2.4Redundant Parallel Configuration (Maximum Two UPS Units for Pn)

These configurations do not have an external System Bypass Cabinet (SBC).

Figure 2-5: Parallel UPS With Common Normal and Bypass AC Inputs

UPS 1

UPS 2

14.56”

22

14.56”

22

 

 

Ground

To loadTo Load

To Normal / Bypass

 

AC Source

 

To access the connections, remove cover (see Section 1.3).

1 - The grounding conductors must be connected to the grounding-plate of each UPS (17).

2 - Connect the three phases of the bypass AC source to connection (15) in each UPS.

3 - Connect the three phases of the supplied loads to connection (14) in UPS1.

4 - Connect (14) in UPS2 to (14) in UPS1 using the three load conductors.

5 - Connect the external battery (+/-) to connections (22) in UPS1 and UPS2.

6 - Tie the cables down to the cabinet frames. 7 - Put the covers back in place.

Figure 2-6: Parallel UPS With Separate Normal and Bypass AC Inputs

UPS 1

22

14.56”

UPS 2

22

14.56”

To access the connections, remove cover (see Section 1.3).

1 - The grounding conductors must be connected to the grounding-plate of each UPS (17).

2 - Connect the three phases of the normal AC source to connection (16) in each UPS.

3 - Connect the three phases of the bypass AC source to connection (15) in each UPS unit.

4 - Connect the three phases of the supplied loads to connection (14) in UPS1.

5 - Connect (14) in UPS2 to (14) in UPS1 using the three load conductors.

Ground

To Load

To Normal

To Bypass

 

AC Source

AC Source

6 - Connect the external battery (+/-) to connections (22) in UPS1 and UPS2.

7 - Tie the cables down to the cabinet frames. 8 - Put the covers back in place.

CAUTION If the two UPSs are placed side by side, connect as indicated above. In the other configurations, always make sure that the cables between the UPSs and bypass AC source have the same cross-section and the same length. The same is true for the cables between the UPSs and the load.

2 — 4

Setup and Installation

86-174010-00 B00

Image 26
Contents MGE Galaxy Page MGE Galaxy Schneider ElectricImportant Safety Instructions MGE GalaxyEnvironment This page left blank intentionally Contents Service Solutions Team Three Phase Products MaintenanceWarranty and Product Registration AppendicesFigures TablesUPS Serial Number Special precautions Safety RulesSafety of persons Display Icons MGE Galaxy Symbol UsageDocument Icons Section Descriptions Setup and InstallationMaintenance IntroductionViii General Description IntroductionScope MGE Galaxy 5000 UPS System with Battery Single Line Diagram UPS power rating KVA Dimensions H x W x DInside the UPS Cabinet, Access to Connections Inside MGE Galaxy 5000 UPS CabinetPower Connection Terminals UPS Cabinet Bottom View LayoutUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Setup and Installation LocationElectrical Specifications Layout of CabinetsConnection of Power Cables in a Single UPS Single UPS With Common Normal and Bypass AC InputsUPS Exchange-current interconnections Can // interconnectionsParallel Configuration for Increased Capacity Four UPSs Interconnections with the external system bypass cabinetXMB08 XMB07 XMB06 Adding Communication Cards 11 Adding Communication CardsConnection of the Relay Communications Card 12 Connection of Relay Communication CardCharacteristics of the input contacts Communications Card Connection ExampleGeneral-shutdown cable Routing the Control/Communications CablesSingle UPS Exchange-current cables Parallel UPSCan cables Operation Shutting Down a Single UPSLoad is protected by the UPS Shutting Down a Parallel ConfigurationRestarting a Single UPS Restarting a Parallel Configuration Load is protected by the UPSsSingle UPS Start Sequence on Bypass AC Input Operation of Mimic-Panel LEDsSingle UPS Start Sequence on Normal AC Input Load on Battery Power Operating ModesUPS Personalization Access to the Personalization FunctionsPersonalization Settings Operating Mode FrequencyDisplay Messages List Operation of the Relay Communication Card Dry Contacts Standard ModeProgrammable Mode Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Battery power MaintenanceIdentification of Alarms Life Cycle Monitoring LCMLoad is no longer protected by the UPS UPS IsolationUPS Isolation Single UPS Parallel UPS Configuration Without External Bypass Cabinet Parallel UPS Configuration With External Bypass Cabinet Shutdown and isolation of all the UPSsUPS starts automatically LED 31 is on Return to the Normal OperationReturn to Normal Single UPS Parallel UPS Configuration Without External Bypass Cabinet Restart the UPS for which all switches are set to OFF UPS restarts and LED 31 is onReturn to Normal Parallel UPS With External Bypass Cabinet Hz Training Center Servicing BatteriesTraining Center This page left blank intentionally Selection of Protection Devices A1 Electrical CharacteristicsAppendices Limitation Input/Output Characteristics Inverter Bypass AC inputLoad output A2 Maximum Allowable Power for Parallel UPS Units MGE -Galaxy A3 UPS Cabinet Major Internal ComponentsA4 Available Options A5 Environment Page User Information MGE Galaxy Warranty and Product RegistrationWarranty Extension Warranty+ Product InformationReturn Policy for Repair of Three Phase Products RGA Technical Support and Product ServicesScheduling Field Service Engineer Support MGE Galaxy Glossary AWGIgbt VAC MGE Galaxy Reorder Form Scenic Avenue Costa Mesa, CA Use this formPage Page Contact Information