Sears 9MPD, N9MP2, N9MP1 Location and Clearances, Winter Shutdown, Typical Upflow Installation

Page 5

Ifyourfurnaceremainsoffforanextendedtime,thepipesinyour

homecouldfreezeandburst,resultingseriouswaterdamage. Watermaycreate conditioninwhichmoldcangrowinyour homeCertaintypesof. moldhavebeenreportedtocauserespi- ratoryproblemsorotherserioushealthrisksRemedialactions,. includingimmediatelydryingallwetitems,shouldbetakenquick- lytohelppreventthedevelopmentofmoldinyourhome.

Ifthe structure will be unattended during cold weather you should take these precautions.

Turn off the water supply to the structure and drain the wa- ter lines if possible and add an antifreeze for potable water to drain traps and toilet tanks. Open faucets in appropriate areas.

-or-

Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Instruct them on a service agency to call to provide service, if required.

-or-

3.Install a reliable remote sensing device that will notify somebody of freezing conditions within the home.

Winter Shutdown

If you go away during the winter months and do not leave the heat on in your home, the plastic transition box and the condensate trap on the furnace must be protected from freeze damage.(See Figure 8 trough Figure 17)

1.Disconnect the 5/8" OD rubber hose from the vent drain fit-

ting that is located downstream of the combustion blower. Insert a funnel into the hose and pour four(4) ounces of sanitary type (RV) antifreeze into the condensate trap. Re- connect the 5/8" OD rubber hose to the stub on the vent drain fitting. Secure with the hose clamp.

2.Disconnect the 3/4" OD rubber hose from the condensate trap. Insert a funnel into the hose and and pour four(4) ounces of sanitary type (RV) antifreeze into the plastic Transition box. Squeeze the hose together near the end and quickly reconnect the 3/4" OD rubber hose to the stub on the condensate trap. Secure with the hose clamp.

When you return home, your furnace will be ready to start, as it is not necessary to drain the antifreeze from the furnace.

2. Installation

CARBON MONOXIDE POISONING HAZARD

Failure to properly vent this furnace or other appliances

can result in death, personal injury and/or property damage.

This furnace can NOT be common vented or connected to

any type B, BW or L vent or vent connector, nor to any

portion of a factory-built or masonry chimney. If this

furnace is replacing a previously common-vented

furnace, it may be necessary to resize the existing vent

and chimneyto prevent oversizing problems for the other

remaining appliance(s). See Venting and Combustion Air

Check in Gas Vent Installation section. This furnace MUST be vented to the outside.

Location and Clearances

4. RefertoFigure lorFigure 2fortypicalinstallationandba-

sic connecting parts required. Refer to Figure 4 for typical

horizontal direct vent installation and basic connecting parts required. Supply and return air plenums and duct are also required.

5.If furnace is a replacement, it is usually best to install the furnace where the old one was. Choose the location or

evaluate the existing location based upon the minimum

clearance and furnace dimensions (Figure 3).

CAUTION

Special precautions MUST be made if installing furnace in an

area which may drop below freezing. This can cause

improper operation or damage to equipment. If furnace

environment has the potential of freezing, the drain trap and

drainline must be protected. The use of electric heat tape or

RV antifreeze is recommended for these installations. (See

"Condensate Trap Freeze Protection Section ")

Do NOT operate furnace in a corrosive atmosphere

containing chlorine, fluorine or any other damaging

chemicals. Refer to Combustion & Ventilation Air section,

Contaminated Combustion Air.

 

Typical Upflow

Installation

 

Aluminum or non-rusting shield recommended. (See

 

Vent Termination Shielding for dimensions).

8" Min. _

_lnletPipe

Couplingon endsol

-

_ _

(not used on

exhaust pipe.Total

Insame

_

Single Pipe

pipe& coupling out-

20'Max.

<_>

model)

atmospheric

 

zone

 

 

 

8"

Min.

