Bradford-White Corp POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER operation manual

Page 45

Step 2: For water heaters using two temperature sensors, pressing the “Select” button again displays the Upper Sensor temperature reading. “Upper Sensor” will be displayed in the lower right side of the status window of the water heater display.

°F

idle

Status Operational

Upper Sensor

Step 3: For water heaters using two temperature sensors, pressing the “Select” button again displays the Lower Sensor temperature reading. “Lower Sensor” will be displayed in the lower left side of the status window of the water heater display.

SELECTSET

°F

 

idle

 

Status Operational

 

Lower Sensor

 

SELECT

SET

To Display Flame Sense Current of the Pilot Flame Sensor:

The pilot flame sense current is available only when the burners are in operation. Step 1: Make sure the status displays

“Heating” or draw enough hot water to start the burners. Step 2: Enter the “Service Mode” described previously. Step 3: Press the “Select” button until a number value is displayed with “Flame Current” to the right of the number. The value displayed is in microamps (µA).

 

Flame

 

Current

µA

 

Heating

 

Status Operational

 

SELECT

SET

45

 

Image 45
Contents Independent PVC Venting With Troubleshooting GuideTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected If YOU Smell GASDimensional layout Section II SpecificationsSection III General Information FeaturesDishwashing Machine Requirements Section IV Installation Instructions Page AIR Requirements Minimum Clearances Remove CrateSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Roof Venting Vertical Venting Through the Wall VentingPage For LOW Ground Clearance Installations Through the Wall Venting With Low Ground ClearanceTermination # of Elbows Wall for LOW Ground Clearance Installations TerminalsRoof Heater Without First Being Certain IT is Filled with Water Section VI Water ConnectionsApproximate TIME/TEMPERATURE Relationships in Scalds Section VII GAS Connections Open Flame for TestingSection IX Electrical Connections Wiring Diagram to the rightTypical Installation Lighting And Shutdown Instructions Section X Operating Instructions Temperature AdjustmentWater Heater Display and Control Buttons Setpoint FlashesSetpoint flashes for 10 seconds Setpoint flashes Press SET for setting to take effect immediatelyPress select Changes to CF/C Flashes Symbol F/C Stops Flashing Changes to F FlashesSetpoint shown in F Page Burner Flame Check Section X MaintenancePage This Water MAY be HOT To reinstall the burner rack, reverse the above procedurePage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Max Setpoint value Water Heater Display Error Code Shown Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint continues to flash while making adjustments Max Setpoint FlashesMax Setpoint stops flashing Display of Water Temperature Exiting SELECTService SET Mode To Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to F F/C Flashes Changes to C F/C FlashesSymbol Stops Flashing Press for 2 seconds How to reset the control from Lockout ConditionsError Codes and Error History Display No Current Error CodeError Code History To view previous error codesNo Error Code Shown for Code Index Error Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Degrees F Procedure for Checking Thermostat SensorsReplacement Parts List for Powered Direct Vent Models Section XII Parts ListVent KIT Components and Optional Condensate TEE 150,00 and 199,999 BTU/HR. Models 3 Vent KITModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Page Section XIV Notes