Bradford-White Corp 238-47707-00E REV 7/12 operation manual Section VI Water Connections

Page 20

SECTION VI: WATER CONNECTIONS

NOTE: BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE MAIN WATER SUPPLY VALVE.

After shutting off the main water supply, open a faucet to relieve the water line pressure to prevent any water from leaking out of the pipes while making the water connections to the water heater. After the pressure has been relieved, close the faucet. The COLD water inlet and HOT water outlet are identified on the top and front of the water heater. Make sure the diptube is in place before making the cold water connection. Make the proper plumbing connections between the water heater and the plumbing system to the house. Install a shut-off valve in the cold water supply line.

CAUTION

If sweat fittings are to be used, DO NOT apply heat to the nipples on top or side of the water heater. Sweat the tubing to the adapter before fitting the adapter to the water connections. It is imperative that heat is not applied to the nipples containing a plastic liner.

Keep clear of the combination temperature and pressure relief valve discharge line outlet. The discharge may be hot enough to cause scald injury. The water is under pressure and may splash.

WARNING

FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE MANUFACTURER FROM ANY CLAIM, WHICH MIGHT RESULT FROM EXCESSIVE TEMPERATURE AND PRESSURES.

Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance, which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not smoke or have open flame near the faucet at the time it is open.

NOTICE

If this water heater is installed in a closed water supply system, such as the one having a back-flow preventer in the cold water supply, provisions must be made to control thermal expansion. DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion. Warranties do not cover damages from thermal expansions such as pressure bulges and/or deformities. Your water supplier or local plumbing inspector should be contacted on how to control this situation.

After installation of the water lines, open the main water supply valve and fill the water heater. While the water heater is filling, open several hot water faucets to allow air to escape from the water system. When a steady stream of water flows through the faucets, close them and check all water connections for possible leaks. NEVER OPERATE THE WATER

HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER.

20

Image 20
Contents With Troubleshooting Guide Independent PVC VentingTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSection II Specifications Dimensional layoutFeatures Section III General InformationDishwashing Machine Requirements Section IV Installation Instructions Page Minimum Clearances Remove Crate AIR RequirementsSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Wall Venting Through the Roof Venting Vertical VentingPage Termination # of Elbows For LOW Ground Clearance InstallationsThrough the Wall Venting With Low Ground Clearance Roof Wall for LOW Ground Clearance InstallationsTerminals Section VI Water Connections Heater Without First Being Certain IT is Filled with WaterApproximate TIME/TEMPERATURE Relationships in Scalds Open Flame for Testing Section VII GAS ConnectionsWiring Diagram to the right Section IX Electrical ConnectionsTypical Installation Lighting And Shutdown Instructions Temperature Adjustment Section X Operating InstructionsWater Heater Display and Control Buttons Setpoint flashes for 10 seconds SetpointFlashes Press SET for setting to take effect immediately Setpoint flashesF/C Flashes Press selectChanges to C Setpoint shown in F Symbol F/C Stops FlashingChanges to F Flashes Page Section X Maintenance Burner Flame CheckPage To reinstall the burner rack, reverse the above procedure This Water MAY be HOTPage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Error Code Shown Water Heater Display Max Setpoint value Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint stops flashing Max Setpoint continues to flash while making adjustmentsMax Setpoint Flashes Exiting SELECTService SET Mode  Display of Water TemperatureTo Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to C F/C Flashes Changes to F F/C FlashesSymbol Stops Flashing How to reset the control from Lockout Conditions Press for 2 secondsNo Current Error Code Error Codes and Error History DisplayError Code History To view previous error codesError Code Index No Error Code Shown for Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Procedure for Checking Thermostat Sensors Degrees FSection XII Parts List Replacement Parts List for Powered Direct Vent ModelsModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Vent KIT Components and Optional Condensate TEE150,00 and 199,999 BTU/HR. Models 3 Vent KIT Page Section XIV Notes