Sears 9MPD125L20B1 manual Venting and Combustion Air Check, Example, Unusually Tight Construction

Page 9

 

 

 

 

Free Area

 

BTUH

 

MinimumFreeArea Requiredfor Each Opening

Input

HorizontalDuct

VerticalDuctor openings

Round Duct

Rating

 

(2,000 BTUH)

 

to outside(4,000 BTUH)

(4,000 BTUH)

50,000

 

25 sq. in.

 

12.5 sq. in.

4"

75,000

 

37.5 sq. in.

 

1825 sq. in.

5"

100,000

 

50 sq. in.

 

25 sq. in.

6"

125,000

 

62.5 sq. in.

 

3125 sq. in.

7"

150,000

 

75 sq. in.

 

37.5 sq. in.

7"

EXAMPLE:

Determining

Free Area

 

 

Appliance

1

Appliance

2

Total

Input

 

100,000

+ 30,000 = (130,000

+ 4,000) =

32.5 Sq. In. Vertical

Appliance

1

Appliance

2

Total

Input

 

100,000 + 30,000 = (130,000 + 2,000) = 65 Sq. In. Horizontal

One permanent opening, commencing within 12" of the top of the

enclosure, shall be permitted where the equipment has clear- ances of at least 1" from the sides and back and 6" from the front of

the appliance. The opening shall directly communicate with the

outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communi- cate with the outdoors, and shall have a minimum free area of:

1 sq. in per 3000 Btu per hr. of the total input rating of all equipment located in the enclosure, and

Not less than the sum ofthe areas of all vent connectors in the confined space.

Unconfined Space Installation

CARBON MONOXIDE POISONING HAZARD

Failure to supply additional air by means of ventilation grilles or ducts could result in death and/or personal injury.

An unconfined space or homes with tight construction may not have adequate air infiltration for proper combustion and ventilation of flue gases.

Most homes will require additional air.

An unconfined space is defined as an area having a minimum vol- ume of 50 cubic feet per 1,000 Btuh total input rating for all gas ap- pliances in area. Refer to Table 2 for minimum area required.

 

I Unconfined

Space

 

 

Minimum Area in Square Feet

BTUH Input

Minimum Area in Square Feet

Rating

 

 

 

50,000

 

312

 

78,000

 

49O

 

114,000

 

712

 

155,000

 

968

 

EXAMPLE: NOTE: Square feet is based on 8 foot ceilings.

28,000 BTUH X 50 Cubic Ft. =

1,400

= 175 Sq. Ft.

1,000

 

8'Ceiling

Height

NOTE: Refer to definitions in section titled Unusually Tight

Construction, If any one of the conditions apply, the space MUST be considered confined space regardless of size.

1.Adjoining rooms can be considered part of an unconfined area if there are openings without doors between rooms.

2.An attic or crawl space may be considered an unconfined space provided there are adequate ventilation openings di- rectly to outdoors. Openings MUST remain open and NOT have any means of being closed off. Ventilation openings to outdoors MUST be at least 1" square of free area per 4,000 BTUH of total input rating for all gas appliances in area.

3.Install air intake a minimum of 12" above maximum snow level and clear of any obstruction. Duct or ventilation open- ing requires one square inch of free area per 4,000 BTU H of total input rating for all gas appliances in area.

4.Air inlet MUST be screened with not less than 1/4" mesh screen.

Unusually Tight Construction

In unconfined spaces, infiltration may be adequate to provide air

for combustion, ventilation and dilution of flue gases. However, in

buildings with unusually tight construction, additional air MUST be provided using the methods described in section titled Confined Space Installation:

Unusually tight construction is defined as: Construction with

1.Walls and ceilings exposed to the outside have a continu- ous, sealed vapor barrier. Openings are gasketed or sealed and

2, Doors and openable windows are weather stripped and

3.Other openings are caulked or sealed. These includejoints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at

penetrations for plumbing, electrical and gas lines, etc.

Ventilation Air

Some provincial codes and local municipalities require ventilation or make-up air be brought into the conditioned space as replace- ment air. Whichever method is used, the mixed return air tempera- ture across the heat exchanger MUST not fall below 60°F or flue gases will condense in the heat exchanger. This will shorten the life of the heat exchanger and possibly void your warranty.

