Page 42

7. Software Version (Display only)

Soft idle

Status Operational

8. Error Code History (Displays ifthere are present error codes or up to 10 previous error codes). Water Heater Display will show -- if there are no error codes.

SELECTSET

No current error codes

idle

Status Operational

To change the Maximum Setpoint Limit (Max Setpoint) for the temperature setpoint:

SELECT SET

WARNING

Setting the water temperature to the maximum set point can result in scalding hot water delivered to the faucets. It is highly recommended that the maximum setpoint be adjusted to the lowest temperature possible for the needs of the installation. See following section to change the maximum setpoint limit (max setpoint). Make sure the water heater control display is not in a public area that can result in the temperature settings being improperly adjusted.

See previous warning on scalds and an ASSE approved mixing valve.

Step 1: In service mode press the “Select” button until “Max Setpoint” is displayed.

 

 

°F

Max

 

 

 

Setpoint

idle

 

 

 

Status

Operational

 

SELECT

42

SET

Image 42
Contents With Troubleshooting Guide Independent PVC VentingTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSection II Specifications Dimensional layoutFeatures Section III General InformationDishwashing Machine Requirements Section IV Installation Instructions Page Minimum Clearances Remove Crate AIR RequirementsSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Wall Venting Through the Roof Venting Vertical VentingPage For LOW Ground Clearance Installations Through the Wall Venting With Low Ground ClearanceTermination # of Elbows Wall for LOW Ground Clearance Installations TerminalsRoof Section VI Water Connections Heater Without First Being Certain IT is Filled with WaterApproximate TIME/TEMPERATURE Relationships in Scalds Open Flame for Testing Section VII GAS ConnectionsWiring Diagram to the right Section IX Electrical ConnectionsTypical Installation Lighting And Shutdown Instructions Temperature Adjustment Section X Operating InstructionsWater Heater Display and Control Buttons Setpoint FlashesSetpoint flashes for 10 seconds Press SET for setting to take effect immediately Setpoint flashesPress select Changes to CF/C Flashes Symbol F/C Stops Flashing Changes to F FlashesSetpoint shown in F Page Section X Maintenance Burner Flame CheckPage To reinstall the burner rack, reverse the above procedure This Water MAY be HOTPage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Error Code Shown Water Heater Display Max Setpoint value Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint continues to flash while making adjustments Max Setpoint FlashesMax Setpoint stops flashing Exiting SELECTService SET Mode  Display of Water TemperatureTo Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to C F/C Flashes Changes to F F/C FlashesSymbol Stops Flashing How to reset the control from Lockout Conditions Press for 2 secondsError Code History No Current Error CodeError Codes and Error History Display To view previous error codesError Code Index No Error Code Shown for Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Procedure for Checking Thermostat Sensors Degrees FSection XII Parts List Replacement Parts List for Powered Direct Vent ModelsVent KIT Components and Optional Condensate TEE 150,00 and 199,999 BTU/HR. Models 3 Vent KITModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Page Section XIV Notes