4. Vent and Combustion Air Piping

CARBON MONOXIDE POISONING, FIRE AND EXPLO- SION HAZARD

Failure to properly vent this furnace can result in death,

personal injury and/or property damage.

Read and follow all instructions in this section.

Single Pipe (N9MP1 Models)

This furnace is certified as a category IV appliance. This furnace requires ventilation openings to provide air for proper combustion and ventilation of flue gases. All duct or openings for supplying combustion and ventilation air must comply with the gas codes or in absence of local codes, the applicable national codes.

When the installation is complete, see the "Venting and Com-

bustion Air Checl4' in this manual.

Direct Vent (N9MP2 Models)

This furnace is certified as a category ]V appliance. This furnace

uses outside air for combustion ONLY, it MUST be taken from the

same atmospheric pressure zone as the vent pipe. See Con-

fined Space Installation in the Combustion and Ventilation Air in this manual.

Dual Certified ('gMPDModels)

This furnace is certified as a category ]V appliance. This furnace

can be installed as a direct vent furnace using outside air for com- bustion or the furnace can use air from inside the structure for

combustion. The INLET air pipe is optional. If combustion air comes from inside the structure, adequate make up air MUST be

provided to compensate for oxygen burned. See Confined

Space Installation in the Combustion and Ventilation Air

chapter. If combustion air is drawn from outside the structure, it MUST be taken from the same atmospheric pressure zone as the vent pipe.

Contaminated Combustion Air

Installations in certain areas or types of structures will increase

the exposure to chemicals or halogens that may harm the fur- Race.

The following areas or types of structures may contain or have ex-

posure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for combustion.

• Commercial buildings.

Buildings with indoor pools.

Furnaces installed in laundry rooms.

Furnaces installed in hobby or craft rooms.

Furnaces installed near chemical storage areas.

Permanent wave solutions for hair.

Chlorinated waxes and cleaners.

Chlorine based swimming pool chemicals.

Water softening chemicals.

De-icing salts or chemicals.

Carbon tetrachloride.

Halogen type refrigerants.

Cleaning solvents (such as perchloroethylene).

44001 111400

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid.

Sulfuric Acid.

Solvent cements and glues.

Antistatic fabric softeners for clothes dryers.

Masonry acid washing materials.

Vent and Combustion Air Piping Guidelines

This furnace is approved for venting with Schedule 40 PVC, CPVC, ABS, Cellular Core pipe fittings and SDR-26 PVC.

NOTE: All PVC, CPVC, ABS, and Cellular Core pipe fittings, sol- vent cement, primers and procedures MUST conform to Ameri- can National Standard Institute and American Society for Testing and Materials (ANSI/ASTM) standards.

Pipe and Fittings - ASTM D1785, D2241, D2466, D2661, D2665, F-891, F-628

PVC Primer and Solvent Cement- ASTM D2564

Procedure for Cementing Joints - Ref ASTM D2855

NOTE: All vent piping MUST be installed in compliance with local

codes or ordinances, these instructions, good trade practices, and codes of country having jurisdiction.

1.Determine the best routing and termination for the vent pipe and air inlet pipe by referring to all of the instructions and guidelines in this Section.

2.Determine the size required for the vent pipe and air inlet pipe.

3.Loosely assemble all venting parts without adhesive (pipe joint cement) for correct fit before final assembly.

4.Use of vertical piping is preferred because there will be some moisture in the flue gases that may condense as it

leaves the vent pipe (See Special Instruction For Horizon- tal Vents).

5.The vertical vent pipe MUST be supported so that no

weight is allowed to rest on the combustion blower.

6.Exhaust vent piping or air inlet piping diameter MUST NOT be reduced.

7.All exhaust vent piping from the furnace to termination MUST slope upwards. A minimum of 1/4" per foot of run is required to properly return condensate to the furnace drain system.

8.Use DWV type long radius elbows whenever possible, as they provide for the minimum slope on horizontal runs and they provide less resistance in the vent system. If DWV el- bows cannot be used, use two, 45 ° elbows when possible.

On horizontal runs the elbows can be slightly misaligned to provide the correct slope.