Max.

ame atmospheric

zone

Increase minimum from 8" to 18" for cold climates (sustained temperatures

below 0 o F).

25-23-33

44001 111400

[_

Image 5
Contents SingleStage MP D 0 75 F 12 a # Denotes BrandJellJill 440 01 1114CO2 ? Furnace/Drip- Leg? YESDate of Start-Up Frozen and Burst Water Pipe Hazard Frozen Water Pipe HazardTypical Upflow Installation InstallationLocation and Clearances Winter ShutdownInstallation Positions Installation RequirementsFurnace Installation Considerations LevelingVENTrgMPD Dimensions & ClearancesAiRI.TAKE TOPAir Openings and ConnectingDucts Combustion & Ventilation Air For Single Pipe InstallationHorizontal Furnace Installation Confined Space Installation RequirementsFree Area Unconfined Space InstallationEhr Vent Check Venting and Combustion Air CheckMake the Following Check HoodSingle Pipe N9MP1 Models Vent and Combustion Air PipingDirect Vent N9MP2 Models Dual Certified gMPDModelsSizing Combustion Air and Vent Pipe Piping Insulation GuidelinesPipe Diameter Table N9MP2 Models Vent Termination ClearancesCondensate Drain Trap Freeze Protection Condensate Drain TrapUnited States Only Canada See Canadian Fuel Gas Code OtherThanYellowPlasticCap Upflow Installations Dual Certified *9MPD-A4 ModelsDrainLine TransitionDrain SomemodelsMountingScrews4 Dual Certified *9MPD-A4 HorizontalLeft InstallationsModels 25-24-12Si.g.Pre...reSwitch Switch HoseRpeept.oT \ e.spre X3L/\Page ReturnAir Page Left Side Venting Stubonthecondensatetrapandsecurewitha3/4clamp Satetrapandsecurewitha3/4clamp Boxandsecurewitha3/4clampDrainstubonthetransitionandsecurewitha3/4clamp Return Air VentFitting TPipe & ClampsInlet Cap Modelsshownhave TwopressureswitchesReturn Air ClampsLeft Combustion Air Pipe Connection Dual Certified or Connecting Vent and Combustion Air PipingVent Pipe Connection PVCVent Pipe Proper Sealing Procedure for Combustion BlowerHorizontal Termination Checkholesizesbymakingsureitissmallerthan the cou Using Exterior RisersVertical Termination Vent Termination ShieldingConcentric Vent and Combustion Air Sidewall Termination Ei271Recommended Alternate Installation for Sustained ColdSidewall Inlet Vent and Exhaust Air Termination Rooftop Inlet Vent and Exhaust Air TerminationAlternate Btuh Input RatingsUSA Only Manifold Gas Pressure AdjustmentSupplyPressure Gas Supply PressureChanging Orifices for High Altitude High Altitude Air Pressure SwitchGeneral Derating Rules Changing OrificesExample Natural Gas Input Rating CheckTypical Gas Piping for Upflow Power SupplyWiring Electrical WiringHumidifier/Electronic Air Cleaner Gas Piping RequirementsFan Delay DIP Switch Settings InstallationFan Timer Connections Ductwork and FilterSizing Filter Installation using Optional Filter RackInsulation FiltersAvailablefromyourdistributor StandoffFilterRack Combustible Floor InstallationAddition Of Air Conditioning Ubbase for Combustible FloorCoil Cabinet Furnace SubbaseAdjust Pilot Burner Checks and AdjustmentsTemperature Rise Check Main Burner Flame CheckHeating and Continuous BlowerSpeed the Same Tochecktemperaturerise,usethefollowingprocedureChanging Blower Speed Continuous Fan OperationCirculating Fan G Request Gas Valve Diagnostic Codes See FigureHeating Request with Gas Supply Line Shut Off OFFTypical Gas Valve Honeywell Honeywell SV9541M Flashes Honeywell SV9541M Smart Valve Trouble shootingFlashes + Flashes + SoftLockoutConcentric Vent Termination Kit # Concentric TerminationVent Termination Clearances Concentric Vent Roof Installation ArerequiredtocompletetheinstallationConcentric Vent and Combustion Air Side Termination Rain Cap to Vent Pipe AssemblyConcentric Termination Kit NAHA001CV & NAHA002CV Venting 25-22-02 Concentric Vent Sidewall Attachment440011114O0 N9MP2100F14A4 N9MP2100J20A4 N9MP2125J20A4 N9MP2075B12A4 N9MP2080F16A4Save This Manual For Future Reference Denotes BrandGeneral Specifications N9MP1Snap HW HSP Hwhsp Specifications N9MP2NAHA001LV NAHAO01LV NAHA002LV PSC/I/2 PSC/II2NAHA00SLV Specifications 9MPD3OO For 100 Models Ton 19 & 22314 Units For 075 Models 3 Ton UnitsFor 100 Models 5 Ton 223/4 Units For 125 Models 5 Ton UnitsDisconnect Before Servicing Ladder Diagram Connection DiagramD22 = = =@O,cFF18 25-23-95Functional Key Description Part125J 100J 125JIoof O50B 075B 080F LOOF LOOJ 125JLOOJ 125J Non-Functional Number 12A 1GANgMP1 050B 075B 080F 100F 100J 125J Number KeyDescription No. Non-Functional100F 100J 16A 14A 20AHeat Exchanger,Primary Heat Exchanger,Secondary KeyDescription No.FunctionalGMPD Number 050F12AKeyDescription No.Non- Functional 080J16A Models *9MPDO50F12A4, Natural Gas Replacement part suppliedKey Description Non-FunctionalNon- Functional Number

