Sears N9MP2125J20B1, N9MP2050B12B1 Installation, FrozenWater Pipe Hazard, Location and Clearances

Page 4

FrozenWater Pipe Hazard

WATER DAMAGE TO PROPERTY HAZARD

Failure to protect against the risk of freezing could result in property damage and/or personal injury.

Do not leave your home unattended for long periods during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes and resultant damage.

Your furnace is designed solely to provide a safe and comfortable

living environment. The furnace is NOT designed to ensure that water pipes will not freeze. It is equipped with several safety de- vices that are designed to turn the furnace off and prevent it from restarting in the event of various potentially unsafe conditions.

If your furnace remains off for an extended time, the pipes in your home could freeze and burst, resulting in serious water damage.

If the structure will be unattended during cold weather you should take these precautions.

1.Turn off the water supply to the structure and drain the water lines if possible and add an antifreeze for potable water to drain traps and toilet tanks. Open faucets in appropriate areas.

-or-

2. Installation

CARBON MONOXIDE POISONING HAZARD

Failure to properly vent this furnace or other appliances could result in death, personal injury and/or property damage.

This furnace can NOT be common vented or connected to any type B, BW or L vent or vent

connector, nor to any portion of a factory-built or masonry chimney. If this furnace is replacing a

3reviously common-vented furnace, it may be necessary to resize the existing vent and chimney to

3revent oversizing problems for the other remaining appliance(s). See Venting and Combus- tion Air Check in Gas Vent Installation section. This furnace MUST be vented to the outside.

Location and Clearances

1,

Refer to Figure 1 or Figure 2 for typical installation and ba-

 

sic connecting parts required. Refer to Figure 4 for typical

 

horizontal direct vent installation and basic connecting parts

 

required. Supply and return air plenums and duct are also

 

required.

Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Instruct them on a service agency to call to provide service, if required.

-or-

3.Install a reliable remote sensing device that will notify some- body of freezing conditions within the home.

Winter Shutdown

If you go away during the winter months and do not leave the heat on in your home, the plastic transition box and the condensate trap on the furnace must be protected from freeze damage.(See Figure 9 trough Figure 18)

1.Disconnect the 5/8" OD rubber hose from the vent drain fit-

ting that is located downstream of the combustion blower. Insert a funnel into the hose and pour four(4) ounces of sani- tary type (RV) antifreeze into the condensate trap. Recon- nect the 5/8" OD rubber hose to the stub on the vent drain fitting. Secure with the hose clamp.

2.Disconnect the 3/4" OD rubber hose from the condensate trap. Insert a funnel into the hose and and pour four(4) ounces of sanitary type (RV) antifreeze into the plastic Tran- sition box. Squeeze the hose together near the end and quickly reconnect the 3/4" OD rubber hose to the stub on the condensate trap. Secure with the hose clamp.

When you return home, your furnace will be ready to start, as it is not necessary to drain the antifreeze from the furnace.

If furnace is a replacement, it is usually best to install the fur- nace where the old one was. Choose the location or evalu-

ate the existing location based upon the minimum clearance and furnace dimensions (Figure 3).

FROZEN AND BURST WATER PIPE HAZARD

Failure to protect against the risk of freezing could result in property damage and/or personal injury.

Special precautions MUST be made if installing furnace in an area which may drop below freezing.

This can cause improper operation or damage to

equipment. If furnace environment has the potential

of freezing, the drain trap and drainline must be

protected. The use of electric heat tape or RV

antifreeze is recommended for these installations.

(See "Condensate Trap Freeze Protection Section")

Do NOT operate furnace in a corrosive atmosphere

containing chlorine, fluorine or any other damaging

chemicals. Refer to Combustion & Ventilation Air section,

Contaminated Combustion Air.