9.All horizontal pipe runs MUST be supported at least every five feet with galvanized strap or other rust resistant materi- al. NO sags or dips are permitted.

10.All vertical pipe runs MUST be supported every six feet where accessible.

11.The minimum pipe run length is 2'.

12.The piping can be run in the same chase or adjacent to sup-

ply or vent pipe for water supply or waste plumbing. It can also be run in the same chase with a vent from another 90+ furnace.

NOTE: In NO case can the piping be run in a chase where

temperatures can exceed 140 ° F. or where radiated heat from adiacent surfaces would exceed 140 ° F.

Image 11
Contents SingleStage 440 01 1114 Denotes BrandMP D 0 75 F 12 a # JellJillCO2 ? Furnace/Drip- Leg? YESDate of Start-Up Frozen and Burst Water Pipe Hazard Frozen Water Pipe HazardWinter Shutdown InstallationTypical Upflow Installation Location and ClearancesLeveling Installation RequirementsInstallation Positions Furnace Installation ConsiderationsTOP Dimensions & ClearancesVENTrgMPD AiRI.TAKEConfined Space Installation Requirements Combustion & Ventilation Air For Single Pipe InstallationAir Openings and ConnectingDucts Horizontal Furnace InstallationFree Area Unconfined Space InstallationEhr Hood Venting and Combustion Air CheckVent Check Make the Following CheckDual Certified gMPDModels Vent and Combustion Air PipingSingle Pipe N9MP1 Models Direct Vent N9MP2 ModelsVent Termination Clearances Piping Insulation GuidelinesSizing Combustion Air and Vent Pipe Pipe Diameter Table N9MP2 ModelsCanada See Canadian Fuel Gas Code OtherThan Condensate Drain TrapCondensate Drain Trap Freeze Protection United States OnlyTransition Upflow Installations Dual Certified *9MPD-A4 ModelsYellowPlasticCap DrainLineDrain SomemodelsMountingScrews4 25-24-12 HorizontalLeft InstallationsDual Certified *9MPD-A4 Models\ e.spre X3L/\ Switch HoseSi.g.Pre...reSwitch Rpeept.oTPage ReturnAir Page Left Side Venting Stubonthecondensatetrapandsecurewitha3/4clamp Satetrapandsecurewitha3/4clamp Boxandsecurewitha3/4clampDrainstubonthetransitionandsecurewitha3/4clamp Return Air VentFitting TPipe & ClampsInlet Air Clamps Modelsshownhave TwopressureswitchesCap ReturnLeft PVC Connecting Vent and Combustion Air PipingCombustion Air Pipe Connection Dual Certified or Vent Pipe ConnectionVent Pipe Proper Sealing Procedure for Combustion BlowerHorizontal Termination Vent Termination Shielding Using Exterior RisersCheckholesizesbymakingsureitissmallerthan the cou Vertical TerminationRooftop Inlet Vent and Exhaust Air Termination Ei271Recommended Alternate Installation for Sustained ColdConcentric Vent and Combustion Air Sidewall Termination Sidewall Inlet Vent and Exhaust Air TerminationGas Supply Pressure Manifold Gas Pressure AdjustmentAlternate Btuh Input RatingsUSA Only SupplyPressureChanging Orifices High Altitude Air Pressure SwitchChanging Orifices for High Altitude General Derating RulesExample Natural Gas Input Rating CheckTypical Gas Piping for Upflow Gas Piping Requirements Electrical WiringPower SupplyWiring Humidifier/Electronic Air CleanerDuctwork and Filter InstallationFan Delay DIP Switch Settings Fan Timer ConnectionsFilters Filter Installation using Optional Filter RackSizing InsulationUbbase for Combustible Floor Combustible Floor InstallationAvailablefromyourdistributor StandoffFilterRack Addition Of Air ConditioningCoil Cabinet Furnace SubbaseMain Burner Flame Check Checks and AdjustmentsAdjust Pilot Burner Temperature Rise CheckContinuous Fan Operation Tochecktemperaturerise,usethefollowingprocedureHeating and Continuous BlowerSpeed the Same Changing Blower SpeedOFF Gas Valve Diagnostic Codes See FigureCirculating Fan G Request Heating Request with Gas Supply Line Shut OffTypical Gas Valve Honeywell Honeywell SV9541M Flashes + SoftLockout Honeywell SV9541M Smart Valve Trouble shootingFlashes Flashes +Concentric Vent Termination Kit # Concentric TerminationVent Termination Clearances Concentric Vent Roof Installation ArerequiredtocompletetheinstallationConcentric Vent and Combustion Air Side Termination Rain Cap to Vent Pipe AssemblyConcentric Termination Kit NAHA001CV & NAHA002CV Venting 25-22-02 Concentric Vent Sidewall Attachment440011114O0 Denotes Brand N9MP2075B12A4 N9MP2080F16A4N9MP2100F14A4 N9MP2100J20A4 N9MP2125J20A4 Save This Manual For Future ReferenceGeneral Specifications N9MP1PSC/I/2 PSC/II2 Specifications N9MP2Snap HW HSP Hwhsp NAHA001LV NAHAO01LV NAHA002LVNAHA00SLV Specifications 9MPD3OO For 125 Models 5 Ton Units For 075 Models 3 Ton UnitsFor 100 Models Ton 19 & 22314 Units For 100 Models 5 Ton 223/4 Units= = =@O,c Connection DiagramDisconnect Before Servicing Ladder Diagram D22FF18 25-23-95100J 125J Key Description PartFunctional 125J1GA O50B 075B 080F LOOF LOOJ 125JIoof LOOJ 125J Non-Functional Number 12A16A 14A 20A KeyDescription No. Non-FunctionalNgMP1 050B 075B 080F 100F 100J 125J Number 100F 100J050F12A KeyDescription No.FunctionalHeat Exchanger,Primary Heat Exchanger,Secondary GMPD NumberKeyDescription No.Non- Functional 080J16A Models *9MPDO50F12A4, Natural Gas Replacement part suppliedNumber Non-FunctionalKey Description Non- Functional

