Bradford-White Corp 238-47707-00E REV 7/12 operation manual If YOU Smell GAS

Page 4

WARNING

This water heater needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air. Insufficient air supply will cause a recirculation of combustion products resulting in contamination that may be hazardous to life. This will result in carboning or sooting of the combustion chamber, burners, and flue tubes and creates a risk of asphyxiation.

Water heater materials of construction, products of combustion and the fuel contain carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working nearby this water heater.

Flammable items, pressurized containers or any other potential fire hazardous articles must never be placed on or adjacent to the water heater. Open containers of flammable material should not be stored or used in the same room with this water heater.

Insulation blankets are not required for this water heater. This water heater meets or exceeds the ASHRAE/IES 90.1b (latest edition) standards with respect to insulation and standby loss requirements.

Setting the water temperature to the maximum set point can result in scalding hot water delivered to the faucets. It is highly recommended that the maximum setpoint be adjusted to the lowest temperature possible for the needs of the installation. See following section in this Installation/Operation Manual to change the maximum setpoint limit (max setpoint). Make sure the water heater control display is not in a public area that can result in the temperature settings being improperly adjusted.

Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance, which is connect to the hot water system. If hydrogen is present, there will be unusual sounds such as air escaping through the pipes as hot water begins to flow. Do not smoke or have open flame near the faucet at the time it is open.

WARNING

Liquefied petroleum gases/propane gas is heavier than air and will remain at floor level if there is a leak. Basements, crawl spaces, closets and areas below ground level will serve as pockets for accumulation of leaking gas. Before lighting, smell all around the appliance area for gas. Be sure to smell next to the floor.

IF YOU SMELL GAS:

DO NOT try to light any appliance.

DO NOT touch any electric switch; do not use any telephone in your building.

Immediately call your gas supplier from a telephone in another building. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

DO NOT OPERATE THE APPLIANCE UNTIL THE LEAKAGE IS CORRECTED!

To comply with NSF requirements this water heater is to be:

a)Sealed to the floor with sealant, in a smooth and easily cleanable way, or

b)Installed with an optional leg kit that includes legs and/or extensions that provide a minimum clearance of 6” beneath the water heater.

4

Image 4
Contents With Troubleshooting Guide Independent PVC VentingTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSection II Specifications Dimensional layoutFeatures Section III General InformationDishwashing Machine Requirements Section IV Installation Instructions Page Minimum Clearances Remove Crate AIR RequirementsSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Wall Venting Through the Roof Venting Vertical VentingPage Through the Wall Venting With Low Ground Clearance For LOW Ground Clearance InstallationsTermination # of Elbows Terminals Wall for LOW Ground Clearance InstallationsRoof Section VI Water Connections Heater Without First Being Certain IT is Filled with WaterApproximate TIME/TEMPERATURE Relationships in Scalds Open Flame for Testing Section VII GAS ConnectionsWiring Diagram to the right Section IX Electrical ConnectionsTypical Installation Lighting And Shutdown Instructions Temperature Adjustment Section X Operating InstructionsWater Heater Display and Control Buttons Flashes SetpointSetpoint flashes for 10 seconds Press SET for setting to take effect immediately Setpoint flashesChanges to C Press selectF/C Flashes Changes to F Flashes Symbol F/C Stops FlashingSetpoint shown in F Page Section X Maintenance Burner Flame CheckPage To reinstall the burner rack, reverse the above procedure This Water MAY be HOTPage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Error Code Shown Water Heater Display Max Setpoint value Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint Flashes Max Setpoint continues to flash while making adjustmentsMax Setpoint stops flashing Exiting SELECTService SET Mode  Display of Water TemperatureTo Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to C F/C Flashes Changes to F F/C FlashesSymbol Stops Flashing How to reset the control from Lockout Conditions Press for 2 secondsNo Current Error Code Error Codes and Error History DisplayError Code History To view previous error codesError Code Index No Error Code Shown for Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Procedure for Checking Thermostat Sensors Degrees FSection XII Parts List Replacement Parts List for Powered Direct Vent Models150,00 and 199,999 BTU/HR. Models 3 Vent KIT Vent KIT Components and Optional Condensate TEEModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Page Section XIV Notes