APC 40 130KVA user manual Electrical Specifications, Layout of Cabinets

Page 24

MGE Galaxy 5000

2.1.1Layout of Cabinets

Figure 2-2: Layout of Cabinets (typical)

TOP VIEW

DISTRIBUTION

TRANSFORMER

MBC

UPS

BATTERY

2.2Electrical Specifications

Table 2-1: Electrical Specifications for the MGE Galaxy 5000

Output Power Rating (0.9 PF)

40KVA

50KVA

 

60KVA

80KVA

100KVA

130KVA

 

 

 

 

 

 

 

 

UPS Voltage (input/output)

480/480

480/480

 

480/480

480/480

480/480

480/480

 

 

 

 

 

 

 

Input/Output Requirements & Frequency

 

Three phase, Three wire + G, 60Hz

 

 

 

 

 

 

 

 

Input Phase Rotation

 

 

 

A, B, C Clockwise

 

 

 

 

 

 

 

 

Input Power Factor

 

 

> 0.98

 

 

 

 

 

 

 

 

 

 

Input Current/Input Current with Battery

48A/59A

59A/70A

 

71A/88A

94A/111A

117A/150A

151A/182A

Charging Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Input Current with Charging Current

57A

70A

 

85A

111A

148A

182A

(at low line -10%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass/Output Current

48A

60A

 

72A

96A

120A

156A

 

 

 

 

 

 

 

 

Battery Voltage

356VDC End Voltage

432VDC Nominal 490VDC Max. Floating Voltage

 

 

 

 

 

 

 

 

Max. Battery Current at Battery Voltage

90A

113A

 

135A

180A

225A

293A

(432 VDC at 100% Load)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. Battery Current at End-Voltage

109A

137A

 

164A

219A

273A

355A

(356 VDC at 100% Load)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Disconnect Circuit Breaker Rating

 

 

 

175A, 250A, 400A

 

 

 

 

 

 

 

 

 

 

Input, Bypass, Maintenance Bypass and

 

125A

 

250A

Output Switch Rating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input and Output Fuse Rating

 

160A

 

315A

 

 

 

 

 

 

 

 

2 — 2

Setup and Installation

86-174010-00 B00

Image 24
Contents MGE Galaxy Page MGE Galaxy Schneider ElectricImportant Safety Instructions MGE GalaxyEnvironment This page left blank intentionally Contents Maintenance Warranty and Product RegistrationService Solutions Team Three Phase Products AppendicesFigures TablesUPS Serial Number Safety Rules Safety of personsSpecial precautions MGE Galaxy Symbol Usage Document IconsDisplay Icons Setup and Installation MaintenanceSection Descriptions IntroductionViii Introduction ScopeGeneral Description MGE Galaxy 5000 UPS System with Battery Single Line Diagram UPS power rating KVA Dimensions H x W x DInside the UPS Cabinet, Access to Connections Inside MGE Galaxy 5000 UPS CabinetPower Connection Terminals UPS Cabinet Bottom View LayoutUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Setup and Installation LocationElectrical Specifications Layout of CabinetsConnection of Power Cables in a Single UPS Single UPS With Common Normal and Bypass AC InputsUPS Exchange-current interconnections Can // interconnectionsParallel Configuration for Increased Capacity Four UPSs Interconnections with the external system bypass cabinetXMB08 XMB07 XMB06 Adding Communication Cards 11 Adding Communication CardsConnection of the Relay Communications Card 12 Connection of Relay Communication CardCharacteristics of the input contacts Communications Card Connection ExampleRouting the Control/Communications Cables Single UPSGeneral-shutdown cable Parallel UPS Can cablesExchange-current cables Operation Shutting Down a Single UPSShutting Down a Parallel Configuration Restarting a Single UPSLoad is protected by the UPS Restarting a Parallel Configuration Load is protected by the UPSsOperation of Mimic-Panel LEDs Single UPS Start Sequence on Normal AC InputSingle UPS Start Sequence on Bypass AC Input Load on Battery Power Operating ModesAccess to the Personalization Functions Personalization Settings Operating ModeUPS Personalization FrequencyDisplay Messages List Standard Mode Programmable ModeOperation of the Relay Communication Card Dry Contacts Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Maintenance Identification of AlarmsBattery power Life Cycle Monitoring LCMUPS Isolation UPS Isolation Single UPSLoad is no longer protected by the UPS Parallel UPS Configuration Without External Bypass Cabinet Parallel UPS Configuration With External Bypass Cabinet Shutdown and isolation of all the UPSsReturn to the Normal Operation Return to Normal Single UPSUPS starts automatically LED 31 is on Parallel UPS Configuration Without External Bypass Cabinet Restart the UPS for which all switches are set to OFF UPS restarts and LED 31 is onReturn to Normal Parallel UPS With External Bypass Cabinet Servicing Batteries Training CenterHz Training Center This page left blank intentionally A1 Electrical Characteristics AppendicesSelection of Protection Devices Limitation Input/Output Characteristics Bypass AC input Load outputInverter A2 Maximum Allowable Power for Parallel UPS Units MGE -Galaxy A3 UPS Cabinet Major Internal ComponentsA4 Available Options A5 Environment Page MGE Galaxy Warranty and Product Registration Warranty Extension Warranty+User Information Product InformationTechnical Support and Product Services Scheduling Field Service Engineer SupportReturn Policy for Repair of Three Phase Products RGA MGE Galaxy Glossary AWGIgbt VAC MGE Galaxy Reorder Form Scenic Avenue Costa Mesa, CA Use this formPage Page Contact Information