APC 40 130KVA user manual Limitation

Page 58

MGE Galaxy 5000

When sizing the upstream circuit breakers, the parameters presented below must be taken into account: Time/current curves for UPS input and output fuses:

 

t (s)

 

 

104

 

 

 

103

 

 

 

102

 

 

 

10

 

 

40-80 kVA: 160A

 

 

 

1

 

 

100-130 kVA: 315A

10-1

 

 

 

10-2

 

 

 

10-3

 

 

 

10-4

 

 

I (A)

10

102

103

104

UPS short-circuit current with inverter coupled and By-pass AC source out of tolerances

 

Sn

 

40KVA

50KVA

 

60KVA

 

80KVA

 

100KVA

 

130KVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In

 

 

48 A

60 A

 

72 A

 

96 A

 

120 A

 

156 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limitation

 

 

230 A

230 A

 

230 A

 

260 A

 

435 A

 

435 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line Current Values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated power of

 

Continuous input

Input current at

Input current at

 

Input/output fuse

 

each UPS unit

 

 

current at V=480V

V=480V overload

V=480V overload

 

ratings

 

 

 

 

 

 

 

 

= 1.25 In limited to

= 1.5 In limited to

 

 

 

 

 

 

 

 

 

 

10 min.

 

1 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40KVA

 

 

 

48 A

60 A

 

 

72 A

 

160 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50KVA

 

 

 

60 A

75 A

 

 

90 A

 

160 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60KVA

 

 

 

72 A

90 A

 

 

108 A

 

160 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80KVA

 

 

 

96 A

120 A

 

 

144 A

 

160 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100KVA

 

 

 

120 A

150 A

 

 

180 A

 

315 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130KVA

 

 

 

156 A

195 A

 

 

234 A

 

315 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A — 2

Appendices

86-174010-00 B00

Image 58
Contents MGE Galaxy Page MGE Galaxy Schneider ElectricImportant Safety Instructions MGE GalaxyEnvironment This page left blank intentionally Contents Service Solutions Team Three Phase Products MaintenanceWarranty and Product Registration AppendicesFigures TablesUPS Serial Number Safety of persons Safety RulesSpecial precautions Document Icons MGE Galaxy Symbol UsageDisplay Icons Section Descriptions Setup and InstallationMaintenance IntroductionViii Scope IntroductionGeneral Description MGE Galaxy 5000 UPS System with Battery Single Line Diagram UPS power rating KVA Dimensions H x W x DInside the UPS Cabinet, Access to Connections Inside MGE Galaxy 5000 UPS CabinetPower Connection Terminals UPS Cabinet Bottom View LayoutUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Setup and Installation LocationElectrical Specifications Layout of CabinetsConnection of Power Cables in a Single UPS Single UPS With Common Normal and Bypass AC InputsUPS Exchange-current interconnections Can // interconnectionsParallel Configuration for Increased Capacity Four UPSs Interconnections with the external system bypass cabinetXMB08 XMB07 XMB06 Adding Communication Cards 11 Adding Communication CardsConnection of the Relay Communications Card 12 Connection of Relay Communication CardCharacteristics of the input contacts Communications Card Connection ExampleSingle UPS Routing the Control/Communications CablesGeneral-shutdown cable Can cables Parallel UPSExchange-current cables Operation Shutting Down a Single UPSRestarting a Single UPS Shutting Down a Parallel ConfigurationLoad is protected by the UPS Restarting a Parallel Configuration Load is protected by the UPSsSingle UPS Start Sequence on Normal AC Input Operation of Mimic-Panel LEDsSingle UPS Start Sequence on Bypass AC Input Load on Battery Power Operating ModesUPS Personalization Access to the Personalization FunctionsPersonalization Settings Operating Mode FrequencyDisplay Messages List Programmable Mode Standard ModeOperation of the Relay Communication Card Dry Contacts Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Battery power MaintenanceIdentification of Alarms Life Cycle Monitoring LCMUPS Isolation Single UPS UPS IsolationLoad is no longer protected by the UPS Parallel UPS Configuration Without External Bypass Cabinet Parallel UPS Configuration With External Bypass Cabinet Shutdown and isolation of all the UPSsReturn to Normal Single UPS Return to the Normal OperationUPS starts automatically LED 31 is on Parallel UPS Configuration Without External Bypass Cabinet Restart the UPS for which all switches are set to OFF UPS restarts and LED 31 is onReturn to Normal Parallel UPS With External Bypass Cabinet Training Center Servicing Batteries Hz Training Center This page left blank intentionally Appendices A1 Electrical CharacteristicsSelection of Protection Devices Limitation Input/Output Characteristics Load output Bypass AC inputInverter A2 Maximum Allowable Power for Parallel UPS Units MGE -Galaxy A3 UPS Cabinet Major Internal ComponentsA4 Available Options A5 Environment Page User Information MGE Galaxy Warranty and Product RegistrationWarranty Extension Warranty+ Product InformationScheduling Field Service Engineer Support Technical Support and Product ServicesReturn Policy for Repair of Three Phase Products RGA MGE Galaxy Glossary AWGIgbt VAC MGE Galaxy Reorder Form Scenic Avenue Costa Mesa, CA Use this formPage Page Contact Information