Sears 9MPD, N9MP2, N9MP1 manual

Page 20

that are provided. If needed, remove the hole plugs from the fur- nace side panel and relocated to the open set of holes in the oppo- site side panel.

NOTE: All gaskets and seals must be in place for sealed combus- tion applications.

For both right and left side vent, remove the 90 ° elbow from the vent fitting by loosening the clamp on the vent fitting.

Ensure that the vent fitting is securely attached to the combustion blower using the rubber coupling and clamps.

Connect the PVC vent extension pipe to the vent fitting. This pipe

has a built-in channel to assist vent condensate disposal. Align the arrow on the PVC pipe with the airflow marking arrow on the vent fitting. See label on the PVC pipe for proper installation. This pipe may only be shortened if an elbow is used to connect the

PVC vent extension tube to field-installed vent pipe. Securely at- tach the PVC vent extension pipe to the vent fitting with the cla rap.

This configuration allows left side venting from the furnace. If right side venting is required, the combustion blower must be relocated on the plastic transition box. Loosen the four(4) screws that se-

cure the blower to the transition approximately 1/2". Rotate the blower 180 ° and secure with the four(4) screws. Note that some combustion blowers have plastic spacers on the mounting legs of the blower located at the 6 and 12 o'clock positions (blower snout to the left or right) that are required for proper fit up of the blower to the transition. Use caution to not over tighten the screws to pre- vent stripping out of the plastic mounting holes.

NOTE: The vent fitting MUST be installed with the airflow marking arrow pointed toward the vent pipe, with the drain stub at a 5 ° to 10 ° downward slope.

Plug the upper drain stub on the vent fitting with the yellow plastic cap.

Connect the PVC vent extension pipe to the vent fitting. This pipe

has a built-in channel to assist vent condensate disposal. Align the arrow on the PVC pipe with the airflow marking arrow on

the vent fitting. See label on the PVC pipe for proper installation. This pipe may only be shortened if an elbow is used to connect the

PVC vent extension tube to field-installed vent pipe. Securely at- tach the PVC vent extension pipe to the vent fitting with the clamp.

Remove the pressure switch hose from the upper stub on the plastic transition box.

Relocate the plastic caps on the stubs of the plastic transition box from the lower stubs to the upper stubs and secure tightly with the clamps.

Route the pressure switch hose to the lower stub on the plastic transition box. Cut off excess hose and discard. Connect the pres- sure switch hose to the lower stub on the plastic transition box. NOTE: Failure to correctly install the pressure switch hose to the transition box can adversely affect the safety control operation.

Connect the 3/4" OU rubber hose with the 90 ° bend to the drain stub on the bottom of the plastic transition box and secure with a 3/4" clamp.

Route the hose to the large drain stub on the condensate trap. Cut off excess hose and discard. Connect the hose to the drain stub

on the transition and secure with a 3/4" clamp.

Connect the 518" OD rubber hose with the 90 ° bend to the lower drain stub on the vent fitting and secure with a 518" clamp.

Route the hose to the smaller stub on the condensate trap. Cut off excess hose and discard. Connect the hose to the drain stub on

the trap and secure with a 5/8" clamp.

For left side or right side mounted condensate trap, the pres-

sure tap on the condensate trap MUST be connected to the un- used pressure tap located on the top of the plastic transition box. Remove the plastic caps from the pressure taps on the conden- sate trap and the plastic transition and connect the 5/16" OD rub- ber hose. (See Figure 12)

NOTE: Route hoses to the condensate trap with no kinking or

binding for proper condensate drainage.

