When sizing the upstream circuit breakers, the parameters presented below must be taken into account: Time/current curves for UPS input and output fuses:
| t (s) |
|
|
104 |
|
|
|
103 |
|
|
|
102 |
|
|
|
10 |
|
| |
|
|
| |
1 |
|
| |
|
|
| |
|
|
| |
|
|
| |
|
| I (A) | |
10 | 102 | 103 | 104 |
UPS
| Sn |
| 40KVA | 50KVA |
| 60KVA |
| 80KVA |
| 100KVA |
| 130KVA |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| In |
|
| 48 A | 60 A |
| 72 A |
| 96 A |
| 120 A |
| 156 A |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Limitation |
|
| 230 A | 230 A |
| 230 A |
| 260 A |
| 435 A |
| 435 A |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Line Current Values |
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Rated power of |
| Continuous input | Input current at | Input current at |
| Input/output fuse | |||||||||
| each UPS unit |
|
| current at V=480V | V=480V overload | V=480V overload |
| ratings | ||||||||
|
|
|
|
|
|
|
| = 1.25 In limited to | = 1.5 In limited to |
|
| |||||
|
|
|
|
|
|
|
| 10 min. |
| 1 min. |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 40KVA |
|
|
| 48 A | 60 A |
|
| 72 A |
| 160 A | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 50KVA |
|
|
| 60 A | 75 A |
|
| 90 A |
| 160 A | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 60KVA |
|
|
| 72 A | 90 A |
|
| 108 A |
| 160 A | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 80KVA |
|
|
| 96 A | 120 A |
|
| 144 A |
| 160 A | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 100KVA |
|
|
| 120 A | 150 A |
|
| 180 A |
| 315 A | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 130KVA |
|
|
| 156 A | 195 A |
|
| 234 A |
| 315 A | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A — 2 | Appendices |