Sears N9MP1, N9MP2, 9MPD manual Concentric Termination Kit NAHA001CV & NAHA002CV Venting

Page 46

Concentric Termination Kit

NAHA001CV & NAHA002CV Venting

....

Table for N9MP2 Models

50,000

& 80,000 Btuh Furnaces

NAHA002CV - 35'& (4) 90 ° elbows with 2" PVC pipe or NAHA001CV - 65'& (4) 90° elbows with 3" PVC pipe

75,000 Btuh Furnaces

NAHA002CV - 20'& (2) 90 ° elbows with 2" PVC pipe or NAHA002CV - 35'& (4) 90° elbows with 2" PVC pipe & Long Vent Kit (See Tech. Manual) or

NAHA001CV - 65'& (4) 90 ° elbows with 3" PVC pipe

100,000 Btuh Furnace

NAHA001CV - 35'& (4) 90° elbows with 3" PVC pipe or NAHA001CV - 65'& (4) 90 ° elbows with 3" PVC pipe & Long Vent Kit (See Tech. Manual)

125,000 Btuh Furnace

NAHA001CV - 35'& (4) 90° elbows with 3" PVC pipe

1.Do not include the field supplied 45 ° elbow in the total elbow count,

2.If more than four elbows are required, reduce the length of

both the inlet and the exhaust pipes five feet for each additional elbow used.

3. Elbows are DWV long radius type for 2" and 3" vents,

NOTE: Feet of pipe is whichever pipe run is the longest, either inlet or outlet side,

If assembly needs to be extended to meet height or side wall

thickness requirement, the two pipes supplied in the kit may be replaced by using the same diameter solid, single (no coupling

connections) field supplied SDR-26 PVC (ASTM D2241) pipes. Do not extend dimension D more than 60". (See Figure 46)

Do not use field supplied couplings to extend the pipes.

Airflow restriction will occur and the furnace pressure

switch may cause intermittent operation.

Partially assemble the concentric vent termination kit. Clean and cement the parts using the procedures for Join- ing Pipe and Fittings section of the manual. A) Cement the

Y Concentric fitting to the 4" diameter kit pipe. (See Figure 47) B) Cement the 3" rain cap to the 21/2 " diameter

kit part. (See Figure 47) NOTE: A field supplied stainless steel screw may be used to secure the rain cap to the pipe

instead of cementing when field disassembly is desired for cleaning (See Figure 47)

Rain Cap to Vent Pipe Assembly

Drill clearance hole in rain

cap and pilot hole in vent pipe.

Stainless steel screw (Field supplied)

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in death,

personal injury and/or property damage.

When using the alternate screw assembly method, drill a

clearance hole in the rain cap and a pilot hole in the vent pipe for the screw size being used. Failure to drill

adequate holes may cause cracking of the PVC

components, allowing flue gases to be recirculated.

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in death,

personal injury and/or property damage.

Do not operate the furnace with the rain cap removed as

recirulation of the flue gases may occur. Water may also

collect inside the larger combustion air pipe and flow to the burner enclosure.

Install the Y concentric fitting and the pipe assembly through the structure's hole. For vertical termination, install the parts through the field supplied roof boot/flashing.

NOTE: Do not allow insulation or other materials to accu-

mulate inside the pipe assembly when installing through the structure's hole.

Secure the assembly to the structure as shown in Figure 45 or Figure 49 using field supplied metal strap- ping or equivalent material.

NOTE: Ensure the termination height is above the roof sur-

face or anticipated snow level as shown in Figure 45 for

vertical termination. Ensure the termination location clear-

ance dimensions are as shown in Figure 48 and Figure 49 for horizontal termination.

