Sears N9MP1125J20B1, N9MP2050B12B1, N9MP2080F16B1, N9MP2075B12B1 440O1102004, Clearance Description

Page 13

Item

Clearance Description

AClearance above grade, veranda, porch, deck, balcony, or anticipated snow level

BClearance to a window or door that may he opened

Canadian Installation (1)

12" (30cm)#

6" (15 cm) for appliances _< 10,000 BTUH (3kW), 12" (30 cm) for appliances > 10,000 Btuh (3 kW) and _<100,O00 Btub (30 kW), 36" (91 cm) for appliances > 100,000 Btab (30 kW)

U.S. Installation (2)

12" (30cm)

6" (15 cm) for appliances_<10,000BTUH(3kW),9" (23 cm) for appliances>10,000Btuh(3 kW)and _<50,000Btuh(15 kW),12" (30cm) for appliances>50,000Btub(15 kW)

CClearance to a permanently closed window

DVertical clearance to a ventilated soffit located above the

terminal within a horizontal distance of 2'(61cm) from the centedine of the terminal

EClearance to an unventilated soffit

FClearance to an outside corner

O

Clearance

to

an inside

corner

 

 

 

H

Clearance

to each side

of the

centedine

extended above

3'(91 cm) within 15' (4.5 m) above the meter/regulator

 

electrical

meter

or gas

service

regulator

assembly

assembly

I

Clearance

to

service regulator

vent outlet

3'(91 cm)

J

Clearance

to

non-mechanical

air supply

inlet to building or

6" (15cm)forappliances_<lO,OOOBTUH(3kW),9" (23cm)

 

the combustion

air inlet

to any

other appliance

for appliances> 10,000Btah (3kW) and _<100,000Btah(30

 

 

 

 

 

 

 

 

kW) and _<50,000Btuh(15kW), 12" (30 cm) for appliances

 

 

 

 

 

 

 

 

> 50,000Btah(15kW)

3'(91 cm) within 15' (4.5 m) above the meter/regulator assembly

6" (15cm)forappliances_<lO,OOOBTUH(3kW),9"

(23cm)

for appliances > 10,000 Btah (3 kW) and _<50,000 Btuh (15 kW), 12" (30 cm) for appliances > 50,000 Btuh (15 kW)

K

Clearance

to a mechanical

air supply inlet

6'(1.83m)

3'(91 cm) above if within 10' (3m horizontally)

L

Clearance

under a veranda,

porch, deck,

or balcony

12"

(30 cm)

+

M

Clearance

to each side of the centerline

extended above or

12"

(30 cm)

12" (30 cm)

 

below vent terminal of the furnace to a dryer or water heater

 

 

 

vent, or other appliance's direct vent intake or exhaust.

 

 

 

N

Clearance

from a plumbing

vent stack

 

3'(91 cm)

3'(91 cm)

(1.)

In accordance wifh the currem CSA B149.1, Natural Gas and Propane Installation Code

(2.)

In accordance

with the current ANSI Z223.1/NFPA 54, National

Fuel Gas Code

 

#18" (46 cm) above roof surface

+ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

For clearances not specified in AN SI Z223.1/N FPA 54 or C SA B149.1, clearances shall be in accordance with local installation codes and the requirements of the gas supplier and the manufactare's installatio i instructions.

Notes:

1. The vent for this appliance shall not terminate a. Over public walkways; or

b. Near soffit vents or crawl space veins or other areas where condensate or vapor could create a nusiance or hazard or property damage; or c. Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.

2. When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the combustiob products of adjacent vents. Recircula0on can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.

