INSTALLING HEATER

Continued

VENTING HEATER

Note: Venting/chimney materials are not supplied with heater.

WARNING

WARNING ICON

G 001

A qualified service person must install the venting system for this heater. If venting system is not properly installed and maintained, the vent safety shut-off system will pre- vent the heater from running. Follow all local codes.

WARNING

WARNING ICON

G 001

This heater has a vent safety shut-off system. This system shuts off the heater gas supply if you do not vent heater properly or the venting system is blocked. Do not operate heater if not properly vented. Do not tamper with the vent safety shut-off system. Carbon monoxide poisoning and death may result.

WARNING

WARNING ICON

G 001

When venting this heater, follow the safety information listed below.

Never vent heater to another room or inside a build- ing. Only vent heater to the outdoors.

Do not vent heater exhaust to a chimney or flue serving another solid-fuel-burning or gas appliance.

We recommend you use flues classified as prefabri- cated or masonry all-fuel chimney or type-B vent. See Vent Types, page 10.

If using old vent, check vent for soot, creosote, and loose particles. If vent is damaged, repair or replace it before using heater.

Extend the vertical section of vent pipe at least three feet above roof penetration.

Extend the vertical section of vent pipe at least two feet above the highest point of any roof within ten feet.

The horizontal run of vent pipe should rise at least 1/4 inch for each foot of run.

Support the vent pipe at least every five feet along its length. Do not use combustible materials to support vent pipe.

Never extend vent pipe horizontally through outside wall and terminate. You must connect a vertical run of vent pipe to the horizontal run. The vertical run must be at least 25% longer than the horizontal run.

Install vent or chimney cap that is approved for use with vented gas room heaters.

Do not use vent pipe smaller in diameter than that of the heater draft hood outlet.

Do not use dampers in the vent pipes.

Vertical height of vent must be greater than five feet above vent connection at draft hood.

100791

Image 8
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualFor Your Safety Contents Safety Information Safety Information Product IdentificationFeatures Installing HeaterLocal Codes UnpackingInstalling Heater Venting Heater Venting Heater Do not vent heater in any of the following ways see FigureVenting Heater Proper Size Vent Supply. Follow all local codes Connecting to GAS SupplyQualified service person must connect heater to gas Gas Connection Pressure Testing Gas Supply Piping System Checking GAS ConnectionsInstalling Radiants Location of RadiantsInstalling Glass Panel For Radiant Models OnlyInserting Glass into Lower Retaining Channel AIR for Combustion and Ventilation AIR for VentilationDetermining FRESH-AIR Flow for Heater Location Draft Hood Spillage TestLeases poisonous carbon monoxide gas into your home Confined area has an air volume of less than 50 cubic 18 to make sure fresh air ventilation is adequateFor Your Safety Read Before Lighting Operating HeaterViewing Pilot Manual Lighting Procedure Blower OperationTo Turn OFF GAS to Appliance Shutting Off HeaterBurner Flame Pattern Inspecting Pilot and Burner FlamePilot Flame Pattern Flame Cleaning MaintenanceTrouble Shooting Observed Possible Problem Cause RemedyCleaning and Mainte TROUBLE- ShootingSee Changing Burner Orifice, Lighting Instructions Ing statement at TopService Procedures Removing Control Valve and Burner TubeRemoving Burner Wiring DiagramBlower Changing Burner OrificeTechnical Service Service Hints35,000 BTU/Hr 50,000 BTU/Hr ModelOrdering Replacement Parts Under WarrantyParts Not Under Warranty PartsAccessories Blower KIT Part Number GA6010Illustrated Parts List Blower AssemblyIllustrated Parts List Cabinet Assembly for Radiant Models Burner Assembly for Radiant Models Parts List Burner Assembly for Radiant Models 100791 100791 Warranty Information Limited Warranty GVR/GVC Vented Propane GAS Heaters