CHIMNEY INSTALLATION THROUGH WALL:

Here are four (4) methods of combustible wall chimney connector pass-throughs. Information was provided from NFPA 211.

Figure 20: Chimney Through Wall - Method A.

Figure 21: Chimney Through Wall - Method B.

Figure 22: Chimney Through Wall - Method C.

Method A. 12” (304.8 mm) Clearance to Combustible Wall Member: Using a minimum thickness 3.5” (89 mm) brick and a 5⁄8” (15.9 mm) minimum wall thickness clay liner, construct a wall pass-through. The clay liner must conform to ASTM C315 (Standard Specification for Clay Fire Linings) or its equivalent. Keep a minimum of 12” (305 mm) of brick masonry between the clay liner and wall combustibles. The clay liner shall run from the brick masonry outer surface to the inner surface of the chimney flue liner but not past the inner surface. Firmly grout or cement the clay liner in place to the chimney flue liner.

Method B. 9” (229 mm) Clearance to Combustible Wall Member: Using a 6” (152 mm) inside diameter, factory-built Solid-Pak chimney section with insulation of 1” (25.4 mm) or more, build a wall pass-through with a minimum 9” (229 mm) air space between the outer wall of the chimney length and wall combustibles. Use sheet metal supports, fastened securely to wall surfaces on all sides, to maintain the 9” (229

mm)air space. When fastening supports to chimney length, do not penetrate the chimney liner (the inside wall of the Solid-Pak chimney). The inner end of the Solid-Pak chimney section shall be flush with the inside of the masonry chimney flue and sealed with a non-water soluble refractory cement. Use this cement to also seal to the brick masonry penetration.

Method C. 6” (152.4 mm) Clearance to Combustible Wall Member: Starting with a minimum 24 gauge (.024” [0.6 mm]) 6” (152.4 mm) metal chimney connector and a minimum 24 gauge ventilated wall thimble which has two air channels of 1” (25.4 mm) each, construct a wall pass-through. There shall be a minimum 6” (152.4 mm) separation area containing fiberglass insulation, from the outer surface of the wall thimble to wall combustibles. Support the wall thimble and cover its opening with a 24 gauge minimum sheet metal support. Maintain the 6” (152.4 mm) space. There should also be a support sized to fit and hold the metal chimney connector. See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure the metal chimney connector do not penetrate chimney flue liner.

Method D. 2” (50.8 mm) Clearance to Combustible Wall Member:

Start with a solid-pak listed factory-built chimney section at least 12” (304 mm) long, with insulation of 1” (25.4 mm) or more, and an inside diameter of 8” (2” [51 mm] larger than the 6” [152.4 mm] chimney connector). Use this as a pass-through for a minimum 24 gauge single- wall steel chimney connector. Keep solid-pak section concentric with and spaced 1” (25.4 mm) off the chimney connector by way of sheet metal support plates at both ends of chimney section. Cover opening, and support chimney section on both sides, with 24 gauge minimum

sheet metal supports. See that the supports are fastened securely to

Figure 23: Chimney Through Wall - Method D. wall surfaces on all sides. Make sure fasteners are used to secure

chimney flue liner.

NOTES:

1.Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through system and the chimney wall, to but not past the inner flue liner face.

2.A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, or ceiling.

24

Image 24
Contents Wood Stove Table of Contents Safety Precautions Operating Instructions First StartReplacing the Glass Maintenance Helpful Hints Worth Repeating What does dry, seasoned wood mean? Air Control Rod 1200 Air Flow Path Specifications Capacity Feet3 0.0708 meter3 Approximate heating area † From front of door opening to edge of floor protection Maintain These Minimum Clearances to Unshielded Combustibles 1700 Freestanding Clearance to Combustibles 1200 Insert Dimensions 1700 Insert Dimensions 1200 Freestanding Flat Top Dimensions 1700 Freestanding Flat Top Dimensions 1200 Freestanding with Fan Kit Dimensions Installation Bolts to removeInstalling Heat Shield Recommended Height for Flue Pipe Chimney Through Wall Method a Roof Clearances Any area within 10 feet Installation into a masonry chimney Venting Outside AIR Insert Installation into existing fireplace with Hearth Metal TAG this Fireplace has Been Before starting this type of installation 3D of Dimensions needed from Fireplace Insert Install into a Zero-Clearance Fireplace Total Bricks Tube C Tube B Tube a Do not USE Door if Glass is Broken Installation of Ceramic Baffle Back View of Freestanding Unit with Fan Kit Removal of right Pod Installation of Trim Parts List EFW-264 PartsDiagramFreestanding Parts Diagram Pedestals & Legs Parts Diagram Fireplace Insert Warranty Limited Five 5 Year Warranty Limited One 1 Year WarrantyExclusions and Limitations Warranty Installation Data Sheet