Installation and User Manual

Safety Rules

Safety of persons

The UPS must be installed in a room with restricted access (qualified personnel only). A UPS has its own external power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC-power source.

Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.

The UPS must be properly grounded.

The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the instructions below must be observed.

Never operate the UPS if the ambient temperature and relative humidity are higher than the levels specified in the documentation.

Never burn the battery (risk of explosion).

Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).

Comply with all applicable regulations for the disposal of the battery.

Caution, wait five minutes before opening the UPS to allow the capacitors to discharge.

Caution, there is high leakage current, the grounding conductor must be connected first.

The product must be installed on a non-inflammable surface (e.g. concrete).

Caution, battery replacement must be carried out by qualified personnel.

Product safety

A protection circuit breaker must be installed upstream and downstream, and be easily accessible.

Never install the UPS near liquids or in an excessively damp environment.

Never let a liquid or foreign body penetrate inside the UPS.

Never block the ventilation grates of the UPS.

Never expose the UPS to direct sunlight or a source of heat.

When replacing battery cells, use the same type and number of cells.

Special precautions

The UPS connection instructions contained in this manual must be followed in the indicated order.

Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS.

If the UPS must be stored prior to installation, storage must be in a dry place.

The admissible storage temperature range is -25°C to +45°C.

If the UPS remains de-energized for a long period, we recommend that you energize the UPS for a period of 24 hours, at least every three months. This charges the battery, thus avoiding possible irreversible damage.

The UPS is designed for normal climatic and environmental operating conditions concerning the altitude, ambient operating temperature, relative humidity and ambient transport and storage conditions.

Using the UPS within the given limits guarantees its operation, but may affect the service life of certain compo- nents, particularly that of the battery and its autonomy. The maximum storage time of the UPS is limited due to the need to recharge the battery.

Unusual operating conditions may justify special design or protection measures:

-harmful smoke, dust, abrasive dust,

-humidity, vapor, salt air, bad weather or dripping,

-explosive dust and gas mixture,

-extreme temperature variations,

-bad ventilation,

-conductive or radiant heat from other sources,

-strong electromagnetic fields,

-radioactive levels higher than those of the natural environment,

-fungus, insects, vermin, etc.,

-battery operating conditions.

86-174010-00 B00

Safety Rules

V

Image 11
Contents MGE Galaxy Page Schneider Electric MGE GalaxyMGE Galaxy Important Safety InstructionsEnvironment This page left blank intentionally Contents Appendices MaintenanceWarranty and Product Registration Service Solutions Team Three Phase ProductsTables FiguresUPS Serial Number Special precautions Safety RulesSafety of persons Display Icons MGE Galaxy Symbol UsageDocument Icons Introduction Setup and InstallationMaintenance Section DescriptionsViii General Description IntroductionScope UPS power rating KVA Dimensions H x W x D MGE Galaxy 5000 UPS System with Battery Single Line DiagramInside MGE Galaxy 5000 UPS Cabinet Inside the UPS Cabinet, Access to ConnectionsUPS Cabinet Bottom View Layout Power Connection TerminalsUser-Machine Interface Display User-Machine Interface DisplayDisplay Screens Display ScreensRelay Communication Card Relay Communication CardThis page left blank intentionally Introduction Location Setup and InstallationLayout of Cabinets Electrical SpecificationsSingle UPS With Common Normal and Bypass AC Inputs Connection of Power Cables in a Single UPSUPS Can // interconnections Exchange-current interconnectionsInterconnections with the external system bypass cabinet Parallel Configuration for Increased Capacity Four UPSsXMB08 XMB07 XMB06 11 Adding Communication Cards Adding Communication Cards12 Connection of Relay Communication Card Connection of the Relay Communications CardCommunications Card Connection Example Characteristics of the input contactsGeneral-shutdown cable Routing the Control/Communications CablesSingle UPS Exchange-current cables Parallel UPSCan cables Shutting Down a Single UPS OperationLoad is protected by the UPS Shutting Down a Parallel ConfigurationRestarting a Single UPS Load is protected by the UPSs Restarting a Parallel ConfigurationSingle UPS Start Sequence on Bypass AC Input Operation of Mimic-Panel LEDsSingle UPS Start Sequence on Normal AC Input Operating Modes Load on Battery PowerFrequency Access to the Personalization FunctionsPersonalization Settings Operating Mode UPS PersonalizationDisplay Messages List Operation of the Relay Communication Card Dry Contacts Standard ModeProgrammable Mode Load on Automatic AUTOMATIC-BYPASS Battery Temperature Fault This page left blank intentionally Life Cycle Monitoring LCM MaintenanceIdentification of Alarms Battery powerLoad is no longer protected by the UPS UPS IsolationUPS Isolation Single UPS Parallel UPS Configuration Without External Bypass Cabinet Shutdown and isolation of all the UPSs Parallel UPS Configuration With External Bypass CabinetUPS starts automatically LED 31 is on Return to the Normal OperationReturn to Normal Single UPS Parallel UPS Configuration Without External Bypass Cabinet UPS restarts and LED 31 is on Restart the UPS for which all switches are set to OFFReturn to Normal Parallel UPS With External Bypass Cabinet Hz Training Center Servicing BatteriesTraining Center This page left blank intentionally Selection of Protection Devices A1 Electrical CharacteristicsAppendices Limitation Input/Output Characteristics Inverter Bypass AC inputLoad output A2 Maximum Allowable Power for Parallel UPS Units A3 UPS Cabinet Major Internal Components MGE -GalaxyA4 Available Options A5 Environment Page Product Information MGE Galaxy Warranty and Product RegistrationWarranty Extension Warranty+ User InformationReturn Policy for Repair of Three Phase Products RGA Technical Support and Product ServicesScheduling Field Service Engineer Support MGE Galaxy AWG GlossaryIgbt VAC MGE Galaxy Use this form Reorder Form Scenic Avenue Costa Mesa, CAPage Page Contact Information