APC 40 130KVA user manual Setup and Installation, Location

Page 23

Setup and Installation

2.0Scope

Guides the user through performing connections required for initial installation. Included are the electrical specifi- cations and connection details.

2.1Location

To ensure correct ventilation, leave nothing on top of the UPS. Leave three feet of free space in front of the UPS for door opening.

The UPS cabinet rests on four levelers positioned in the four corners of the cabinet to spread the weight. The UPS must be installed in a room with restricted access (qualified personnel only).

Figure 2-1: Installation of UPS

86-174010-00 B00

Setup and Installation

2 — 1

Image 23
Contents MGE Galaxy Page Schneider Electric MGE GalaxyMGE Galaxy Important Safety InstructionsEnvironment This page left blank intentionally Contents Appendices MaintenanceWarranty and Product Registration Service Solutions Team Three Phase ProductsTables FiguresUPS Serial Number Special precautions Safety RulesSafety of persons Display Icons MGE Galaxy Symbol UsageDocument Icons Introduction Setup and InstallationMaintenance Section DescriptionsViii General Description IntroductionScope UPS power rating KVA Dimensions H x W x D MGE Galaxy 5000 UPS System with Battery Single Line DiagramInside MGE Galaxy 5000 UPS Cabinet Inside the UPS Cabinet, Access to ConnectionsUPS Cabinet Bottom View Layout Power Connection TerminalsUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Location Setup and InstallationLayout of Cabinets Electrical SpecificationsSingle UPS With Common Normal and Bypass AC Inputs Connection of Power Cables in a Single UPSUPS Can // interconnections Exchange-current interconnectionsInterconnections with the external system bypass cabinet Parallel Configuration for Increased Capacity Four UPSsXMB08 XMB07 XMB06 11 Adding Communication Cards Adding Communication Cards12 Connection of Relay Communication Card Connection of the Relay Communications CardCommunications Card Connection Example Characteristics of the input contactsGeneral-shutdown cable Routing the Control/Communications CablesSingle UPS Exchange-current cables Parallel UPSCan cables Shutting Down a Single UPS OperationLoad is protected by the UPS Shutting Down a Parallel ConfigurationRestarting a Single UPS Load is protected by the UPSs Restarting a Parallel ConfigurationSingle UPS Start Sequence on Bypass AC Input Operation of Mimic-Panel LEDsSingle UPS Start Sequence on Normal AC Input Operating Modes Load on Battery PowerFrequency Access to the Personalization FunctionsPersonalization Settings Operating Mode UPS PersonalizationDisplay Messages List Operation of the Relay Communication Card Dry Contacts Standard ModeProgrammable Mode Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Life Cycle Monitoring LCM MaintenanceIdentification of Alarms Battery powerLoad is no longer protected by the UPS UPS IsolationUPS Isolation Single UPS Parallel UPS Configuration Without External Bypass Cabinet Shutdown and isolation of all the UPSs Parallel UPS Configuration With External Bypass CabinetUPS starts automatically LED 31 is on Return to the Normal OperationReturn to Normal Single UPS Parallel UPS Configuration Without External Bypass Cabinet UPS restarts and LED 31 is on Restart the UPS for which all switches are set to OFFReturn to Normal Parallel UPS With External Bypass Cabinet Hz Training Center Servicing BatteriesTraining Center This page left blank intentionally Selection of Protection Devices A1 Electrical CharacteristicsAppendices Limitation Input/Output Characteristics Inverter Bypass AC inputLoad output A2 Maximum Allowable Power for Parallel UPS Units A3 UPS Cabinet Major Internal Components MGE -GalaxyA4 Available Options A5 Environment Page Product Information MGE Galaxy Warranty and Product RegistrationWarranty Extension Warranty+ User InformationReturn Policy for Repair of Three Phase Products RGA Technical Support and Product ServicesScheduling Field Service Engineer Support MGE Galaxy AWG GlossaryIgbt VAC MGE Galaxy Use this form Reorder Form Scenic Avenue Costa Mesa, CAPage Page Contact Information