APC 40 130KVA user manual Restarting a Single UPS, Shutting Down a Parallel Configuration

Page 36

MGE Galaxy 5000

3.2Restarting a Single UPS

Check that switches Q4S (9) and Q5N (11) are closed. If this is the case, continue with this procedure, otherwise refer to Section 4.4.1 "Return to the Normal Operation, Single UPS".

Figure 3-2: Restarting a Single UPS

35

1 - Set the Normal AC source input switch Q1 (8) to the ON position.

2 - Wait until the end of the start sequence.

3 - Set the battery circuit breaker of the auxiliary cabinets to the ON position.

The UPS starts automatically. LED (31) is ON.

The load is protected by the UPS.

If LED (31) remains OFF, press the ON button (37) (the UPS is in manual start mode) and confirm if necessary by pressing the function key (35) marked .

If LED (31) still remains OFF and either of LEDs (32) or (33) is ON, a fault has occurred (see Section 4.1).

3.3Shutting Down a Parallel Configuration

Figure 3-3: Shutting Down a Parallel Configuration

1 - Press a button on each unit to exit sleep mode.

2 - Press the OFF button (38) on each unit for 3 seconds.

The load is no longer protected by the UPSs. It is supplied via the bypass.

3 - Set the battery circuit breakers of the auxillary cabinets to the OFF position.

4 - Set the input switch Q1 (8) in each UPS to the OFF position.

The charger no longer operates to keep the batteries fully charged.

5 - Open the upstream circuit breakers of Normal AC source and Bypass AC source to completely power off the installation.

3 — 2

Operation

86-174010-00 B00

Image 36
Contents MGE Galaxy Page MGE Galaxy Schneider ElectricImportant Safety Instructions MGE GalaxyEnvironment This page left blank intentionally Contents Maintenance Warranty and Product RegistrationService Solutions Team Three Phase Products AppendicesFigures TablesUPS Serial Number Safety Rules Safety of personsSpecial precautions MGE Galaxy Symbol Usage Document IconsDisplay Icons Setup and Installation MaintenanceSection Descriptions IntroductionViii Introduction ScopeGeneral Description MGE Galaxy 5000 UPS System with Battery Single Line Diagram UPS power rating KVA Dimensions H x W x DInside the UPS Cabinet, Access to Connections Inside MGE Galaxy 5000 UPS CabinetPower Connection Terminals UPS Cabinet Bottom View LayoutUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Setup and Installation LocationElectrical Specifications Layout of CabinetsConnection of Power Cables in a Single UPS Single UPS With Common Normal and Bypass AC InputsUPS Exchange-current interconnections Can // interconnectionsParallel Configuration for Increased Capacity Four UPSs Interconnections with the external system bypass cabinetXMB08 XMB07 XMB06 Adding Communication Cards 11 Adding Communication CardsConnection of the Relay Communications Card 12 Connection of Relay Communication CardCharacteristics of the input contacts Communications Card Connection ExampleRouting the Control/Communications Cables Single UPSGeneral-shutdown cable Parallel UPS Can cablesExchange-current cables Operation Shutting Down a Single UPSShutting Down a Parallel Configuration Restarting a Single UPSLoad is protected by the UPS Restarting a Parallel Configuration Load is protected by the UPSsOperation of Mimic-Panel LEDs Single UPS Start Sequence on Normal AC InputSingle UPS Start Sequence on Bypass AC Input Load on Battery Power Operating ModesAccess to the Personalization Functions Personalization Settings Operating ModeUPS Personalization FrequencyDisplay Messages List Standard Mode Programmable ModeOperation of the Relay Communication Card Dry Contacts Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Maintenance Identification of AlarmsBattery power Life Cycle Monitoring LCMUPS Isolation UPS Isolation Single UPSLoad is no longer protected by the UPS Parallel UPS Configuration Without External Bypass Cabinet Parallel UPS Configuration With External Bypass Cabinet Shutdown and isolation of all the UPSsReturn to the Normal Operation Return to Normal Single UPSUPS starts automatically LED 31 is on Parallel UPS Configuration Without External Bypass Cabinet Restart the UPS for which all switches are set to OFF UPS restarts and LED 31 is onReturn to Normal Parallel UPS With External Bypass Cabinet Servicing Batteries Training CenterHz Training Center This page left blank intentionally A1 Electrical Characteristics AppendicesSelection of Protection Devices Limitation Input/Output Characteristics Bypass AC input Load outputInverter A2 Maximum Allowable Power for Parallel UPS Units MGE -Galaxy A3 UPS Cabinet Major Internal ComponentsA4 Available Options A5 Environment Page MGE Galaxy Warranty and Product Registration Warranty Extension Warranty+User Information Product InformationTechnical Support and Product Services Scheduling Field Service Engineer SupportReturn Policy for Repair of Three Phase Products RGA MGE Galaxy Glossary AWGIgbt VAC MGE Galaxy Reorder Form Scenic Avenue Costa Mesa, CA Use this formPage Page Contact Information