Sears 9MPD125L20B1 Concentric Termination, Vent Termination Clearances, Led Indicatescheck/Repair

Page 45

HONEYWELL SV9541M "SMART VALVE" Trouble shooting continued

LED

INDICATESCHECK/REPAIR

STATUS

6Flashes +

3Flashes

SoftLockout.

Last failure was pressure switch

Maximum recycle count exceeded

Combustion air blower is de-energized, Circulating blower is de- energized after the "OFF" delay.

After 5-minute delay time, control system will reset and initiate a new ignition sequence,

Ignition system control switch must be in the ON position.

Pressure switches operation, tubing, and wiring.

Restrictions in furnace air intake or vent piping.

High winds blowing against vent.

6Flashes +

4Flashes

Soft Lockout.

Last failure was limit circuit opened during run.

Combustion air blower is de-energized, Circulating blower is de-energized after the "OFF" delay.

After 5-minute delay time, control system will reset and initiate a new ignition sequence,

Main limit switch.

Limit and rollout switch wiring is in good condition and securely connected.

Restriction in duct work.

Dirty filter

 

SoftLockout.

 

 

Blowerfailure(typical)

Deadblower.

7 Flashes

 

Limittrip tooklongerthan2 minutesto reset.

Blockedductwork.

 

 

System will start a new ignition sequence after 1 hour, if call for

 

 

heat still present.

 

11. Concentric Termination

Vent Termination Clearances

CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD

Failure to properly vent this furnace could result in death, personal injury and/or property damage.

Inlet and outlet pipes may NOT be vented directly above each other (standard vent terminals).

1.Determine termination locations based on clearances spe-

cified in following steps and as shown in Figure 7, Figure 45 through Figure 50.

2.The vent termination must be located at least 12" above

ground or normally expected snow accumulation levels.

3.Do NOT terminate over public walkways. Avoid areas where condensate may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.

4. The vent termination shall be located at least 4'horizontally from any electric meter, gas meter, gas regulator, and any

relief equipment. These distances apply ONLY to U.S.

installations.

The vent termination is to be located at least 3' above any forced air inlet located within 10' ; and at least 10' from a

combustion air intake of another appliance, except another direct vent furnace intake.

6.In Canada, the Canadian Fuel Gas Codetakes precedence

over the preceding termination instructions.

Concentric Vent Termination - Kit #

NAHA001CV & NAHA002CV

These kits are for vertical or horizontal termination of the combus- tion air inlet and the exhaust vent pipes on Category IV gas-fired condensing furnaces. The NAHAO01CV kit can be used for 3" di- ameter pipe systems. The NAHAOO2CV kit can be used for 2" di- ameter pipe system. Refer to Table 13 for the correct pipe size for

the furnace. Both the combustion air inlet and the exhaust vent pipes must attach to the termination kit. The termination kit must terminate outside the structure and must be installed per the in- structions outlined below for vertical or horizontal termination. Ver-