E_

440 01 1020 04

Image 4
Contents Table of Contents SingleStageKeep This page for future referenceYES NOE YESSafety Rules FrozenWater Pipe Hazard InstallationLocation and Clearances Typical Upflow Installation Installation RequirementsTypical Downflow Installation Dimensions & Clearances Leveling Combustion Ventilation Air Air Openings and Connecting DuctsRequirements Venting and Combustion Air Check ExampleUnusually Tight Construction Ventilation AirFor Two Pipe Installation Vent and Combustion Air PipingSingle Pipe N9MP1 Models Direct Vent N9MP2 ModelsTocompensateforoxygenburnedSee.Confined Space Installa Piping Insulation GuidelinesContaminated Combustion Air Vent and Combustion Air Piping GuidelinesSizing Combustion Air and Vent Pipe N9MP1 & *9MPD ModelsVent Termination Clearances Carbon Monoxide POISONING, Fire and Explosion Hazard440O1102004 Clearance Description15cmforappliances10,OOOBTUH3kW,12 CondensateDrain Trap Condensate Drain Trap Freeze ProtectionUpflow Installations Top Vent Upflow Installations Top Vent See FigureUpflowInstallationsVentthru LeftSide Upflow Installations Vent thru Left Side See FigureSwitch Side ViewAll Models Vent thru Right Side See Figure All ModelsVentthru RightSideOnly Inlet 4= Downflow Left Side Vent and Trap SeeFigureDownflow Right Side Vent and Trap Downflow Right Side Vent and Trap See FigurePVC 3/4 Coupling & Clamps 112ID Drain Hose On SomeHorizontal Left Thru Top Horizontal Left-Thru Top SeeHorizontal Left-Side Vent See Figure Horizontal Left-Side VentHorizontal Right thru Top Yellowor black16ID Rubber Tube\\ Relief Tube ExtensionHorizontalRight-SideVent Horizontal Right Side Vent SeeFigureConnecting Tee Trap to Condensate Trap and Main Drain Line Connecting Vent and Combustion Air PipingOpen Tee Tee TrapConnecting Vent Pipes and Termination Proper Sealing Procedure for CombustionVent Pipe Connection Fire HazardUsing Exterior Risers Horizontal TerminationVertical Termination Vent Termination ShieldingMulti Vent Termination Clearances Concentric Vent and Combustion Air Sidewall TerminationSidewall Inlet Vent and Exhaust Air Termination CmbustincncentricRoof -AirTerminationventandManifold Gas Pressure Adjustment Supply PressureGas Supply Pressure IAIternate Input Ratings, USA onlyNatural PressureFor the 50,000, 75,000, 100,000 and 125,000 Btuh Models TaiHigh Altitude Air Pressure Switch General Derating RulesElectrical SHOCK, Fire or Explosion Hazard Changing OrificesGas Piping Requirements Manual shut- offLow Pressure ValveElectrical Wiring InstallationsPower SupplyWiring Humidifier/Electronic Air CleanerFan Delay DIP Switch Settings Fan Timer ConnectionsReduced Furnacelife Hazard Mountedto eithertheleftorrightInstallation Ductwork and FilterSizing InsulationFilter Installation using Optional Filter Rack Downflow Furnace InstallationCombustible Floor Installation Downflow applications, unless installing on nonFloorDimensions SubbasesforCombustibleFloorsDimensionsFurnace Subbase Checks and Adjustments Adjust Pilot BurnerGas SupplyPressure StartupTemperature Rise Check Heating and Continuous BlowerSpeed SameChanging Blower Speed Reduced Furnace Life HazardFurnace Maintenance FIRE, EXPLOSION, or Carbon Monoxide HazardsHeating W Request Circulating Fan G RequestHeating Request with Gas Supply Line Shut Off Gas Valve Diagnostic Codes See Figure Typical Gas Valve HoneywellOFF ThanHoneywell SV9541M Smart Valve Sequence of Operation Honeywell SV9541M Smart Valve Trouble shooting Flashes Flashes + I FlashLED IndicatesConcentric Termination Vent Termination ClearancesConcentric Vent Termination Kit # LED INDICATESCHECK/REPAIRRequiredtocompletetheinstallation TicalterminationispreferredFieldsuppliedpipeandfittingsareRain Cap to Vent Pipe Assembly Concentric Vent and Combustion Air Side TerminationTable for N9MP2 Models 50,000 & 80,000 Btuh Furnaces Roof OverhangAir Elbow Concentric Vent Sidewall Attachment25-22-02 N9MP2075B12B1 N9MP2080F16B1 N9MP2100F14B1 N9MP2100J20B1 N9MP2125J20B1Denotes Brand 25-23-30Specifications N9MP1 Model SpecificationsGeneral Specifications N9MP2 Gas & IgnitionSpecifications 9MPD BlowerDataFor 050 Models 3 Ton Units For 075 Models 3 Ton UnitsFor 100 Models Ton 19 & 22314 Units For 080 Models 4 Ton 19 & 22314 UnitsIlttl Neutral tData UI I BKw25-23-95 Key Description Part Functional125J 100J 125JNon-Functional 1GB14B 20B 12B 16B 14BNo. Non-Functional 16B 14B 20B 12BKey Description N9MP1 N9MP2 OsobPart not Illustrated NAHF002LP9MPD Number 080F12B 075F12B 080J16B 100J14B100J20B 128L20B Capacitor,7.SMfd.,370VParts *gMPD KeyDescription No.Non- FunctionalNumber 050F12B 078F12B 080J16B 100J14B 100J2OB 125L20BPart GMPD Non- FunctionalNumber 050F12B 075F12B 080J16B1013816 + Order from Service Parts 44001 Non- Functional Number050F12B 075F12B 080J16B 100J14B IOOJ20B