Venting and Combustion Air Check

NOTE: When an existing Category I furnace is removed or re- placed, the original venting system may no longer be sized to prop- erly vent the attached appliances, and to make sure there is adequate combustion air for all appliances, MAKE THE FOL-

LOWING CHECK.

 

Vent

Check

 

Vent Pipe----_,l

I 7

Draft Hood

Typical Gas

f

_'_

 

WaterHeate

/ i

i

Match

I

 

 

I

If flame pulls towards draft hood, this indicates sufficient

venting.

44001 102004

[_

Image 9
Contents SingleStage Table of ContentsThis page for future reference KeepYES NOE YESSafety Rules Installation FrozenWater Pipe HazardLocation and Clearances Installation Requirements Typical Upflow InstallationTypical Downflow Installation Dimensions & Clearances Leveling Air Openings and Connecting Ducts Combustion Ventilation AirRequirements Example Venting and Combustion Air CheckUnusually Tight Construction Ventilation AirVent and Combustion Air Piping For Two Pipe InstallationSingle Pipe N9MP1 Models Direct Vent N9MP2 ModelsPiping Insulation Guidelines TocompensateforoxygenburnedSee.Confined Space InstallaContaminated Combustion Air Vent and Combustion Air Piping GuidelinesN9MP1 & *9MPD Models Sizing Combustion Air and Vent PipeVent Termination Clearances Carbon Monoxide POISONING, Fire and Explosion HazardClearance Description 440O110200415cmforappliances10,OOOBTUH3kW,12 Condensate Drain Trap Freeze Protection CondensateDrain TrapUpflow Installations Top Vent See Figure Upflow Installations Top VentUpflow Installations Vent thru Left Side See Figure UpflowInstallationsVentthru LeftSideSwitch Side ViewAll ModelsVentthru RightSide All Models Vent thru Right Side See FigureOnly Downflow Left Side Vent and Trap SeeFigure Inlet 4=Downflow Right Side Vent and Trap See Figure Downflow Right Side Vent and TrapPVC 3/4 Coupling & Clamps 112ID Drain Hose On SomeHorizontal Left-Thru Top See Horizontal Left Thru TopHorizontal Left-Side Vent Horizontal Left-Side Vent See FigureYellowor black Horizontal Right thru Top16ID Rubber Tube\\ Relief Tube ExtensionHorizontal Right Side Vent SeeFigure HorizontalRight-SideVentConnecting Vent and Combustion Air Piping Connecting Tee Trap to Condensate Trap and Main Drain LineOpen Tee Tee TrapProper Sealing Procedure for Combustion Connecting Vent Pipes and TerminationVent Pipe Connection Fire HazardHorizontal Termination Using Exterior RisersVertical Termination Vent Termination ShieldingConcentric Vent and Combustion Air Sidewall Termination Multi Vent Termination ClearancesSidewall Inlet Vent and Exhaust Air Termination CmbustincncentricRoof -AirTerminationventandSupply Pressure Manifold Gas Pressure AdjustmentGas Supply Pressure IAIternate Input Ratings, USA onlyPressure NaturalFor the 50,000, 75,000, 100,000 and 125,000 Btuh Models TaiGeneral Derating Rules High Altitude Air Pressure SwitchElectrical SHOCK, Fire or Explosion Hazard Changing OrificesManual shut- off Gas Piping RequirementsLow Pressure ValveInstallations Electrical WiringPower SupplyWiring Humidifier/Electronic Air CleanerFan Timer Connections Fan Delay DIP Switch SettingsReduced Furnacelife Hazard Mountedto eithertheleftorrightDuctwork and Filter InstallationSizing InsulationDownflow Furnace Installation Filter Installation using Optional Filter RackCombustible Floor Installation Downflow applications, unless installing on nonSubbasesforCombustibleFloorsDimensions FloorDimensionsFurnace Subbase Adjust Pilot Burner Checks and AdjustmentsGas SupplyPressure StartupHeating and Continuous BlowerSpeed Same Temperature Rise CheckChanging Blower Speed Reduced Furnace Life HazardFIRE, EXPLOSION, or Carbon Monoxide Hazards Furnace MaintenanceCirculating Fan G Request Heating W RequestHeating Request with Gas Supply Line Shut Off Typical Gas Valve Honeywell Gas Valve Diagnostic Codes See FigureOFF ThanHoneywell SV9541M Smart Valve Sequence of Operation Flashes Flashes + I Flash Honeywell SV9541M Smart Valve Trouble shootingLED IndicatesVent Termination Clearances Concentric TerminationConcentric Vent Termination Kit # LED INDICATESCHECK/REPAIRTicalterminationispreferredFieldsuppliedpipeandfittingsare RequiredtocompletetheinstallationConcentric Vent and Combustion Air Side Termination Rain Cap to Vent Pipe AssemblyTable for N9MP2 Models 50,000 & 80,000 Btuh Furnaces Roof OverhangConcentric Vent Sidewall Attachment Air Elbow25-22-02 N9MP2100F14B1 N9MP2100J20B1 N9MP2125J20B1 N9MP2075B12B1 N9MP2080F16B1Denotes Brand 25-23-30Model Specifications Specifications N9MP1General Gas & Ignition Specifications N9MP2BlowerData Specifications 9MPDFor 075 Models 3 Ton Units For 050 Models 3 Ton UnitsFor 100 Models Ton 19 & 22314 Units For 080 Models 4 Ton 19 & 22314 UnitsNeutral t IlttlData UI I BKw25-23-95 Functional Key Description Part125J 100J 125J1GB Non-Functional14B 20B 12B 16B 14B16B 14B 20B 12B No. Non-FunctionalN9MP1 N9MP2 Osob Key DescriptionPart not Illustrated NAHF002LPNumber 080F12B 075F12B 080J16B 100J14B 9MPD100J20B 128L20B Capacitor,7.SMfd.,370VKeyDescription No.Non- Functional Parts *gMPDNumber 050F12B 078F12B 080J16B 100J14B 100J2OB 125L20BNon- Functional Part GMPDNumber 050F12B 075F12B 080J16BNon- Functional Number 1013816 + Order from Service Parts 44001050F12B 075F12B 080J16B 100J14B IOOJ20B

