3.10.3List of Operating Status Conditions That May be Assigned to an SECI Output

Operating status

Description

conditions

 

 

 

GENERAL ALARM

PFC fault OR

 

Inverter fault OR

 

Bypass static switch fault OR

 

Charger fault OR

 

Thermal overload on AC bypass OR

 

Normal AC input fuse blown OR

 

ALIN board input fuse blown OR

 

Q3BP and Q5N are closed simultaneously OR

 

External Q3BP and external Q5N are closed simultaneously OR

 

EPO activated OR

 

Battery backup time ended, shift to wait mode OR

 

Battery temperature fault > 45°C , charger shutdown OR

 

Battery deep discharge OR

 

Charger shutdown due to battery room temperature outside tolerances OR

 

Abnormal presence of voltage on the output before closing the bypass static

 

switch. (frequency converter) OR

 

UPS in downgraded mode OR

 

External CAN communication fault OR

 

Internal CAN communication fault (GDEN, MIZNUS and CHAN) OR

 

CAN cable physically cut OR

 

CAN communication relay fault OR

 

UPS personalization fault.

 

 

BATTERY FAULT

The battery will soon reach the end of its theoretical service life OR

 

Battery must be checked (following a faulty battery test)

 

 

LOAD ON UPS

Inverter connected to the load and operating on normal AC input.

 

Battery operations due to a BPI or battery test are signalled as operation on the

 

normal AC input.

 

 

LOAD ON AUTOMATIC

The static switch on the AC bypass is closed.

BYPASS

 

 

 

LOAD ON BATTERY

Inverter connected to the load and operating on battery power.

POWER

Battery operations due to a battery test are not signalled.

 

 

LOW BATTERY WARNING

Battery has reached the low-battery warning level (voltage or time). The two

 

thresholds may be user set.

 

 

OVERLOAD

One of the unit modules (rectifier, inverter or AC bypass) is overloaded (thermal or

 

instantaneous).

 

 

86-174010-00 B00

Operation

3 — 9

Image 43
Contents MGE Galaxy Page Schneider Electric MGE GalaxyMGE Galaxy Important Safety InstructionsEnvironment This page left blank intentionally Contents Appendices MaintenanceWarranty and Product Registration Service Solutions Team Three Phase ProductsTables FiguresUPS Serial Number Safety of persons Safety RulesSpecial precautions Document Icons MGE Galaxy Symbol UsageDisplay Icons Introduction Setup and InstallationMaintenance Section DescriptionsViii Scope IntroductionGeneral Description UPS power rating KVA Dimensions H x W x D MGE Galaxy 5000 UPS System with Battery Single Line DiagramInside MGE Galaxy 5000 UPS Cabinet Inside the UPS Cabinet, Access to ConnectionsUPS Cabinet Bottom View Layout Power Connection TerminalsUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Location Setup and InstallationLayout of Cabinets Electrical SpecificationsSingle UPS With Common Normal and Bypass AC Inputs Connection of Power Cables in a Single UPSUPS Can // interconnections Exchange-current interconnectionsInterconnections with the external system bypass cabinet Parallel Configuration for Increased Capacity Four UPSsXMB08 XMB07 XMB06 11 Adding Communication Cards Adding Communication Cards12 Connection of Relay Communication Card Connection of the Relay Communications CardCommunications Card Connection Example Characteristics of the input contactsSingle UPS Routing the Control/Communications CablesGeneral-shutdown cable Can cables Parallel UPSExchange-current cables Shutting Down a Single UPS OperationRestarting a Single UPS Shutting Down a Parallel ConfigurationLoad is protected by the UPS Load is protected by the UPSs Restarting a Parallel ConfigurationSingle UPS Start Sequence on Normal AC Input Operation of Mimic-Panel LEDsSingle UPS Start Sequence on Bypass AC Input Operating Modes Load on Battery PowerFrequency Access to the Personalization FunctionsPersonalization Settings Operating Mode UPS PersonalizationDisplay Messages List Programmable Mode Standard ModeOperation of the Relay Communication Card Dry Contacts Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Life Cycle Monitoring LCM MaintenanceIdentification of Alarms Battery powerUPS Isolation Single UPS UPS IsolationLoad is no longer protected by the UPS Parallel UPS Configuration Without External Bypass Cabinet Shutdown and isolation of all the UPSs Parallel UPS Configuration With External Bypass CabinetReturn to Normal Single UPS Return to the Normal OperationUPS starts automatically LED 31 is on Parallel UPS Configuration Without External Bypass Cabinet UPS restarts and LED 31 is on Restart the UPS for which all switches are set to OFFReturn to Normal Parallel UPS With External Bypass Cabinet Training Center Servicing BatteriesHz Training Center This page left blank intentionally Appendices A1 Electrical CharacteristicsSelection of Protection Devices Limitation Input/Output Characteristics Load output Bypass AC inputInverter A2 Maximum Allowable Power for Parallel UPS Units A3 UPS Cabinet Major Internal Components MGE -GalaxyA4 Available Options A5 Environment Page Product Information MGE Galaxy Warranty and Product RegistrationWarranty Extension Warranty+ User InformationScheduling Field Service Engineer Support Technical Support and Product ServicesReturn Policy for Repair of Three Phase Products RGA MGE Galaxy AWG GlossaryIgbt VAC MGE Galaxy Use this form Reorder Form Scenic Avenue Costa Mesa, CAPage Page Contact Information