or other approved methods that conform to lo- cal codes and good trade practices.

I.When furnace supply ducts carry air outside furnace area, seal return air duct to furnace casing and terminate duct out- side furnace space.

2.Install air conditioning cooling coil (evaporator) on outlet side of furnace.

3.For furnaces installed without a cooling coil it is recom- mended that the outlet duct be provided with a removable

access panel. This panel should be accessible when the furnace is installed so the exterior of the heat exchanger can

be viewed for inspections. The access panel MUST be sealed to prevent leaks.

4.If separate evaporator and blower units are used, install good sealing dampers for air flow control. Chilled air going

through the furnace could cause condensation and shorten the furnace life.

NOTE: Dampers (field supplied) can be either automatic or manu- al. Manually operated dampers MUST be equipped with a means to prevent furnace or air conditioning operation unless da roper is in the full heat or cool position.

CARBON MONOXIDE POISONING HAZARD.

Failure to follow this warning could result in death, personal injury and/or property damage.

Cool air passing over heat exchanger can cause

condensate to form resulting in heat exchanger failure.

Connections

NOTE: On upflow installations, return air can enter through either side, both sides, or the bottom. On horizontal or downflow installa-

tions the return air must enter through the knockout opening in the lower panel of the furnace. Return air can not enter through rear of the furnace. When the furnace is located in an area near or adja- cent to the living area, the system should be carefully designed

with returns to minimize noise transmission through the return grille. Any blower moving a high volume of air will produce audible noise which could be obJectionable to when the unit is located very close to living areas. It is advisable to route the return air ducts un- der the floor or through the attic.

I.For side connections using a 16" x 25" filter, cut out the em- bossed area shown in Figure 34. This will provide a 14112,, x

22112 ,, approximate opening.

Embossed

Area

 

on Side of

Furnace

j_-

 

_'_

Furnace

 

"

Bottom

NOTE: Furnaces with 5 TONS cooling rating require two(2) side returns or one side return with bottom return.

2.Bottom returns can be made by removing the knockout pan-

el in the furnace base. Do NOT remove knock-out except for a bottom return.

3.Installation of locking-type dampers are recommended in all branches, or in individual ducts to balance system's air flow.

4.Non-combustible, flexible duct connectors are recom-

mended for return and supply connections to furnace.

5.If air return grille is located close to the fan inlet, install at

least one, 90 ° air turn between fan and inlet grille to reduce noise.

NOTE: To further reduce noise, install acoustical air turning vanes and/or line the inside of duct with acoustical material.

Sizing

Existing or new ductwork MUST be sized to handle the correct amount of airflow for either heating only or heating and air condi- tioning.

Insulation

1.Insulate ductwork installed in attics or other areas exposed

to outside temperatures with a minimum of 2" insulation and vapor barrier.

2.Insulate ductwork in indoor unconditioned areas with a mini- mum of 1" insulation with indoor type vapor barrier.

Filters

A Filter must be used:

Filters are not supplied with these furnaces, but can be purchased from dealer.

Use either filter type:

Washable, high velocity filters are based on a maximum air flow rating of 600 FPM.

Disposable, Iowvelocity filters are based on a maximum air flow of 300 FPM when used with filter grille.

NOTE: Disposable, low velocity filters may be replaced with wash- able, high velocity filter providing they meet the minimum size areas. Washable, high velocity filters can be replaced ONLY with same type and size.