Concentric Vent and Combustion-

Air Side Termination

Roof Overhang

Maintain 12" clearance above highest antici-

pated snow level or grade whichever is great-

er.25-22-02

[_

44001111400

Image 46
Contents SingleStage JellJill Denotes BrandMP D 0 75 F 12 a # 440 01 1114Date of Start-Up Furnace/Drip- Leg? YESCO2 ? Frozen Water Pipe Hazard Frozen and Burst Water Pipe HazardLocation and Clearances InstallationTypical Upflow Installation Winter ShutdownFurnace Installation Considerations Installation RequirementsInstallation Positions LevelingAiRI.TAKE Dimensions & ClearancesVENTrgMPD TOPHorizontal Furnace Installation Combustion & Ventilation Air For Single Pipe InstallationAir Openings and ConnectingDucts Confined Space Installation RequirementsEhr Unconfined Space InstallationFree Area Make the Following Check Venting and Combustion Air CheckVent Check HoodDirect Vent N9MP2 Models Vent and Combustion Air PipingSingle Pipe N9MP1 Models Dual Certified gMPDModelsPipe Diameter Table N9MP2 Models Piping Insulation GuidelinesSizing Combustion Air and Vent Pipe Vent Termination ClearancesUnited States Only Condensate Drain TrapCondensate Drain Trap Freeze Protection Canada See Canadian Fuel Gas Code OtherThanDrainLine Upflow Installations Dual Certified *9MPD-A4 ModelsYellowPlasticCap TransitionMountingScrews4 SomemodelsDrain Models HorizontalLeft InstallationsDual Certified *9MPD-A4 25-24-12Rpeept.oT Switch HoseSi.g.Pre...reSwitch \ e.spre X3L/\Page ReturnAir Page Left Side Venting Drainstubonthetransitionandsecurewitha3/4clamp Satetrapandsecurewitha3/4clamp Boxandsecurewitha3/4clampStubonthecondensatetrapandsecurewitha3/4clamp Inlet VentFitting TPipe & ClampsReturn Air Return Modelsshownhave TwopressureswitchesCap Air ClampsLeft Vent Pipe Connection Connecting Vent and Combustion Air PipingCombustion Air Pipe Connection Dual Certified or PVCHorizontal Termination Proper Sealing Procedure for Combustion BlowerVent Pipe Vertical Termination Using Exterior RisersCheckholesizesbymakingsureitissmallerthan the cou Vent Termination ShieldingSidewall Inlet Vent and Exhaust Air Termination Ei271Recommended Alternate Installation for Sustained ColdConcentric Vent and Combustion Air Sidewall Termination Rooftop Inlet Vent and Exhaust Air TerminationSupplyPressure Manifold Gas Pressure AdjustmentAlternate Btuh Input RatingsUSA Only Gas Supply PressureGeneral Derating Rules High Altitude Air Pressure SwitchChanging Orifices for High Altitude Changing OrificesTypical Gas Piping for Upflow Natural Gas Input Rating CheckExample Humidifier/Electronic Air Cleaner Electrical WiringPower SupplyWiring Gas Piping RequirementsFan Timer Connections InstallationFan Delay DIP Switch Settings Ductwork and FilterInsulation Filter Installation using Optional Filter RackSizing FiltersAddition Of Air Conditioning Combustible Floor InstallationAvailablefromyourdistributor StandoffFilterRack Ubbase for Combustible FloorFurnace Subbase Coil CabinetTemperature Rise Check Checks and AdjustmentsAdjust Pilot Burner Main Burner Flame CheckChanging Blower Speed Tochecktemperaturerise,usethefollowingprocedureHeating and Continuous BlowerSpeed the Same Continuous Fan OperationHeating Request with Gas Supply Line Shut Off Gas Valve Diagnostic Codes See FigureCirculating Fan G Request OFFTypical Gas Valve Honeywell Honeywell SV9541M Flashes + Honeywell SV9541M Smart Valve Trouble shootingFlashes Flashes + SoftLockoutVent Termination Clearances Concentric TerminationConcentric Vent Termination Kit # Arerequiredtocompletetheinstallation Concentric Vent Roof InstallationConcentric Termination Kit NAHA001CV & NAHA002CV Venting Rain Cap to Vent Pipe AssemblyConcentric Vent and Combustion Air Side Termination Concentric Vent Sidewall Attachment 25-22-02440011114O0 Save This Manual For Future Reference N9MP2075B12A4 N9MP2080F16A4N9MP2100F14A4 N9MP2100J20A4 N9MP2125J20A4 Denotes BrandSpecifications N9MP1 GeneralNAHA001LV NAHAO01LV NAHA002LV Specifications N9MP2Snap HW HSP Hwhsp PSC/I/2 PSC/II23OO Specifications 9MPDNAHA00SLV For 100 Models 5 Ton 223/4 Units For 075 Models 3 Ton UnitsFor 100 Models Ton 19 & 22314 Units For 125 Models 5 Ton UnitsD22 Connection DiagramDisconnect Before Servicing Ladder Diagram = = =@O,c25-23-95 FF18125J Key Description PartFunctional 100J 125JLOOJ 125J Non-Functional Number 12A O50B 075B 080F LOOF LOOJ 125JIoof 1GA100F 100J KeyDescription No. Non-FunctionalNgMP1 050B 075B 080F 100F 100J 125J Number 16A 14A 20AGMPD Number KeyDescription No.FunctionalHeat Exchanger,Primary Heat Exchanger,Secondary 050F12AKeyDescription No.Non- Functional Models *9MPDO50F12A4, Natural Gas Replacement part supplied 080J16ANon- Functional Non-FunctionalKey Description Number

9MPD, N9MP1, N9MP2 specifications

The Sears N9MP2, N9MP1, and 9MPD are prominent models in the realm of residential heating systems, specifically designed to provide efficient and effective heating solutions. These models are part of Sears' commitment to quality and innovation, making them a popular choice among homeowners seeking reliability and performance.

The N9MP2 is a high-efficiency multi-speed gas furnace that boasts an impressive AFUE (Annual Fuel Utilization Efficiency) rating. This feature allows the furnace to convert a significant portion of fuel into usable heat, which effectively translates to lower energy bills for homeowners. The unit is equipped with a two-stage gas valve that provides increased comfort by adjusting the heating output based on demand, ensuring an even temperature throughout the home.

The N9MP1, like its counterpart, is known for its reliability and efficiency. It offers a single-stage operation that is ideal for homes needing consistent heating without the necessity for the more complex stages present in two-stage systems. This model also has a good AFUE rating, making it a cost-effective solution for families looking to reduce their heating expenses. Its design is tailored for easy installation and maintenance, allowing homeowners to keep their heating systems running at optimal performance without hassle.

The 9MPD model takes a step further with its advanced technology integration. It features a sophisticated control board that allows for easier diagnostics and enhanced system management. The 9MPD is also designed with quiet operation in mind, employing advanced sound-reduction technologies to minimize noise levels during heating cycles. Homeowners will appreciate the peace and quiet it brings, particularly in shared living spaces.

All three models are equipped with high-quality insulation and specialized heat exchangers that enhance their thermal efficiency. Additionally, they are designed with safety features such as automatic shut-off systems and robust flame rollout protection, ensuring a safe heating experience.

In terms of characteristics, these models are generally constructed with durable materials, designed to endure harsh weather conditions while providing consistent heating. They can be connected to various home automation systems, which adds to their appeal for tech-savvy consumers.

In conclusion, the Sears N9MP2, N9MP1, and 9MPD represent a comprehensive lineup of reliable, efficient, and technologically advanced heating systems suitable for contemporary homes. Their dedication to performance ensures that homeowners enjoy a warm and energy-efficient environment throughout the chilly seasons.