9MPD, N9MP1, N9MP2 specifications

The Sears N9MP2, N9MP1, and 9MPD are prominent models in the realm of residential heating systems, specifically designed to provide efficient and effective heating solutions. These models are part of Sears' commitment to quality and innovation, making them a popular choice among homeowners seeking reliability and performance.

The N9MP2 is a high-efficiency multi-speed gas furnace that boasts an impressive AFUE (Annual Fuel Utilization Efficiency) rating. This feature allows the furnace to convert a significant portion of fuel into usable heat, which effectively translates to lower energy bills for homeowners. The unit is equipped with a two-stage gas valve that provides increased comfort by adjusting the heating output based on demand, ensuring an even temperature throughout the home.

The N9MP1, like its counterpart, is known for its reliability and efficiency. It offers a single-stage operation that is ideal for homes needing consistent heating without the necessity for the more complex stages present in two-stage systems. This model also has a good AFUE rating, making it a cost-effective solution for families looking to reduce their heating expenses. Its design is tailored for easy installation and maintenance, allowing homeowners to keep their heating systems running at optimal performance without hassle.

The 9MPD model takes a step further with its advanced technology integration. It features a sophisticated control board that allows for easier diagnostics and enhanced system management. The 9MPD is also designed with quiet operation in mind, employing advanced sound-reduction technologies to minimize noise levels during heating cycles. Homeowners will appreciate the peace and quiet it brings, particularly in shared living spaces.

All three models are equipped with high-quality insulation and specialized heat exchangers that enhance their thermal efficiency. Additionally, they are designed with safety features such as automatic shut-off systems and robust flame rollout protection, ensuring a safe heating experience.

In terms of characteristics, these models are generally constructed with durable materials, designed to endure harsh weather conditions while providing consistent heating. They can be connected to various home automation systems, which adds to their appeal for tech-savvy consumers.

In conclusion, the Sears N9MP2, N9MP1, and 9MPD represent a comprehensive lineup of reliable, efficient, and technologically advanced heating systems suitable for contemporary homes. Their dedication to performance ensures that homeowners enjoy a warm and energy-efficient environment throughout the chilly seasons.