Bradford-White Corp 238-47707-00E REV 7/12 operation manual Press for 2 seconds

Page 50

How to reset the control from Lockout Conditions:

WARNING

The following procedure is for service and installation personnel only. Resetting lockout conditions without correcting the malfunction can result in a hazardous condition.

If an error code is displayed (except for #4, low flame sense current), the water heater will be in a “lockout condition” with the water heater display showing the error code number and “Service Needed” in the status section of the display window. Error codes 62 (maximum number of retries detected) and 63 (maximum number if ignition recycles detected) are “Soft Lockouts” in which the control can be reset in the “User Mode” by pressing the lower right button under “Lockout Reset” shown in the lower right portion of the display. The control will also go through 3 attempts to relight the burners every hour in the soft lockout condition.

Resetting Error Codes in Soft Lockout Condition

Error Code Shown in

Water Heater Display

Status Service needed

SELECT Lockout RESET

Press for 2 seconds

All other error codes will put the water heater into a “Hard Lockout” condition, in which the water heater will not operate and cannot be reset in the “User Mode”. To reset a hard lockout, first enter the “Service Mode” described earlier by pressing both the “Temperature Up” and “Select Buttons” at the same time for 3 seconds. Then press the lower right button under “Lockout Reset” in the water heater display and hold for 3 seconds.

Resetting Error Codes in Hard Lockout Condition

 

 

Error Code Shown in

 

 

 

Water Heater Display

 

Status Service Needed

 

Status Service Needed

 

 

SELECT

SET

 

SELECT Lockout RESET

Step 1: Press for 3 seconds

Step 2: Press for 3 seconds to

to enter service mode.

reset control in service mode.

50

Image 50
Contents With Troubleshooting Guide Independent PVC VentingTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSection II Specifications Dimensional layoutFeatures Section III General InformationDishwashing Machine Requirements Section IV Installation Instructions Page Minimum Clearances Remove Crate AIR RequirementsSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Wall Venting Through the Roof Venting Vertical VentingPage Termination # of Elbows For LOW Ground Clearance InstallationsThrough the Wall Venting With Low Ground Clearance Roof Wall for LOW Ground Clearance InstallationsTerminals Section VI Water Connections Heater Without First Being Certain IT is Filled with WaterApproximate TIME/TEMPERATURE Relationships in Scalds Open Flame for Testing Section VII GAS ConnectionsWiring Diagram to the right Section IX Electrical ConnectionsTypical Installation Lighting And Shutdown Instructions Temperature Adjustment Section X Operating InstructionsWater Heater Display and Control Buttons Setpoint flashes for 10 seconds SetpointFlashes Press SET for setting to take effect immediately Setpoint flashesF/C Flashes Press selectChanges to C Setpoint shown in F Symbol F/C Stops FlashingChanges to F Flashes Page Section X Maintenance Burner Flame CheckPage To reinstall the burner rack, reverse the above procedure This Water MAY be HOTPage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Error Code Shown Water Heater Display Max Setpoint value Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint stops flashing Max Setpoint continues to flash while making adjustmentsMax Setpoint Flashes Exiting SELECTService SET Mode  Display of Water TemperatureTo Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to C F/C Flashes Changes to F F/C FlashesSymbol Stops Flashing How to reset the control from Lockout Conditions Press for 2 secondsError Code History No Current Error CodeError Codes and Error History Display To view previous error codesError Code Index No Error Code Shown for Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Procedure for Checking Thermostat Sensors Degrees FSection XII Parts List Replacement Parts List for Powered Direct Vent ModelsModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Vent KIT Components and Optional Condensate TEE150,00 and 199,999 BTU/HR. Models 3 Vent KIT Page Section XIV Notes