APC 40 130KVA user manual Parallel Configuration for Increased Capacity Four UPSs

Page 28

MGE Galaxy 5000

Figure 2-8: Parallel Configuration for Increased Capacity (Four UPSs)

These configurations have an external System Bypass Cabinet (SBC).

PCA INTN

PCA INTN

UPS 1

UPS 2

 

Blue

 

plug

20

20

SBC

 

Interconnections with the external system bypass cabinet (20):

Interconnect terminals 7, 8, 9, and 10 on the auxiliary terminal block TB2 in the system bypass cabinet to UPS terminal blocks XMS04/XMS05 pins 1, 2, 3, and 4 respectively.

Create a loop connection between the cabinet and the UPSs as shown in Figure 2-8.

Details of terminal block connections.

 

 

 

 

 

 

TB2

7

8

 

9

 

10

 

 

20

20

 

 

UPS 4

 

UPS 3

 

 

Red

4

3

2

1

 

 

 

Common

SBC

XMS04 /

XMS05

 

 

 

 

 

 

TB2

7

 

 

1

 

 

 

 

 

8

 

 

2

 

 

 

 

 

 

9

 

 

3

 

 

 

 

 

 

10

 

 

4

 

 

 

 

 

 

 

 

plug

 

 

 

 

19

19

21

21

19

19

21

21

UPS 1

UPS 2

 

Blue

 

plug

UPS 4

UPS 3

 

Red plug

Note: The interconnection cables for the SBC are not supplied

Exchange-current interconnections (19): Use the XMS02 and XMS03 connectors to create a loop between the UPSs (all the XMS02 and XMS03 connectors must be used).

CAN // interconnections (21): Daisy-chain the UPSs using the XMS06 and XMS07 connectors. Fit a blue plug on the first UPS unit and a red plug on the last UPS (all the XMS06 and XMS07 connectors must be used).

Note: The supplied cables are 33 ft long. To ensure sufficient isolation of exchange-current, CAN and external bypass cabinet cables, they must be run separately from the power cables.

2 — 6

Setup and Installation

86-174010-00 B00

Image 28
Contents MGE Galaxy Page MGE Galaxy Schneider ElectricImportant Safety Instructions MGE GalaxyEnvironment This page left blank intentionally Contents Maintenance Warranty and Product RegistrationService Solutions Team Three Phase Products AppendicesFigures TablesUPS Serial Number Safety of persons Safety RulesSpecial precautions Document Icons MGE Galaxy Symbol UsageDisplay Icons Setup and Installation MaintenanceSection Descriptions IntroductionViii Scope IntroductionGeneral Description MGE Galaxy 5000 UPS System with Battery Single Line Diagram UPS power rating KVA Dimensions H x W x DInside the UPS Cabinet, Access to Connections Inside MGE Galaxy 5000 UPS CabinetPower Connection Terminals UPS Cabinet Bottom View LayoutUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Setup and Installation LocationElectrical Specifications Layout of CabinetsConnection of Power Cables in a Single UPS Single UPS With Common Normal and Bypass AC InputsUPS Exchange-current interconnections Can // interconnectionsParallel Configuration for Increased Capacity Four UPSs Interconnections with the external system bypass cabinetXMB08 XMB07 XMB06 Adding Communication Cards 11 Adding Communication CardsConnection of the Relay Communications Card 12 Connection of Relay Communication CardCharacteristics of the input contacts Communications Card Connection ExampleSingle UPS Routing the Control/Communications CablesGeneral-shutdown cable Can cables Parallel UPSExchange-current cables Operation Shutting Down a Single UPSRestarting a Single UPS Shutting Down a Parallel ConfigurationLoad is protected by the UPS Restarting a Parallel Configuration Load is protected by the UPSsSingle UPS Start Sequence on Normal AC Input Operation of Mimic-Panel LEDsSingle UPS Start Sequence on Bypass AC Input Load on Battery Power Operating ModesAccess to the Personalization Functions Personalization Settings Operating ModeUPS Personalization FrequencyDisplay Messages List Programmable Mode Standard ModeOperation of the Relay Communication Card Dry Contacts Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Maintenance Identification of AlarmsBattery power Life Cycle Monitoring LCMUPS Isolation Single UPS UPS IsolationLoad is no longer protected by the UPS Parallel UPS Configuration Without External Bypass Cabinet Parallel UPS Configuration With External Bypass Cabinet Shutdown and isolation of all the UPSsReturn to Normal Single UPS Return to the Normal OperationUPS starts automatically LED 31 is on Parallel UPS Configuration Without External Bypass Cabinet Restart the UPS for which all switches are set to OFF UPS restarts and LED 31 is onReturn to Normal Parallel UPS With External Bypass Cabinet Training Center Servicing BatteriesHz Training Center This page left blank intentionally Appendices A1 Electrical CharacteristicsSelection of Protection Devices Limitation Input/Output Characteristics Load output Bypass AC inputInverter A2 Maximum Allowable Power for Parallel UPS Units MGE -Galaxy A3 UPS Cabinet Major Internal ComponentsA4 Available Options A5 Environment Page MGE Galaxy Warranty and Product Registration Warranty Extension Warranty+User Information Product InformationScheduling Field Service Engineer Support Technical Support and Product ServicesReturn Policy for Repair of Three Phase Products RGA MGE Galaxy Glossary AWGIgbt VAC MGE Galaxy Reorder Form Scenic Avenue Costa Mesa, CA Use this formPage Page Contact Information