Isle Royale Wood Stove
4Installation Considerations
A. Hearth Protection Requirements
FLOOR PROTECTION: Floor protector must be non- combustible material, extending beneath heater and to the front, sides and rear as indicated. The fl oor must be non- combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers. A layer of thin brick or ceramic tile over a combustible fl oor is not suffi cient.
In US installations, it is necessary to install a fl oor protec- tor a minimum of 16 inches (406mm) in front of glass and 8 inches (203mm) to both sides of the fuel loading door. Open the door and measure 8 inches (203mm) from the side edge of the opening in the face of the appliance. *See exception.
In Canada, similar fl oor protection must be provided 18 inches (457mm) in front and 8 inches (203mm) from the sides and rear of the stove. *See exception.
*EXCEPTION:
See Figure 11.4.
WARNING
FIRE RISK.
•Hearth pads must be installed exactly as specified.
High temperatures or hot embers may ignite concealed combustibles.
Fuel loading door |
Minimum |
16" from glass - std legs |
8" |
USA |
Minimum |
Figure 11.1
|
|
| 51" |
| ||
| coverage |
|
|
| optional | |
|
|
|
| |||
|
|
|
| coverage | ||
36 |
|
|
|
| ||
optional |
|
|
|
|
| |
|
|
| loading | door | 8” | |
|
|
|
| |||
51" |
| fuel |
|
| ||
|
|
|
| |||
|
|
|
|
| ||
|
|
|
| 16" | coverage | |
optional | required | |||||
38 |
| |||||
| 30 | |||||
coverage |
|
|
| |||
|
|
|
| |||
USA Installations |
|
|
|
|
Figure 11.3
| 203mm (8") |
|
203mm | 203mm | 1219mm |
(8") | (8") | |
|
| (48") |
|
| Minimum |
| 457mm (18") |
|
| CANADA |
|
| 1137mm |
|
| Minimum |
|
Figure 11.2
must extend length of flue and 2" (51mm) beyond each side of pipe
USA - Required
CANADA - Recommended
Figure 11.4
November 22, 2011 | Page 11 | |
|
|