Enviro C-10637, 50-1096 owner manual Venting Fireplace Inserts, Installation of Sienna DV and BV

Page 14

Initial Installation

QUALIFIED INSTALLERS ONLY

VENTING FIREPLACE INSERTS:

The ENVIRO SIENNA may be installed and vented into any solid fuel fireplace that has been installed in accordance with the National, Provincial/State and local building codes and has been constructed of non- combustible materials. Before starting refer to PREPARING YOUR SIENNA FOR INSTALLATION and CONVERTING A

DIRECT VENT FIREPLACE TO A B-VENT FIREPLACE.

An approved chimney liner and rain cap must be used. A throat connector or flashing must be installed to ensure a tight seal, top performance, safety and efficiency. Carefully follow the manufacturer’s instructions that accompany the chimney liner kit.

Remove the vent collar plate from the top of the insert and connect it securely with sheet metal screws and/or hose clamps. Check for any tears in the liner at this point. IMPORTANT: The screws that hold the vent collar plate in its approved position must be installed.

�� �����

Install sealed throat connector or flashing to prevent leakage of room air

up through chimney.

DV Only: Before installing vent

liners, mark each liner on both ends

to designate which is the intake and the exhaust.

Measure the height of the chimney

beforehand and purchase the

appropriate kit. Never attempt to over-

stretch a flexible liner to accommodate

the height of the chimney.

Any flue damper must be removed or

blocked permanently in the open

position.

The chimney must be clean, in good

working order and constructed of non-

combustible materials.

Make sure that all chimney cleanouts are tight fitting and will not permit air to leak into the chimney

�� �����

Figure 12: Installation of Sienna DV and BV.

14

Image 14
Contents What to do if YOU Smell GAS General Safety PrecautionsFor Your Safety Table of Contents Codes And Approvals Vented GAS Fireplace Heater Sienna BV/DV NG/LPGRating Label Location SpecificationsDimensions 33 x 46 84cm x 193 cm Pilot Light Operating InstructionsPilot Lighting Instructions Turn OFF Unit Remote Controls OptionalBurner Lighting Blower SpeedCleaning the Firebox Maintenance And ServiceCleaning the Glass Cleaning the Plated SurfacesTo be Installed by a Qualified Service Agency only Fuel ConversionInitial Installation Clearances to CombustiblesVent Model Automatic Flue GAS Spill Switch B-VENT Model only Minimum Fireplace SizePreparing Your Sienna for Installation Direct Vent ModelInstallation of Sienna DV and BV Venting Fireplace InsertsProng from this plug Electrical RequirementsGas Line Connection GAS Line ConnectionConverting a Direct Vent Fireplace to a B-VENT Fireplace Converting to a BV fireplaceSecondary Installation Replacing the BlowerInstallation of Surround Panel Door RemovalLOG SET and Ember Installation Empty firebox with grate and locator pinsThird Stage Log Set Installation Adjusting Venturi AIR Settings Never operate the fireplace with the glass door removedBrick panel set is fragile, handle with extreme care Removing the Brick PanelTrouble Shooting BV onlyParts List- Unit Components NumberComponentsDiagramParts Parts Diagram Burner Parts List Options Parts Diagram Options Warranty To the DealerInstallation Data Sheet