3.5Operation of Mimic-Panel LEDs
The MGE Galaxy 5000 system is simple to operate and yet provides a wealth of continuous monitoring and diagnostic features to ensure proper operation. Operators gain access to information in the MGE Galaxy 5000 system through the display and its integrated LED mimic panel.
Figure 3-5: Operation of Mimic-Panel LEDs
37
Single UPS Start Sequence on Normal AC Input
| Steps | Action | LED (39) | LED (40) | LED (41) | LED (42) | LED (43) |
|
|
|
|
|
|
|
|
| 1 | Q1 open | Off | Off | Off | Off | Off |
|
|
|
|
|
|
|
|
| 2 | Close Q1 | green | Off | red | Off | red |
|
|
|
|
|
|
|
|
| 3 | Close Battery CB | green | Off | Off | Off | red |
|
|
|
|
|
|
|
|
| 4 | Close Q4S | green | Off | Off | Off | green |
|
|
|
|
|
|
|
|
| 5 | Close Q5N | green | Off | Off | green | green |
|
|
|
|
|
|
|
|
| 6 | Open Q3BP | green | Off | Off | green | green |
|
|
|
|
|
|
|
|
| 7 | Press ON button (37) | green | green | Off | green | Off |
|
|
|
|
|
|
|
|
Single UPS Start Sequence on Bypass AC Input |
|
|
|
| |||
|
|
|
|
|
|
|
|
| Steps | Action | LED (39) | LED (40) | LED (41) | LED (42) | LED (43) |
|
|
|
|
|
|
|
|
| 1 | Q4S open | Off | Off | Off | Off | Off |
|
|
|
|
|
|
|
|
| 2 | Close Q4S | Off | Off | red | Off | green |
|
|
|
|
|
|
|
|
| 3 | Close Q5N | Off | Off | red | green | green |
|
|
|
|
|
|
|
|
| 4 | Open Q3BP | Off | Off | red | green | green |
|
|
|
|
|
|
|
|
| 5 | Close Q1 | green | Off | red | green | green |
|
|
|
|
|
|
|
|
| 6 | Close Battery CB | green | Off | Off | green | green |
|
|
|
|
|
|
|
|
| 7 | Press ON button (37) | green | green | Off | green | Off |
|
|
|
|
|
|
|
|
3 — 4 | Operation |