Bradford-White Corp POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER operation manual

Page 37

SECTION XI: DIAGNOSTIC AND TROUBLESHOOTING GUIDE

DIAGNOSTIC GUIDE FOR HONEYWELL INTEGRATED CONTROL SYSTEM

SEQUENCE OF OPERATION FOR PDV AND INDUCED DRAFT MODELS

1.When the tank temperature drops below the temperature setpoint on the display, the control sends power to the induced draft blower to start the ignition sequence.

2.When blower reaches the full operating speed, the pressure switch closes, completing the 24 volt circuit to the safety circuit of the control. If the exhaust vent becomes blocked or the blower fails, the pressure switch will open, the gas valves close, and the blower stops after a 5 second post-purge. The blower will restart and continue to operate in the lockout condition until the blockage is removed or the venting problem is corrected. Error code 29 will appear on the water heater display.

3.The control will continue to operate the blower for 15 seconds to “prepurge” any flue products remaining before starting the ignition sequence.

4.After the prepurge period, the control sends 24 volt power to the pilot valve “PV” terminals on the gas valve allowing pilot gas to flow to the pilot. The control also sends high voltage through the pilot electrode to spark to the pilot hood and ignite the pilot gas. If the pilot does not ignite within 90 seconds, the pilot valve is denergized and the sparking stops for 75 seconds. The control will attempt to ignite the pilot two more times. If the pilot does not light on the 3rd attempt, the control will go into “soft lockout” for 1 hour and then will repeat the 3 ignition attempts. The blower is off during the “soft lockout” period.

5.When the pilot is lit, the flame is sensed by the flame sense rod. The flame sense signal received by the control board causes the sparking to stop and the main gas valve to open. The main burners ignite from the pilot flame. The pilot is continually monitored by the flame sensing circuit. If for any reason, the pilot flame is not sensed by the flame sensing circuit, the gas valves close. After a 75 second delay, the pilot valve opens and the pilot electrode sparks to relight the pilot. The same sequence will occur in the event of a power supply or gas supply interruption.

6.The main burners continue to operate until the water temperature in the tank increases past the control setpoint, which will cause the gas valve to close. The blower stops operating 5 seconds after the gas valve closes. The water heater remains in the standby mode until the temperature drops below the setpoint and initiates another heating cycle.

7.If for some reason, the tank temperature should reach or exceed 200˚F, then the control closes the gas valve and goes into a “hard lockout” state and will not operate until reset by a qualified service person. The display will read “error code 65”, which indicates the tank high limit temperature has been exceeded. No attempt should be made to reset the control until a service person has corrected the cause of the high limit condition. Refer to the diagnostic service section at the end of this Installation and Operating Instructions Manual.

37

Image 37
Contents Independent PVC Venting With Troubleshooting GuideTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected If YOU Smell GASDimensional layout Section II SpecificationsSection III General Information FeaturesDishwashing Machine Requirements Section IV Installation Instructions Page AIR Requirements Minimum Clearances Remove CrateSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Roof Venting Vertical Venting Through the Wall VentingPage Through the Wall Venting With Low Ground Clearance For LOW Ground Clearance InstallationsTermination # of Elbows Terminals Wall for LOW Ground Clearance InstallationsRoof Heater Without First Being Certain IT is Filled with Water Section VI Water ConnectionsApproximate TIME/TEMPERATURE Relationships in Scalds Section VII GAS Connections Open Flame for TestingSection IX Electrical Connections Wiring Diagram to the rightTypical Installation Lighting And Shutdown Instructions Section X Operating Instructions Temperature AdjustmentWater Heater Display and Control Buttons Flashes SetpointSetpoint flashes for 10 seconds Setpoint flashes Press SET for setting to take effect immediatelyChanges to C Press selectF/C Flashes Changes to F Flashes Symbol F/C Stops FlashingSetpoint shown in F Page Burner Flame Check Section X MaintenancePage This Water MAY be HOT To reinstall the burner rack, reverse the above procedurePage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Max Setpoint value Water Heater Display Error Code Shown Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint Flashes Max Setpoint continues to flash while making adjustmentsMax Setpoint stops flashing Display of Water Temperature Exiting SELECTService SET Mode To Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to F F/C Flashes Changes to C F/C FlashesSymbol Stops Flashing Press for 2 seconds How to reset the control from Lockout ConditionsError Codes and Error History Display No Current Error CodeError Code History To view previous error codesNo Error Code Shown for Code Index Error Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Degrees F Procedure for Checking Thermostat SensorsReplacement Parts List for Powered Direct Vent Models Section XII Parts List150,00 and 199,999 BTU/HR. Models 3 Vent KIT Vent KIT Components and Optional Condensate TEEModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Page Section XIV Notes