440O1102004

[_

Image 45
Contents SingleStage Table of ContentsThis page for future reference KeepYES NOE YESSafety Rules Installation FrozenWater Pipe HazardLocation and Clearances Installation Requirements Typical Upflow InstallationTypical Downflow Installation Dimensions & Clearances Leveling Air Openings and Connecting Ducts Combustion Ventilation AirRequirements Example Venting and Combustion Air CheckUnusually Tight Construction Ventilation AirVent and Combustion Air Piping For Two Pipe InstallationSingle Pipe N9MP1 Models Direct Vent N9MP2 ModelsPiping Insulation Guidelines TocompensateforoxygenburnedSee.Confined Space InstallaContaminated Combustion Air Vent and Combustion Air Piping GuidelinesN9MP1 & *9MPD Models Sizing Combustion Air and Vent PipeVent Termination Clearances Carbon Monoxide POISONING, Fire and Explosion HazardClearance Description 440O110200415cmforappliances10,OOOBTUH3kW,12 Condensate Drain Trap Freeze Protection CondensateDrain TrapUpflow Installations Top Vent See Figure Upflow Installations Top VentUpflow Installations Vent thru Left Side See Figure UpflowInstallationsVentthru LeftSideSwitch Side ViewAll ModelsVentthru RightSide All Models Vent thru Right Side See FigureOnly Downflow Left Side Vent and Trap SeeFigure Inlet 4=Downflow Right Side Vent and Trap See Figure Downflow Right Side Vent and TrapPVC 3/4 Coupling & Clamps 112ID Drain Hose On SomeHorizontal Left-Thru Top See Horizontal Left Thru TopHorizontal Left-Side Vent Horizontal Left-Side Vent See FigureYellowor black Horizontal Right thru Top16ID Rubber Tube\\ Relief Tube ExtensionHorizontal Right Side Vent SeeFigure HorizontalRight-SideVentConnecting Vent and Combustion Air Piping Connecting Tee Trap to Condensate Trap and Main Drain LineOpen Tee Tee TrapProper Sealing Procedure for Combustion Connecting Vent Pipes and TerminationVent Pipe Connection Fire HazardHorizontal Termination Using Exterior RisersVertical Termination Vent Termination ShieldingConcentric Vent and Combustion Air Sidewall Termination Multi Vent Termination ClearancesSidewall Inlet Vent and Exhaust Air Termination CmbustincncentricRoof -AirTerminationventandSupply Pressure Manifold Gas Pressure AdjustmentGas Supply Pressure IAIternate Input Ratings, USA onlyPressure NaturalFor the 50,000, 75,000, 100,000 and 125,000 Btuh Models TaiGeneral Derating Rules High Altitude Air Pressure SwitchElectrical SHOCK, Fire or Explosion Hazard Changing OrificesManual shut- off Gas Piping RequirementsLow Pressure ValveInstallations Electrical WiringPower SupplyWiring Humidifier/Electronic Air CleanerFan Timer Connections Fan Delay DIP Switch SettingsReduced Furnacelife Hazard Mountedto eithertheleftorrightDuctwork and Filter InstallationSizing InsulationDownflow Furnace Installation Filter Installation using Optional Filter RackCombustible Floor Installation Downflow applications, unless installing on nonSubbasesforCombustibleFloorsDimensions FloorDimensionsFurnace Subbase Adjust Pilot Burner Checks and AdjustmentsGas SupplyPressure StartupHeating and Continuous BlowerSpeed Same Temperature Rise CheckChanging Blower Speed Reduced Furnace Life HazardFIRE, EXPLOSION, or Carbon Monoxide Hazards Furnace MaintenanceCirculating Fan G Request Heating W RequestHeating Request with Gas Supply Line Shut Off Typical Gas Valve Honeywell Gas Valve Diagnostic Codes See Figure OFF ThanHoneywell SV9541M Smart Valve Sequence of Operation Flashes Flashes + I Flash Honeywell SV9541M Smart Valve Trouble shootingLED IndicatesVent Termination Clearances Concentric TerminationConcentric Vent Termination Kit # LED INDICATESCHECK/REPAIRTicalterminationispreferredFieldsuppliedpipeandfittingsare RequiredtocompletetheinstallationConcentric Vent and Combustion Air Side Termination Rain Cap to Vent Pipe AssemblyTable for N9MP2 Models 50,000 & 80,000 Btuh Furnaces Roof OverhangConcentric Vent Sidewall Attachment Air Elbow25-22-02 N9MP2100F14B1 N9MP2100J20B1 N9MP2125J20B1 N9MP2075B12B1 N9MP2080F16B1Denotes Brand 25-23-30Model Specifications Specifications N9MP1General Gas & Ignition Specifications N9MP2BlowerData Specifications 9MPDFor 075 Models 3 Ton Units For 050 Models 3 Ton UnitsFor 100 Models Ton 19 & 22314 Units For 080 Models 4 Ton 19 & 22314 UnitsNeutral t IlttlData UI I BKw25-23-95 Functional Key Description Part125J 100J 125J1GB Non-Functional14B 20B 12B 16B 14B16B 14B 20B 12B No. Non-FunctionalN9MP1 N9MP2 Osob Key DescriptionPart not Illustrated NAHF002LPNumber 080F12B 075F12B 080J16B 100J14B 9MPD100J20B 128L20B Capacitor,7.SMfd.,370VKeyDescription No.Non- Functional Parts *gMPDNumber 050F12B 078F12B 080J16B 100J14B 100J2OB 125L20BNon- Functional Part GMPDNumber 050F12B 075F12B 080J16BNon- Functional Number 1013816 + Order from Service Parts 44001050F12B 075F12B 080J16B 100J14B IOOJ20B