440O1102004

E_

Image 13
Contents SingleStage Table of ContentsThis page for future reference KeepYES NOE YESSafety Rules FrozenWater Pipe Hazard InstallationLocation and Clearances Typical Upflow Installation Installation RequirementsTypical Downflow Installation Dimensions & Clearances Leveling Combustion Ventilation Air Air Openings and Connecting DuctsRequirements Example Venting and Combustion Air CheckUnusually Tight Construction Ventilation Air Vent and Combustion Air Piping For Two Pipe Installation Single Pipe N9MP1 Models Direct Vent N9MP2 ModelsPiping Insulation Guidelines TocompensateforoxygenburnedSee.Confined Space InstallaContaminated Combustion Air Vent and Combustion Air Piping GuidelinesN9MP1 & *9MPD Models Sizing Combustion Air and Vent PipeVent Termination Clearances Carbon Monoxide POISONING, Fire and Explosion HazardClearance Description 440O110200415cmforappliances10,OOOBTUH3kW,12 Condensate Drain Trap Freeze Protection CondensateDrain TrapUpflow Installations Top Vent See Figure Upflow Installations Top VentUpflow Installations Vent thru Left Side See Figure UpflowInstallationsVentthru LeftSideSwitch Side ViewAll Models Vent thru Right Side See Figure All ModelsVentthru RightSideOnly Downflow Left Side Vent and Trap SeeFigure Inlet 4=Downflow Right Side Vent and Trap See Figure Downflow Right Side Vent and TrapPVC 3/4 Coupling & Clamps 112ID Drain Hose On SomeHorizontal Left-Thru Top See Horizontal Left Thru TopHorizontal Left-Side Vent Horizontal Left-Side Vent See FigureYellowor black Horizontal Right thru Top16ID Rubber Tube\\ Relief Tube ExtensionHorizontal Right Side Vent SeeFigure HorizontalRight-SideVentConnecting Vent and Combustion Air Piping Connecting Tee Trap to Condensate Trap and Main Drain LineOpen Tee Tee TrapProper Sealing Procedure for Combustion Connecting Vent Pipes and TerminationVent Pipe Connection Fire HazardHorizontal Termination Using Exterior RisersVertical Termination Vent Termination ShieldingConcentric Vent and Combustion Air Sidewall Termination Multi Vent Termination ClearancesSidewall Inlet Vent and Exhaust Air Termination CmbustincncentricRoof -AirTerminationventandSupply Pressure Manifold Gas Pressure AdjustmentGas Supply Pressure IAIternate Input Ratings, USA onlyPressure NaturalFor the 50,000, 75,000, 100,000 and 125,000 Btuh Models TaiGeneral Derating Rules High Altitude Air Pressure SwitchElectrical SHOCK, Fire or Explosion Hazard Changing OrificesManual shut- off Gas Piping RequirementsLow Pressure ValveInstallations Electrical WiringPower SupplyWiring Humidifier/Electronic Air CleanerFan Timer Connections Fan Delay DIP Switch SettingsReduced Furnacelife Hazard Mountedto eithertheleftorrightDuctwork and Filter InstallationSizing InsulationDownflow Furnace Installation Filter Installation using Optional Filter RackCombustible Floor Installation Downflow applications, unless installing on nonFloorDimensions SubbasesforCombustibleFloorsDimensionsFurnace Subbase Adjust Pilot Burner Checks and AdjustmentsGas SupplyPressure StartupHeating and Continuous BlowerSpeed Same Temperature Rise CheckChanging Blower Speed Reduced Furnace Life HazardFIRE, EXPLOSION, or Carbon Monoxide Hazards Furnace MaintenanceHeating W Request Circulating Fan G RequestHeating Request with Gas Supply Line Shut Off Typical Gas Valve Honeywell Gas Valve Diagnostic Codes See FigureOFF ThanHoneywell SV9541M Smart Valve Sequence of Operation Flashes Flashes + I Flash Honeywell SV9541M Smart Valve Trouble shootingLED IndicatesVent Termination Clearances Concentric TerminationConcentric Vent Termination Kit # LED INDICATESCHECK/REPAIRTicalterminationispreferredFieldsuppliedpipeandfittingsare RequiredtocompletetheinstallationConcentric Vent and Combustion Air Side Termination Rain Cap to Vent Pipe AssemblyTable for N9MP2 Models 50,000 & 80,000 Btuh Furnaces Roof OverhangAir Elbow Concentric Vent Sidewall Attachment25-22-02 N9MP2100F14B1 N9MP2100J20B1 N9MP2125J20B1 N9MP2075B12B1 N9MP2080F16B1Denotes Brand 25-23-30Specifications N9MP1 Model SpecificationsGeneral Gas & Ignition Specifications N9MP2BlowerData Specifications 9MPDFor 075 Models 3 Ton Units For 050 Models 3 Ton UnitsFor 100 Models Ton 19 & 22314 Units For 080 Models 4 Ton 19 & 22314 UnitsNeutral t IlttlData UI I BKw25-23-95 Functional Key Description Part125J 100J 125J1GB Non-Functional14B 20B 12B 16B 14B16B 14B 20B 12B No. Non-FunctionalN9MP1 N9MP2 Osob Key DescriptionPart not Illustrated NAHF002LPNumber 080F12B 075F12B 080J16B 100J14B 9MPD100J20B 128L20B Capacitor,7.SMfd.,370VKeyDescription No.Non- Functional Parts *gMPDNumber 050F12B 078F12B 080J16B 100J14B 100J2OB 125L20BNon- Functional Part GMPDNumber 050F12B 075F12B 080J16BNon- Functional Number 1013816 + Order from Service Parts 44001050F12B 075F12B 080J16B 100J14B IOOJ20B