9MPD100J20B1, N9MP2100J20B1, 9MPD050F12B1, N9MP1100J20B1, N9MP1125J20B1 specifications

The Sears N9MP1075B12B1, N9MPD125L20B1, N9MP1050B12B1, N9MPD080J16B1, and N9MP2125J20B1 are part of the trusted line of gas furnaces manufactured by Sears, specifically designed to deliver reliable heating solutions for residential applications. These models incorporate cutting-edge technology and robust engineering, making them popular choices among homeowners looking for efficiency and comfort.

One of the main features of these models is their high-efficiency operation. With Annual Fuel Utilization Efficiency (AFUE) ratings exceeding 90%, these furnaces convert a significant portion of fuel into usable heat, thereby reducing energy costs. The N9MP series employs a multi-speed blower system that optimizes airflow for enhanced comfort while minimizing noise levels, ensuring a pleasant indoor environment.

The N9MPD125L20B1 and N9MPD080J16B1 variants highlight their adaptability through dual-stage heating capabilities. This technology allows the furnace to adjust its output based on the thermal demands of the home, preventing energy wastage during milder conditions while providing robust heating during extreme cold spells. The two-stage combustion process not only improves comfort but also contributes to lower greenhouse gas emissions.

Durability is another hallmark of these Sears models. With heavy-duty heat exchangers crafted from high-quality materials, they are built to withstand the rigors of regular use. Additionally, the inclusion of advanced safety mechanisms ensures that the system operates securely, reducing potential risks associated with gas furnaces.

The N9MP2125J20B1 model stands out due to its whisper-quiet operation. Homeowners can enjoy a warm home without the disruptive sound commonly associated with traditional heating systems, thanks to the insulated cabinet design and efficient blower operation.

Furthermore, these models come equipped with user-friendly digital thermostats, which allow precise temperature control and programmable settings, enabling homeowners to tailor their heating needs to fit their lifestyle. The compatibility with smart home systems also adds convenience, enabling users to manage their heating remotely, saving even more energy.

In conclusion, the Sears N9MP1075B12B1, N9MPD125L20B1, N9MP1050B12B1, N9MPD080J16B1, and N9MP2125J20B1 gas furnaces exemplify innovation in heating technology. Their energy-efficient designs, advanced features, and durable construction make them reliable choices for homeowners seeking comfort and sustainability in their heating solutions.