9MPD, N9MP1, N9MP2 specifications

The Sears N9MP2, N9MP1, and 9MPD are prominent models in the realm of residential heating systems, specifically designed to provide efficient and effective heating solutions. These models are part of Sears' commitment to quality and innovation, making them a popular choice among homeowners seeking reliability and performance.

The N9MP2 is a high-efficiency multi-speed gas furnace that boasts an impressive AFUE (Annual Fuel Utilization Efficiency) rating. This feature allows the furnace to convert a significant portion of fuel into usable heat, which effectively translates to lower energy bills for homeowners. The unit is equipped with a two-stage gas valve that provides increased comfort by adjusting the heating output based on demand, ensuring an even temperature throughout the home.

The N9MP1, like its counterpart, is known for its reliability and efficiency. It offers a single-stage operation that is ideal for homes needing consistent heating without the necessity for the more complex stages present in two-stage systems. This model also has a good AFUE rating, making it a cost-effective solution for families looking to reduce their heating expenses. Its design is tailored for easy installation and maintenance, allowing homeowners to keep their heating systems running at optimal performance without hassle.

The 9MPD model takes a step further with its advanced technology integration. It features a sophisticated control board that allows for easier diagnostics and enhanced system management. The 9MPD is also designed with quiet operation in mind, employing advanced sound-reduction technologies to minimize noise levels during heating cycles. Homeowners will appreciate the peace and quiet it brings, particularly in shared living spaces.

All three models are equipped with high-quality insulation and specialized heat exchangers that enhance their thermal efficiency. Additionally, they are designed with safety features such as automatic shut-off systems and robust flame rollout protection, ensuring a safe heating experience.

In terms of characteristics, these models are generally constructed with durable materials, designed to endure harsh weather conditions while providing consistent heating. They can be connected to various home automation systems, which adds to their appeal for tech-savvy consumers.

In conclusion, the Sears N9MP2, N9MP1, and 9MPD represent a comprehensive lineup of reliable, efficient, and technologically advanced heating systems suitable for contemporary homes. Their dedication to performance ensures that homeowners enjoy a warm and energy-efficient environment throughout the chilly seasons.