HONEYWELL SV9541M "SMART VALVE" Trouble shooting continued
LED
INDICATESCHECK/REPAIR
STATUS
6Flashes +
3Flashes
SoftLockout.
Last failure was pressure switch
Maximum recycle count exceeded
Combustion air blower is
After
Ignition system control switch must be in the ON position.
Pressure switches operation, tubing, and wiring.
Restrictions in furnace air intake or vent piping.
High winds blowing against vent.
6Flashes +
4Flashes
Soft Lockout.
Last failure was limit circuit opened during run.
Combustion air blower is
After
Main limit switch.
Limit and rollout switch wiring is in good condition and securely connected.
Restriction in duct work.
Dirty filter
| SoftLockout. |
| |
| Blowerfailure(typical) | Deadblower. | |
7 Flashes |
| ||
Limittrip tooklongerthan2 minutesto reset. | Blockedductwork. | ||
| |||
| System will start a new ignition sequence after 1 hour, if call for |
| |
| heat still present. |
|
11. Concentric Termination
Vent Termination Clearances
CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD
Failure to properly vent this furnace could result in death, personal injury and/or property damage.
Inlet and outlet pipes may NOT be vented directly above each other (standard vent terminals).
1.Determine termination locations based on clearances spe-
cified in following steps and as shown in Figure 7, Figure 45 through Figure 50.
2.The vent termination must be located at least 12" above
ground or normally expected snow accumulation levels.
3.Do NOT terminate over public walkways. Avoid areas where condensate may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
4. The vent termination shall be located at least 4'horizontally from any electric meter, gas meter, gas regulator, and any
relief equipment. These distances apply ONLY to U.S.
installations.
The vent termination is to be located at least 3' above any forced air inlet located within 10' ; and at least 10' from a
combustion air intake of another appliance, except another direct vent furnace intake.
6.In Canada, the Canadian Fuel Gas Codetakes precedence
over the preceding termination instructions.
Concentric Vent Termination - Kit #
NAHA001CV & NAHA002CV
These kits are for vertical or horizontal termination of the combus- tion air inlet and the exhaust vent pipes on Category IV
the furnace. Both the combustion air inlet and the exhaust vent pipes must attach to the termination kit. The termination kit must terminate outside the structure and must be installed per the in- structions outlined below for vertical or horizontal termination. Ver-
440O1102004 | [_ |