Bradford-White Corp POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER operation manual

Page 51

Error Codes and Error History Display:

If there is an operating problem with the water heater, an error code number will appear on the water heater display with “Service Needed” to the right of the “Status” indicator. The error code label is located below the water heater display and the following section in this Installation and Operating Instruction Manual explains the error codes with corrective actions to repair the water heater.

Example of Error Code in the Display:

idle

 

Service Needed

 

SELECT

SET

Error Code History:

In “Service Mode” pressing the “Select” button after the “Software Version” (item 8 in the previously described sequence of service modes) will show an error code history, if there have been any previous operating problems with the water heater. If the display shows --, there is not a current error code.

The Water Heater Display will provide up to 10 previous error codes. The oldest error code will be stored in code index #1 and the most recent in code index #10 (if there are 10 error codes).

To view previous error codes:

Step 1:

In “Service Mode” press the “Select” button until the next display after the “Software Version”. If there are no current error codes, the display will show -- .

No Current Error Code

 

°F

 

idle

 

 

Status

Operational

 

SELECT

SET

51

Image 51
Contents Independent PVC Venting With Troubleshooting GuideTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected If YOU Smell GASDimensional layout Section II SpecificationsSection III General Information FeaturesDishwashing Machine Requirements Section IV Installation Instructions Page AIR Requirements Minimum Clearances Remove CrateSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Roof Venting Vertical Venting Through the Wall VentingPage For LOW Ground Clearance Installations Through the Wall Venting With Low Ground ClearanceTermination # of Elbows Wall for LOW Ground Clearance Installations TerminalsRoof Heater Without First Being Certain IT is Filled with Water Section VI Water ConnectionsApproximate TIME/TEMPERATURE Relationships in Scalds Section VII GAS Connections Open Flame for TestingSection IX Electrical Connections Wiring Diagram to the rightTypical Installation Lighting And Shutdown Instructions Section X Operating Instructions Temperature AdjustmentWater Heater Display and Control Buttons Setpoint FlashesSetpoint flashes for 10 seconds Setpoint flashes Press SET for setting to take effect immediatelyPress select Changes to CF/C Flashes Symbol F/C Stops Flashing Changes to F FlashesSetpoint shown in F Page Burner Flame Check Section X MaintenancePage This Water MAY be HOT To reinstall the burner rack, reverse the above procedurePage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Max Setpoint value Water Heater Display Error Code Shown Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint continues to flash while making adjustments Max Setpoint FlashesMax Setpoint stops flashing Display of Water Temperature Exiting SELECTService SET Mode To Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to F F/C Flashes Changes to C F/C FlashesSymbol Stops Flashing Press for 2 seconds How to reset the control from Lockout ConditionsTo view previous error codes No Current Error CodeError Codes and Error History Display Error Code HistoryNo Error Code Shown for Code Index Error Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Degrees F Procedure for Checking Thermostat SensorsReplacement Parts List for Powered Direct Vent Models Section XII Parts ListVent KIT Components and Optional Condensate TEE 150,00 and 199,999 BTU/HR. Models 3 Vent KITModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Page Section XIV Notes