Bradford-White Corp POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER operation manual

Page 13

Figure 3.

Direct Vent Terminal Clearances

 

 

Canadian Installations1

US Installations2

A=

Clearance above grade, veranda, porch, deck or balcony

12 inches (30 cm)

12 inches (30 cm)

 

 

 

 

B=

Clearance to widow or door that may be opened

36 inches (91 cm)

12 inches (30 cm)

 

 

 

 

C=

Clearance to permanently closed widow

*b

*b

 

 

 

 

D=

Vertical clearance to ventilated soffit located above the terminal within a

12 inches (30 cm) *a

12 inches (30 cm) *a

horizontal distance of 2 feet (61 cm) from the center line of the terminal

 

 

 

E=

Clearance to unventilated soffit

12 inches (30 cm) *a

12 inches (30 cm) *a

 

 

 

 

F=

Clearance to outside corner

*b

*b

 

 

 

 

G=

Clearance to inside corner

*b

*b

 

 

 

 

 

 

3 feet (91 cm) within a

 

H=

Clearance to each side of center line extended above meter/regulator

height 15 feet (4.6 m)

*b

assembly

above the meter/regulator

 

 

 

 

assembly

 

I=

Clearance to service regulator vent outlet or oil tank vent

36 inches (91 cm)

*b

 

 

 

 

J=

Clearance to non-mechanical air supply inlet to building or the combustion air

36 inches (91 cm)

12 inches (30 cm)

inlet to any other appliance

 

 

 

K=

Clearance to a mechanical air supply inlet

6 feet (1.83 m)

3 feet (91 cm) above if

within 10 feet horizontally

 

 

 

L=

Clearance above paved sidewalk or paved driveway located on public

7 feet (2.13 m)†

*b

property

 

 

 

M=

Clearance under a veranda, porch, deck, or balcony

12 inches (30 cm) ‡

12 inches (30 cm) ‡

1In accordance with the current CAN/CGA-B149 Installation Codes.

2In accordance with the current ANSI Z223.1-(Latest edition)/NFPA 54 National Fuel Gas Code.

† A vent must not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and serves both dwellings.

Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. *a) A minimum clearance value determined by testing in accordance with section 2.20.

*b) “Clearance in accordance with local installation codes and the requirements of the gas supplier”.

13

Image 13
Contents Independent PVC Venting With Troubleshooting GuideTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected If YOU Smell GASDimensional layout Section II SpecificationsSection III General Information FeaturesDishwashing Machine Requirements Section IV Installation Instructions Page AIR Requirements Minimum Clearances Remove CrateSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Roof Venting Vertical Venting Through the Wall VentingPage Through the Wall Venting With Low Ground Clearance For LOW Ground Clearance InstallationsTermination # of Elbows Terminals Wall for LOW Ground Clearance InstallationsRoof Heater Without First Being Certain IT is Filled with Water Section VI Water ConnectionsApproximate TIME/TEMPERATURE Relationships in Scalds Section VII GAS Connections Open Flame for TestingSection IX Electrical Connections Wiring Diagram to the rightTypical Installation Lighting And Shutdown Instructions Section X Operating Instructions Temperature AdjustmentWater Heater Display and Control Buttons Flashes SetpointSetpoint flashes for 10 seconds Setpoint flashes Press SET for setting to take effect immediatelyChanges to C Press selectF/C Flashes Changes to F Flashes Symbol F/C Stops FlashingSetpoint shown in F Page Burner Flame Check Section X MaintenancePage This Water MAY be HOT To reinstall the burner rack, reverse the above procedurePage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Max Setpoint value Water Heater Display Error Code Shown Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint Flashes Max Setpoint continues to flash while making adjustmentsMax Setpoint stops flashing Display of Water Temperature Exiting SELECTService SET Mode To Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to F F/C Flashes Changes to C F/C FlashesSymbol Stops Flashing Press for 2 seconds How to reset the control from Lockout ConditionsError Codes and Error History Display No Current Error CodeError Code History To view previous error codesNo Error Code Shown for Code Index Error Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Degrees F Procedure for Checking Thermostat SensorsReplacement Parts List for Powered Direct Vent Models Section XII Parts List150,00 and 199,999 BTU/HR. Models 3 Vent KIT Vent KIT Components and Optional Condensate TEEModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Page Section XIV Notes