Sears N9MP1 Venting and Combustion Air Check, Vent Check, Make the Following Check, Hood, Heater

Page 10

3.Installairintakeminimumof12"abovemaximumsnow levelandclearofanyobstructionDuctorventilationopen.- ingrequiresonesquareinchoffreeareaper4,000BTUH

oftotal input rating for all gas appliances in area.

4.Air inlet MUST be screened with not less than 1/4" mesh

screen.

Unusually Tight Construction

In unconfined spaces, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in

buildings with unusually tight construction, additional air MUST be provided using the methods described in section titled Con- fined Space Installation:

Unusually tight construction is defined as: Construction with

1.Walls and ceilings exposed to the outside have a continu-

ous, sealed vapor barrier. Openings are gasketed or sealed and

2, Doors and openable windows are weather stripped and

3.Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at

penetrations for plumbing, electrical and gas lines, etc.

Ventilation Air

Some provincial codes and local municipalities require ventilation or make-up air be brought into the conditioned space as replace- ment air. Whichever method is used, the mixed return air temper- ature across the heat exchanger MUST not fall below 60 °F or flue gases will condense in the heat exchanger. This will shorten the life of the heat exchanger and possibly void your warranty.

Venting and Combustion Air Check

The following information is supplied to allow the installer to make

adjustments to the setup of existing appliances, IF REQUIRED, based on good trade practices, local codes, and good judgement

of the installer. Manufacturer does NOT take responsibility for

modifications made to existing equipment.

NOTE: If this installation replaces an existing furnace from a commonly vented system, the original venting system may no longer be sized to properly vent the attached appliances. An im- properly sized venting system may cause the formation of con- densate in the vent and the leakage or spillage of vent gases. To

make sure there is adequate combustion air for all appliances,

MAKE THE FOLLOWING CHECK.

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each

appliance connected to the venting system being placed

into operation, while all other appliances connected to the venting system are not in operation:

1.Seal any unused openings in the venting system.

2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI

Z223,1/NFPA 54 or CSA B149. 1, Natural Gas and Pro-

pane Installation Codes and these instructions. Deter- mine that there is no blockage or restriction, leakage, cor- rosion and other de to ensure there is no blockage or re- striction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3.As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.

4.Close fireplace dampers.

5.Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.

6.Followthe lighting instructions. Place the appliance being inspected into operation. Adjust thermostat so appliance is operate continuously.

7.Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. (Figure 6)

8.If improper venting is observed, during any of the above

tests, the venting system must be corrected in accor-

dance with the National Fuel Gas Code, ANSI

Z223,1/NFPA 54 or CSA B149. 1, Natural Gas and Pro-

pane Installation Codes.

9.After it has been determined that each appliance con- nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans,

fireplace dampers and any other gas-fired burning ap- pliance to their previous conditions of use.

Vent Check

 

VentPipe

--_1

 

[

A/

Draft

Hood

 

Typical

Gas

 

 

 

 

 

 

 

Water

Heater,_

f

[

[

_ _,_._.

Match

 

 

I

 

 

 

!

 

 

If flame

pulls towards

 

draft

hood,

this

indicates

suffi-

cient venting.

 

 

 

 

 

 

 

For Two Pipe Installation

This furnace can NOT be common vented or connected to any type B, BW or L vent or vent connector, nor to any portion of a fac- tory-built or masonry chimney. If this furnace is replacing a pre-

viously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for

the other remaining appliance(s). See "Venting and Combustion Air Check"in this section. This furnace MUST be vented to the outside.

