Enviro 1700 Fireplace Freestanding † From front of door opening to edge of floor protection

Page 13

Specifications

CLEARANCES TO COMBUSTIBLES - 1200 INSERT:

Table 3: 1200 Insert Clearance to Combustibles.

A

Minimum clearance to an unshielded side wall

10” (254 mm)

����

 

 

B

Minimum clearance to an unshielded 8” (203 mm) mantle

21” (533 mm)

 

 

 

C

Minimum top facing (protruding 3⁄4” [19 mm]) clearance

171⁄2” (445 mm)

��������

E

† From front of door opening to edge of floor protection

USA 16” (406 mm)

 

D

Minimum side facing (protruding 3⁄4” [19 mm]) clearance

1” (25 mm)

 

 

 

 

CND 18” (450 mm)

 

 

 

F

† From side/back of unit to edge of floor protection

USA 6” (152 mm)

 

 

 

 

CND 8” (200 mm)

 

 

 

 

 

FLOOR PROTECTION:

If unit is raised 0” - 2” (0mm-51mm); 1” (25mm) non-combustible material with k value = 0.84 or equivalent.

If unit is raised 2” - 8” (51mm-203mm); 1⁄2” (13mm) non-combustible material with k value = 0.84 or equivalent. If unit is raised greater than 8” (203 mm) or more; any non-combustible material can be used.

Table 4: 1200 Insert Minimum Fireplace Size.

 

Masonry

Zero Clearance

 

 

 

Minimum Depth

131⁄2” (343mm)

14” (279mm)

 

 

 

Minimum Width at back of fireplace

223⁄8” (568mm)

23” (584mm)

 

 

 

Minimum Width at front of fireplace

27” (686mm)

271⁄4” (692mm)

 

 

 

Minimum Width at front of fireplace to include shroud

333⁄4” (857mm)

34” (864mm)

 

 

 

Minimum Height

191⁄4” (489mm)

20” (508mm)

 

 

 

CLEARANCES TO COMBUSTIBLES - 1700 INSERT:

Table 5: 1700 Insert Clearance to Combustibles.

A

Minimum clearance to an unshielded side wall

10”

(254 mm)

 

 

 

 

B

Minimum clearance to an unshielded 8” (203 mm) mantle

24”

(610 mm)

 

 

 

C

Minimum top facing (protruding 3⁄4” [19 mm]) clearance

191⁄2” (495 mm)

 

 

 

 

D

Minimum side facing (protruding 3⁄4” [19 mm]) clearance

1”

(25 mm)

 

 

 

E

† From front of door opening to edge of floor protection

USA 16” (406 mm)

 

 

CND 18” (450 mm)

 

 

 

F

† From side of unit to edge of floor protection

USA 6” (152 mm)

 

 

CND 8” (200 mm)

 

 

 

 

����

��������

 

 

 

 

 

FLOOR PROTECTION:

If unit is raised 0” - 2” (0mm-51mm); 1” (25mm) non-combustible material with k value = 0.84 or equivalent.

If unit is raised 2” - 8” (51mm-203mm); 1⁄2” (13mm) non-combustible material with k value = 0.84 or equivalent. If unit is raised greater than 8” (203 mm) or more; any non-combustible material can be used.

Table 6: 1700 Insert Minimum Fireplace Size.

 

Masonry

Zero Clearance

 

 

 

Minimum Depth

18” (457mm)

181⁄2” (470mm)

 

 

 

Minimum Width at back of fireplace

223⁄8” (568mm)

23” (584mm)

 

 

 

Minimum Width at front of fireplace

27” (686mm)

271⁄4” (692mm)

 

 

 

Minimum Width at front of fireplace to include shroud

333⁄4” (857mm)

34” (864mm)

 

 

 

Minimum Height

191⁄4” (489mm)

20” (508mm)

 

 

 

13

Image 13
Contents Wood Stove Table of Contents Safety Precautions First Start Operating InstructionsReplacing the Glass Maintenance Helpful Hints Worth Repeating What does dry, seasoned wood mean? Air Control Rod 1200 Air Flow Path Specifications Capacity Feet3 0.0708 meter3 Approximate heating area † From front of door opening to edge of floor protection Maintain These Minimum Clearances to Unshielded Combustibles 1700 Freestanding Clearance to Combustibles 1200 Insert Dimensions 1700 Insert Dimensions 1200 Freestanding Flat Top Dimensions 1700 Freestanding Flat Top Dimensions 1200 Freestanding with Fan Kit Dimensions Bolts to remove InstallationInstalling Heat Shield Recommended Height for Flue Pipe Chimney Through Wall Method a Roof Clearances Any area within 10 feet Installation into a masonry chimney Venting Outside AIR Insert Installation into existing fireplace with Hearth Metal TAG this Fireplace has Been Before starting this type of installation 3D of Dimensions needed from Fireplace Insert Install into a Zero-Clearance Fireplace Total Bricks Tube C Tube B Tube a Do not USE Door if Glass is Broken Installation of Ceramic Baffle Back View of Freestanding Unit with Fan Kit Removal of right Pod Installation of Trim Parts List EFW-264 PartsDiagramFreestanding Parts Diagram Pedestals & Legs Parts Diagram Fireplace Insert Limited Five 5 Year Warranty Limited One 1 Year Warranty WarrantyExclusions and Limitations Warranty Installation Data Sheet