APC 40 130KVA user manual XMB08 XMB07 XMB06

Page 29

Installation and User Manual

Fitting the Protection Cover for the Auxiliary Interconnection Cables

The protection cover supplied with the parallel connected UPS units protects the user against direct contact with voltages other than SELVs and ensures the auxiliary interconnection cables are maintained in position.

Figure 2-9: Fitting the Protection Cover for the Auxiliary Interconnection Cables

Note: Tie down the cables as indicated in the diagram in Section 2.9.

2.6Connection of General Shutdown or Remote Emergency Power Off (REPO) Terminal Block

Figure 2-10: Connection of General Shutdown or Remote Emergency Power OFF (REPO) Terminal Block

XMB08 XMB07 XMB06

1 - Remove the wire jumper from terminal block (7).

2 - Connect the general shutdown NC contact to terminals 1 and 2 (SELV). 3 - Tie the cable down as illustrated in Section 2.9.

CAUTION Pressing the general shutdown button causes UPS shutdown and opening of the battery circuit breaker (with opening of the bypass static switch depending on personalization settings). The Remote Emergency Power Off (REPO) notion is applicable to installations where pressing the button also causes the upstream Normal AC source and bypass AC source circuit-breakers to open. In parallel configurations, there must be a single general shutdown button with a separate contact for each UPS unit.

86-174010-00 B00

Setup and Installation

2 — 7

Image 29
Contents MGE Galaxy Page Schneider Electric MGE GalaxyMGE Galaxy Important Safety InstructionsEnvironment This page left blank intentionally Contents Warranty and Product Registration MaintenanceService Solutions Team Three Phase Products AppendicesTables FiguresUPS Serial Number Special precautions Safety RulesSafety of persons Display Icons MGE Galaxy Symbol UsageDocument Icons Maintenance Setup and InstallationSection Descriptions IntroductionViii General Description IntroductionScope UPS power rating KVA Dimensions H x W x D MGE Galaxy 5000 UPS System with Battery Single Line DiagramInside MGE Galaxy 5000 UPS Cabinet Inside the UPS Cabinet, Access to ConnectionsUPS Cabinet Bottom View Layout Power Connection TerminalsUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Location Setup and InstallationLayout of Cabinets Electrical SpecificationsSingle UPS With Common Normal and Bypass AC Inputs Connection of Power Cables in a Single UPSUPS Can // interconnections Exchange-current interconnectionsInterconnections with the external system bypass cabinet Parallel Configuration for Increased Capacity Four UPSsXMB08 XMB07 XMB06 11 Adding Communication Cards Adding Communication Cards12 Connection of Relay Communication Card Connection of the Relay Communications CardCommunications Card Connection Example Characteristics of the input contactsGeneral-shutdown cable Routing the Control/Communications CablesSingle UPS Exchange-current cables Parallel UPSCan cables Shutting Down a Single UPS OperationLoad is protected by the UPS Shutting Down a Parallel ConfigurationRestarting a Single UPS Load is protected by the UPSs Restarting a Parallel ConfigurationSingle UPS Start Sequence on Bypass AC Input Operation of Mimic-Panel LEDsSingle UPS Start Sequence on Normal AC Input Operating Modes Load on Battery PowerPersonalization Settings Operating Mode Access to the Personalization FunctionsUPS Personalization FrequencyDisplay Messages List Operation of the Relay Communication Card Dry Contacts Standard ModeProgrammable Mode Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Identification of Alarms MaintenanceBattery power Life Cycle Monitoring LCMLoad is no longer protected by the UPS UPS IsolationUPS Isolation Single UPS Parallel UPS Configuration Without External Bypass Cabinet Shutdown and isolation of all the UPSs Parallel UPS Configuration With External Bypass CabinetUPS starts automatically LED 31 is on Return to the Normal OperationReturn to Normal Single UPS Parallel UPS Configuration Without External Bypass Cabinet UPS restarts and LED 31 is on Restart the UPS for which all switches are set to OFFReturn to Normal Parallel UPS With External Bypass Cabinet Hz Training Center Servicing BatteriesTraining Center This page left blank intentionally Selection of Protection Devices A1 Electrical CharacteristicsAppendices Limitation Input/Output Characteristics Inverter Bypass AC inputLoad output A2 Maximum Allowable Power for Parallel UPS Units A3 UPS Cabinet Major Internal Components MGE -GalaxyA4 Available Options A5 Environment Page Warranty Extension Warranty+ MGE Galaxy Warranty and Product RegistrationUser Information Product InformationReturn Policy for Repair of Three Phase Products RGA Technical Support and Product ServicesScheduling Field Service Engineer Support MGE Galaxy AWG GlossaryIgbt VAC MGE Galaxy Use this form Reorder Form Scenic Avenue Costa Mesa, CAPage Page Contact Information