E_

44001 111400

Image 10
Contents SingleStage JellJill Denotes BrandMP D 0 75 F 12 a # 440 01 1114Date of Start-Up Furnace/Drip- Leg? YESCO2 ? Frozen Water Pipe Hazard Frozen and Burst Water Pipe HazardLocation and Clearances InstallationTypical Upflow Installation Winter ShutdownFurnace Installation Considerations Installation RequirementsInstallation Positions LevelingAiRI.TAKE Dimensions & ClearancesVENTrgMPD TOPHorizontal Furnace Installation Combustion & Ventilation Air For Single Pipe InstallationAir Openings and ConnectingDucts Confined Space Installation RequirementsEhr Unconfined Space InstallationFree Area Make the Following Check Venting and Combustion Air CheckVent Check HoodDirect Vent N9MP2 Models Vent and Combustion Air PipingSingle Pipe N9MP1 Models Dual Certified gMPDModelsPipe Diameter Table N9MP2 Models Piping Insulation GuidelinesSizing Combustion Air and Vent Pipe Vent Termination ClearancesUnited States Only Condensate Drain TrapCondensate Drain Trap Freeze Protection Canada See Canadian Fuel Gas Code OtherThanDrainLine Upflow Installations Dual Certified *9MPD-A4 ModelsYellowPlasticCap TransitionMountingScrews4 SomemodelsDrain Models HorizontalLeft InstallationsDual Certified *9MPD-A4 25-24-12Rpeept.oT Switch HoseSi.g.Pre...reSwitch \ e.spre X3L/\Page ReturnAir Page Left Side Venting Drainstubonthetransitionandsecurewitha3/4clamp Satetrapandsecurewitha3/4clamp Boxandsecurewitha3/4clampStubonthecondensatetrapandsecurewitha3/4clamp Inlet VentFitting TPipe & ClampsReturn Air Return Modelsshownhave TwopressureswitchesCap Air ClampsLeft Vent Pipe Connection Connecting Vent and Combustion Air PipingCombustion Air Pipe Connection Dual Certified or PVCHorizontal Termination Proper Sealing Procedure for Combustion BlowerVent Pipe Vertical Termination Using Exterior RisersCheckholesizesbymakingsureitissmallerthan the cou Vent Termination ShieldingSidewall Inlet Vent and Exhaust Air Termination Ei271Recommended Alternate Installation for Sustained ColdConcentric Vent and Combustion Air Sidewall Termination Rooftop Inlet Vent and Exhaust Air TerminationSupplyPressure Manifold Gas Pressure AdjustmentAlternate Btuh Input RatingsUSA Only Gas Supply PressureGeneral Derating Rules High Altitude Air Pressure SwitchChanging Orifices for High Altitude Changing OrificesTypical Gas Piping for Upflow Natural Gas Input Rating CheckExample Humidifier/Electronic Air Cleaner Electrical WiringPower SupplyWiring Gas Piping RequirementsFan Timer Connections InstallationFan Delay DIP Switch Settings Ductwork and FilterInsulation Filter Installation using Optional Filter RackSizing FiltersAddition Of Air Conditioning Combustible Floor InstallationAvailablefromyourdistributor StandoffFilterRack Ubbase for Combustible FloorFurnace Subbase Coil CabinetTemperature Rise Check Checks and AdjustmentsAdjust Pilot Burner Main Burner Flame CheckChanging Blower Speed Tochecktemperaturerise,usethefollowingprocedureHeating and Continuous BlowerSpeed the Same Continuous Fan OperationHeating Request with Gas Supply Line Shut Off Gas Valve Diagnostic Codes See FigureCirculating Fan G Request OFFTypical Gas Valve Honeywell Honeywell SV9541M Flashes + Honeywell SV9541M Smart Valve Trouble shootingFlashes Flashes + SoftLockoutVent Termination Clearances Concentric TerminationConcentric Vent Termination Kit # Arerequiredtocompletetheinstallation Concentric Vent Roof InstallationConcentric Termination Kit NAHA001CV & NAHA002CV Venting Rain Cap to Vent Pipe AssemblyConcentric Vent and Combustion Air Side Termination Concentric Vent Sidewall Attachment 25-22-02440011114O0 Save This Manual For Future Reference N9MP2075B12A4 N9MP2080F16A4N9MP2100F14A4 N9MP2100J20A4 N9MP2125J20A4 Denotes BrandSpecifications N9MP1 GeneralNAHA001LV NAHAO01LV NAHA002LV Specifications N9MP2Snap HW HSP Hwhsp PSC/I/2 PSC/II23OO Specifications 9MPDNAHA00SLV For 100 Models 5 Ton 223/4 Units For 075 Models 3 Ton UnitsFor 100 Models Ton 19 & 22314 Units For 125 Models 5 Ton UnitsD22 Connection DiagramDisconnect Before Servicing Ladder Diagram = = =@O,c25-23-95 FF18125J Key Description PartFunctional 100J 125JLOOJ 125J Non-Functional Number 12A O50B 075B 080F LOOF LOOJ 125JIoof 1GA100F 100J KeyDescription No. Non-FunctionalNgMP1 050B 075B 080F 100F 100J 125J Number 16A 14A 20AGMPD Number KeyDescription No.FunctionalHeat Exchanger,Primary Heat Exchanger,Secondary 050F12AKeyDescription No.Non- Functional Models *9MPDO50F12A4, Natural Gas Replacement part supplied 080J16ANon- Functional Non-FunctionalKey Description Number

9MPD, N9MP1, N9MP2 specifications

The Sears N9MP2, N9MP1, and 9MPD are prominent models in the realm of residential heating systems, specifically designed to provide efficient and effective heating solutions. These models are part of Sears' commitment to quality and innovation, making them a popular choice among homeowners seeking reliability and performance.

The N9MP2 is a high-efficiency multi-speed gas furnace that boasts an impressive AFUE (Annual Fuel Utilization Efficiency) rating. This feature allows the furnace to convert a significant portion of fuel into usable heat, which effectively translates to lower energy bills for homeowners. The unit is equipped with a two-stage gas valve that provides increased comfort by adjusting the heating output based on demand, ensuring an even temperature throughout the home.

The N9MP1, like its counterpart, is known for its reliability and efficiency. It offers a single-stage operation that is ideal for homes needing consistent heating without the necessity for the more complex stages present in two-stage systems. This model also has a good AFUE rating, making it a cost-effective solution for families looking to reduce their heating expenses. Its design is tailored for easy installation and maintenance, allowing homeowners to keep their heating systems running at optimal performance without hassle.

The 9MPD model takes a step further with its advanced technology integration. It features a sophisticated control board that allows for easier diagnostics and enhanced system management. The 9MPD is also designed with quiet operation in mind, employing advanced sound-reduction technologies to minimize noise levels during heating cycles. Homeowners will appreciate the peace and quiet it brings, particularly in shared living spaces.

All three models are equipped with high-quality insulation and specialized heat exchangers that enhance their thermal efficiency. Additionally, they are designed with safety features such as automatic shut-off systems and robust flame rollout protection, ensuring a safe heating experience.

In terms of characteristics, these models are generally constructed with durable materials, designed to endure harsh weather conditions while providing consistent heating. They can be connected to various home automation systems, which adds to their appeal for tech-savvy consumers.

In conclusion, the Sears N9MP2, N9MP1, and 9MPD represent a comprehensive lineup of reliable, efficient, and technologically advanced heating systems suitable for contemporary homes. Their dedication to performance ensures that homeowners enjoy a warm and energy-efficient environment throughout the chilly seasons.