[_

44001 111400

Image 20
Contents SingleStage Denotes Brand MP D 0 75 F 12 a #JellJill 440 01 1114CO2 ? Furnace/Drip- Leg? YESDate of Start-Up Frozen Water Pipe Hazard Frozen and Burst Water Pipe HazardInstallation Typical Upflow InstallationLocation and Clearances Winter ShutdownInstallation Requirements Installation PositionsFurnace Installation Considerations LevelingDimensions & Clearances VENTrgMPDAiRI.TAKE TOPCombustion & Ventilation Air For Single Pipe Installation Air Openings and ConnectingDuctsHorizontal Furnace Installation Confined Space Installation RequirementsFree Area Unconfined Space InstallationEhr Venting and Combustion Air Check Vent CheckMake the Following Check HoodVent and Combustion Air Piping Single Pipe N9MP1 ModelsDirect Vent N9MP2 Models Dual Certified gMPDModelsPiping Insulation Guidelines Sizing Combustion Air and Vent PipePipe Diameter Table N9MP2 Models Vent Termination ClearancesCondensate Drain Trap Condensate Drain Trap Freeze ProtectionUnited States Only Canada See Canadian Fuel Gas Code OtherThanUpflow Installations Dual Certified *9MPD-A4 Models YellowPlasticCapDrainLine TransitionDrain SomemodelsMountingScrews4 HorizontalLeft Installations Dual Certified *9MPD-A4Models 25-24-12 Switch Hose Si.g.Pre...reSwitch Rpeept.oT \ e.spre X3L/\Page ReturnAir Page Left Side Venting Stubonthecondensatetrapandsecurewitha3/4clamp Satetrapandsecurewitha3/4clamp Boxandsecurewitha3/4clampDrainstubonthetransitionandsecurewitha3/4clamp Return Air VentFitting TPipe & ClampsInlet Modelsshownhave Twopressureswitches CapReturn Air ClampsLeft Connecting Vent and Combustion Air Piping Combustion Air Pipe Connection Dual Certified orVent Pipe Connection PVCVent Pipe Proper Sealing Procedure for Combustion BlowerHorizontal Termination Using Exterior Risers Checkholesizesbymakingsureitissmallerthan the couVertical Termination Vent Termination ShieldingEi271Recommended Alternate Installation for Sustained Cold Concentric Vent and Combustion Air Sidewall TerminationSidewall Inlet Vent and Exhaust Air Termination Rooftop Inlet Vent and Exhaust Air TerminationManifold Gas Pressure Adjustment Alternate Btuh Input RatingsUSA OnlySupplyPressure Gas Supply PressureHigh Altitude Air Pressure Switch Changing Orifices for High AltitudeGeneral Derating Rules Changing OrificesExample Natural Gas Input Rating CheckTypical Gas Piping for Upflow Electrical Wiring Power SupplyWiringHumidifier/Electronic Air Cleaner Gas Piping RequirementsInstallation Fan Delay DIP Switch SettingsFan Timer Connections Ductwork and FilterFilter Installation using Optional Filter Rack SizingInsulation FiltersCombustible Floor Installation Availablefromyourdistributor StandoffFilterRackAddition Of Air Conditioning Ubbase for Combustible FloorFurnace Subbase Coil CabinetChecks and Adjustments Adjust Pilot BurnerTemperature Rise Check Main Burner Flame CheckTochecktemperaturerise,usethefollowingprocedure Heating and Continuous BlowerSpeed the SameChanging Blower Speed Continuous Fan OperationGas Valve Diagnostic Codes See Figure Circulating Fan G RequestHeating Request with Gas Supply Line Shut Off OFFTypical Gas Valve Honeywell Honeywell SV9541M Honeywell SV9541M Smart Valve Trouble shooting FlashesFlashes + Flashes + SoftLockoutConcentric Vent Termination Kit # Concentric TerminationVent Termination Clearances Arerequiredtocompletetheinstallation Concentric Vent Roof InstallationConcentric Vent and Combustion Air Side Termination Rain Cap to Vent Pipe AssemblyConcentric Termination Kit NAHA001CV & NAHA002CV Venting Concentric Vent Sidewall Attachment 25-22-02440011114O0 N9MP2075B12A4 N9MP2080F16A4 N9MP2100F14A4 N9MP2100J20A4 N9MP2125J20A4Save This Manual For Future Reference Denotes BrandSpecifications N9MP1 GeneralSpecifications N9MP2 Snap HW HSP HwhspNAHA001LV NAHAO01LV NAHA002LV PSC/I/2 PSC/II2NAHA00SLV Specifications 9MPD3OO For 075 Models 3 Ton Units For 100 Models Ton 19 & 22314 UnitsFor 100 Models 5 Ton 223/4 Units For 125 Models 5 Ton UnitsConnection Diagram Disconnect Before Servicing Ladder DiagramD22 = = =@O,c25-23-95 FF18Key Description Part Functional125J 100J 125JO50B 075B 080F LOOF LOOJ 125J IoofLOOJ 125J Non-Functional Number 12A 1GAKeyDescription No. Non-Functional NgMP1 050B 075B 080F 100F 100J 125J Number100F 100J 16A 14A 20AKeyDescription No.Functional Heat Exchanger,Primary Heat Exchanger,SecondaryGMPD Number 050F12AKeyDescription No.Non- Functional Models *9MPDO50F12A4, Natural Gas Replacement part supplied 080J16ANon-Functional Key DescriptionNon- Functional Number