44001 102004

E_

Image 35
Contents SingleStage Table of ContentsYES KeepThis page for future reference YES NOESafety Rules Location and Clearances InstallationFrozenWater Pipe Hazard Typical Downflow Installation Installation RequirementsTypical Upflow Installation Dimensions & Clearances Leveling Requirements Air Openings and Connecting DuctsCombustion Ventilation Air Ventilation Air Venting and Combustion Air CheckExample Unusually Tight ConstructionDirect Vent N9MP2 Models For Two Pipe InstallationVent and Combustion Air Piping Single Pipe N9MP1 ModelsVent and Combustion Air Piping Guidelines TocompensateforoxygenburnedSee.Confined Space InstallaPiping Insulation Guidelines Contaminated Combustion AirCarbon Monoxide POISONING, Fire and Explosion Hazard Sizing Combustion Air and Vent PipeN9MP1 & *9MPD Models Vent Termination ClearancesClearance Description 440O110200415cmforappliances10,OOOBTUH3kW,12 Condensate Drain Trap Freeze Protection CondensateDrain TrapUpflow Installations Top Vent See Figure Upflow Installations Top VentSide View UpflowInstallationsVentthru LeftSideUpflow Installations Vent thru Left Side See Figure SwitchOnly All ModelsVentthru RightSideAll Models Vent thru Right Side See Figure Downflow Left Side Vent and Trap SeeFigure Inlet 4=Coupling & Clamps 112ID Drain Hose On Some Downflow Right Side Vent and TrapDownflow Right Side Vent and Trap See Figure PVC 3/4Horizontal Left-Thru Top See Horizontal Left Thru TopHorizontal Left-Side Vent Horizontal Left-Side Vent See FigureRelief Tube Extension Horizontal Right thru TopYellowor black 16ID Rubber Tube\\Horizontal Right Side Vent SeeFigure HorizontalRight-SideVentTee Trap Connecting Tee Trap to Condensate Trap and Main Drain LineConnecting Vent and Combustion Air Piping Open TeeFire Hazard Connecting Vent Pipes and TerminationProper Sealing Procedure for Combustion Vent Pipe ConnectionVent Termination Shielding Using Exterior RisersHorizontal Termination Vertical TerminationCmbustincncentricRoof -AirTerminationventand Multi Vent Termination ClearancesConcentric Vent and Combustion Air Sidewall Termination Sidewall Inlet Vent and Exhaust Air TerminationIAIternate Input Ratings, USA only Manifold Gas Pressure AdjustmentSupply Pressure Gas Supply PressureTai NaturalPressure For the 50,000, 75,000, 100,000 and 125,000 Btuh ModelsChanging Orifices High Altitude Air Pressure SwitchGeneral Derating Rules Electrical SHOCK, Fire or Explosion HazardValve Gas Piping RequirementsManual shut- off Low PressureHumidifier/Electronic Air Cleaner Electrical WiringInstallations Power SupplyWiringMountedto eithertheleftorright Fan Delay DIP Switch SettingsFan Timer Connections Reduced Furnacelife HazardInsulation InstallationDuctwork and Filter SizingDownflow applications, unless installing on non Filter Installation using Optional Filter RackDownflow Furnace Installation Combustible Floor InstallationFurnace Subbase SubbasesforCombustibleFloorsDimensionsFloorDimensions Startup Checks and AdjustmentsAdjust Pilot Burner Gas SupplyPressureReduced Furnace Life Hazard Temperature Rise CheckHeating and Continuous BlowerSpeed Same Changing Blower SpeedFIRE, EXPLOSION, or Carbon Monoxide Hazards Furnace MaintenanceHeating Request with Gas Supply Line Shut Off Circulating Fan G RequestHeating W Request Than Gas Valve Diagnostic Codes See FigureTypical Gas Valve Honeywell OFFHoneywell SV9541M Smart Valve Sequence of Operation Indicates Honeywell SV9541M Smart Valve Trouble shootingFlashes Flashes + I Flash LEDLED INDICATESCHECK/REPAIR Concentric TerminationVent Termination Clearances Concentric Vent Termination Kit #TicalterminationispreferredFieldsuppliedpipeandfittingsare RequiredtocompletetheinstallationRoof Overhang Rain Cap to Vent Pipe AssemblyConcentric Vent and Combustion Air Side Termination Table for N9MP2 Models 50,000 & 80,000 Btuh Furnaces25-22-02 Concentric Vent Sidewall AttachmentAir Elbow 25-23-30 N9MP2075B12B1 N9MP2080F16B1N9MP2100F14B1 N9MP2100J20B1 N9MP2125J20B1 Denotes BrandGeneral Model SpecificationsSpecifications N9MP1 Gas & Ignition Specifications N9MP2BlowerData Specifications 9MPDFor 080 Models 4 Ton 19 & 22314 Units For 050 Models 3 Ton UnitsFor 075 Models 3 Ton Units For 100 Models Ton 19 & 22314 UnitsUI I BKw IlttlNeutral t Data25-23-95 100J 125J Key Description PartFunctional 125J12B 16B 14B Non-Functional1GB 14B 20B16B 14B 20B 12B No. Non-FunctionalNAHF002LP Key DescriptionN9MP1 N9MP2 Osob Part not IllustratedCapacitor,7.SMfd.,370V 9MPDNumber 080F12B 075F12B 080J16B 100J14B 100J20B 128L20B125L20B Parts *gMPDKeyDescription No.Non- Functional Number 050F12B 078F12B 080J16B 100J14B 100J2OB080J16B Part GMPDNon- Functional Number 050F12B 075F12BIOOJ20B 1013816 + Order from Service Parts 44001Non- Functional Number 050F12B 075F12B 080J16B 100J14B

9MPD100J20B1, N9MP2100J20B1, 9MPD050F12B1, N9MP1100J20B1, N9MP1125J20B1 specifications

The Sears N9MP1075B12B1, N9MPD125L20B1, N9MP1050B12B1, N9MPD080J16B1, and N9MP2125J20B1 are part of the trusted line of gas furnaces manufactured by Sears, specifically designed to deliver reliable heating solutions for residential applications. These models incorporate cutting-edge technology and robust engineering, making them popular choices among homeowners looking for efficiency and comfort.

One of the main features of these models is their high-efficiency operation. With Annual Fuel Utilization Efficiency (AFUE) ratings exceeding 90%, these furnaces convert a significant portion of fuel into usable heat, thereby reducing energy costs. The N9MP series employs a multi-speed blower system that optimizes airflow for enhanced comfort while minimizing noise levels, ensuring a pleasant indoor environment.

The N9MPD125L20B1 and N9MPD080J16B1 variants highlight their adaptability through dual-stage heating capabilities. This technology allows the furnace to adjust its output based on the thermal demands of the home, preventing energy wastage during milder conditions while providing robust heating during extreme cold spells. The two-stage combustion process not only improves comfort but also contributes to lower greenhouse gas emissions.

Durability is another hallmark of these Sears models. With heavy-duty heat exchangers crafted from high-quality materials, they are built to withstand the rigors of regular use. Additionally, the inclusion of advanced safety mechanisms ensures that the system operates securely, reducing potential risks associated with gas furnaces.

The N9MP2125J20B1 model stands out due to its whisper-quiet operation. Homeowners can enjoy a warm home without the disruptive sound commonly associated with traditional heating systems, thanks to the insulated cabinet design and efficient blower operation.

Furthermore, these models come equipped with user-friendly digital thermostats, which allow precise temperature control and programmable settings, enabling homeowners to tailor their heating needs to fit their lifestyle. The compatibility with smart home systems also adds convenience, enabling users to manage their heating remotely, saving even more energy.

In conclusion, the Sears N9MP1075B12B1, N9MPD125L20B1, N9MP1050B12B1, N9MPD080J16B1, and N9MP2125J20B1 gas furnaces exemplify innovation in heating technology. Their energy-efficient designs, advanced features, and durable construction make them reliable choices for homeowners seeking comfort and sustainability in their heating solutions.