9MPD100J20B1, N9MP2100J20B1, 9MPD050F12B1, N9MP1100J20B1, N9MP1125J20B1 specifications

The Sears N9MP1075B12B1, N9MPD125L20B1, N9MP1050B12B1, N9MPD080J16B1, and N9MP2125J20B1 are part of the trusted line of gas furnaces manufactured by Sears, specifically designed to deliver reliable heating solutions for residential applications. These models incorporate cutting-edge technology and robust engineering, making them popular choices among homeowners looking for efficiency and comfort.

One of the main features of these models is their high-efficiency operation. With Annual Fuel Utilization Efficiency (AFUE) ratings exceeding 90%, these furnaces convert a significant portion of fuel into usable heat, thereby reducing energy costs. The N9MP series employs a multi-speed blower system that optimizes airflow for enhanced comfort while minimizing noise levels, ensuring a pleasant indoor environment.

The N9MPD125L20B1 and N9MPD080J16B1 variants highlight their adaptability through dual-stage heating capabilities. This technology allows the furnace to adjust its output based on the thermal demands of the home, preventing energy wastage during milder conditions while providing robust heating during extreme cold spells. The two-stage combustion process not only improves comfort but also contributes to lower greenhouse gas emissions.

Durability is another hallmark of these Sears models. With heavy-duty heat exchangers crafted from high-quality materials, they are built to withstand the rigors of regular use. Additionally, the inclusion of advanced safety mechanisms ensures that the system operates securely, reducing potential risks associated with gas furnaces.

The N9MP2125J20B1 model stands out due to its whisper-quiet operation. Homeowners can enjoy a warm home without the disruptive sound commonly associated with traditional heating systems, thanks to the insulated cabinet design and efficient blower operation.

Furthermore, these models come equipped with user-friendly digital thermostats, which allow precise temperature control and programmable settings, enabling homeowners to tailor their heating needs to fit their lifestyle. The compatibility with smart home systems also adds convenience, enabling users to manage their heating remotely, saving even more energy.

In conclusion, the Sears N9MP1075B12B1, N9MPD125L20B1, N9MP1050B12B1, N9MPD080J16B1, and N9MP2125J20B1 gas furnaces exemplify innovation in heating technology. Their energy-efficient designs, advanced features, and durable construction make them reliable choices for homeowners seeking comfort and sustainability in their heating solutions.