Bradford-White Corp 238-47707-00E REV 7/12 Section VII GAS Connections, Open Flame for Testing

Page 22

SECTION VII: GAS CONNECTIONS

The gas supply lines must meet all requirements of the National Fuel Gas Code (ANSI Z223.1-Latest Edition), or in Canada CAN/CGA B149.1 Natural Gas Installation Code (Latest Edition) or CAN/CGA B149.2 Propane Installation Code (Latest Edition).

The minimum permissible gas supply pressure for the purpose of input adjustment is one (1.0) inch (0.25 kPa) water column above the operating manifold pressure. See the rating plate and gas valve for the manifold pressure and gas type. The maximum permissible gas supply pressure is fourteen (14.0) inches (3.5 kPa) water column for natural gas and liquefied petroleum gases/propane gas.

1.Connect this water heater only to the type of gas (Natural or Propane gas) as shown on the rating plate. Use clean black iron pipe or equivalent material approved by local codes and ordinances. (Dirt and scale from the pipe can enter the gas valve and cause it to malfunction). The inlet gas line must have a minimum length of three (3) inches (7.6 cm) drip leg (sediment trap) installed as close to the water heater’s gas valve as possible. A ground joint union must be installed as close to the water heater as possible in the gas supply line feeding the water heater to permit servicing of the water heater. Compounds used on the threaded joints of the gas piping must be resistant to the action of liquefied petroleum gases/propane gas. DO NOT apply pipe dope to the gas valve inlet and make certain that no pipe dope has become lodged in the inlet screen of the gas valve. Extreme care must be taken to ensure no pipe dope enters the gas valve. Avoid excessive torque when tightening the gas supply line to the gas valve. Excessive torque may result in cracking of the gas valve housing and could create a gas leak. The suggested maximum torque is 31.5 ft. lbs. (4.4 kg-m).

WARNING

The manufacturer of this water heater will not be liable for any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque.

2.This water heater and its gas connection must be leak tested before placing the water heater in operation. Check for gas leaks with a soap and water solution and a brush or a commercial leak detector fluid. NEVER USE A MATCH OR

OPEN FLAME FOR TESTING!

CAUTION

The water heater and individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa). The water heater must be isolated from the gas supply piping system by closing its manual shutoff valve during any pressure testing of the gas supply system at test pressures equal to or less than 1/2 psi (3.5 kPa). The supply line must be capped when not connected to the water heater.

3.While checking for leaks care must be taken to prevent solution from contacting the electrical connections at the control. If electrical connections at the control become wet, they must be thoroughly dried before attempting to operate the water heater.

WARNING

Installation or service of this water heater requires ability equivalent to that of a licensed tradesman in the field involved. Plumbing, air supply, venting, gas supply and electrical work are required.

Light the unit in accordance with the operating instructions label attached to the water heater.

Under no circumstances should the input rate exceed the input rate shown on the water heater rating plate. Over firing could result in damage or sooting of the water heater.

If the unit is exposed to the following, do not operate water heater until all corrective steps have been made by a factory authorized independent service contractor or qualified service professional.

1.Flooding to or above the level of the burner or controls

2.External firing

3.Damage

4.Firing without water

5.Sooting

22

Image 22
Contents With Troubleshooting Guide Independent PVC VentingTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSection II Specifications Dimensional layoutFeatures Section III General InformationDishwashing Machine Requirements Section IV Installation Instructions Page Minimum Clearances Remove Crate AIR RequirementsSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Wall Venting Through the Roof Venting Vertical VentingPage Through the Wall Venting With Low Ground Clearance For LOW Ground Clearance InstallationsTermination # of Elbows Terminals Wall for LOW Ground Clearance InstallationsRoof Section VI Water Connections Heater Without First Being Certain IT is Filled with WaterApproximate TIME/TEMPERATURE Relationships in Scalds Open Flame for Testing Section VII GAS ConnectionsWiring Diagram to the right Section IX Electrical ConnectionsTypical Installation Lighting And Shutdown Instructions Temperature Adjustment Section X Operating InstructionsWater Heater Display and Control Buttons Flashes SetpointSetpoint flashes for 10 seconds Press SET for setting to take effect immediately Setpoint flashesChanges to C Press selectF/C Flashes Changes to F Flashes Symbol F/C Stops FlashingSetpoint shown in F Page Section X Maintenance Burner Flame CheckPage To reinstall the burner rack, reverse the above procedure This Water MAY be HOTPage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Error Code Shown Water Heater Display Max Setpoint value Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint Flashes Max Setpoint continues to flash while making adjustmentsMax Setpoint stops flashing Exiting SELECTService SET Mode  Display of Water TemperatureTo Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to C F/C Flashes Changes to F F/C FlashesSymbol Stops Flashing How to reset the control from Lockout Conditions Press for 2 secondsError Code History No Current Error CodeError Codes and Error History Display To view previous error codesError Code Index No Error Code Shown for Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Procedure for Checking Thermostat Sensors Degrees FSection XII Parts List Replacement Parts List for Powered Direct Vent Models150,00 and 199,999 BTU/HR. Models 3 Vent KIT Vent KIT Components and Optional Condensate TEEModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Page Section XIV Notes