Bradford-White Corp POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Terminals, Roof

Page 19

Direct Vent System Installation for Models with Input Ratings Over 200,000 Btu/Hr.

Models with input ratings over 200,000 Btu/hr. must use 4” (10.2 cm) diameter pipe. Install the blower adaptor exhaust vent assembly and gasket supplied in the vent kit carton on the exhaust blower outlet flange as described in the previous section. Connect the 4” (10.2 cm) pipe to the 4” (10.2 cm) reducers attached to the combustion air intake pipe and blower exhaust outlet. The supplied 4” (10.2 cm) exhaust vent and combustion air intake terminals must also be used. Follow the venting system installation instructions for installing 4” (10.2 cm) diameter pipe detailed on pages 14-17 and figures 4-8 and follow the venting tables 5 and 6 for the maximum venting distances.

Maximum Venting Distances (Horizontal, Vertical, or Combined)

TABLE 5

EXHAUST VENT OR COMBUSTION AIR INTAKE PIPE LENGTHS FOR 4” (10.2 cm) PIPE

Number of 90° Elbows (Excluding vent

Maximum distance of straight pipe (excluding

vent or air intake terminal) to exterior wall or

terminals)

roof.

 

1

55 ft. (16.8 m)

2

50 ft. (15.2 m)

3

45 ft. (13.7 m)

4

40 ft. (12.2 m)

TABLE 6

4” (10.2 cm) EXHAUST VENT OR COMBUSTION AIR INTAKE PIPE LENGTHS FROM INSIDE

WALL FOR LOW GROUND CLEARANCE INSTALLATIONS

Terminating

# of Elbows

Maximum Length

(2) 90° Elbows with (1) 90° Elbow

1

45 ft (13.7 m)

(2) 90° Elbows with (1) 90° Elbow

2

40 ft (12.2 m)

(2) 90° Elbows with (1) 90° Elbow

3

35 ft (10.7 m)

(2) 90° Elbows with (1) 90° Elbow

4

30 ft (9.1 m)

19

Image 19
Contents Independent PVC Venting With Troubleshooting GuideTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected If YOU Smell GASDimensional layout Section II SpecificationsSection III General Information FeaturesDishwashing Machine Requirements Section IV Installation Instructions Page AIR Requirements Minimum Clearances Remove CrateSection V Venting Approved Venting Materials Direct Vent Terminal Clearances 40 ft .19 m Page Through the Roof Venting Vertical Venting Through the Wall VentingPage Through the Wall Venting With Low Ground Clearance For LOW Ground Clearance InstallationsTermination # of Elbows Terminals Wall for LOW Ground Clearance InstallationsRoof Heater Without First Being Certain IT is Filled with Water Section VI Water ConnectionsApproximate TIME/TEMPERATURE Relationships in Scalds Section VII GAS Connections Open Flame for TestingSection IX Electrical Connections Wiring Diagram to the rightTypical Installation Lighting And Shutdown Instructions Section X Operating Instructions Temperature AdjustmentWater Heater Display and Control Buttons Flashes SetpointSetpoint flashes for 10 seconds Setpoint flashes Press SET for setting to take effect immediatelyChanges to C Press selectF/C Flashes Changes to F Flashes Symbol F/C Stops FlashingSetpoint shown in F Page Burner Flame Check Section X MaintenancePage This Water MAY be HOT To reinstall the burner rack, reverse the above procedurePage Section XI Diagnostic and Troubleshooting Guide Max Setpoint Next to Temperature Setpoint value Max Setpoint value Water Heater Display Error Code Shown Water Heater DisplaySELECT Setpoint Display/Change No current error codes Max Setpoint Flashes Max Setpoint continues to flash while making adjustmentsMax Setpoint stops flashing Display of Water Temperature Exiting SELECTService SET Mode To Display Flame Sense Current of the Pilot Flame Sensor To Display and Change Temperature Setpoint Setpoint Stops Flashing Changes to F F/C Flashes Changes to C F/C FlashesSymbol Stops Flashing Press for 2 seconds How to reset the control from Lockout ConditionsTo view previous error codes No Current Error CodeError Codes and Error History Display Error Code HistoryNo Error Code Shown for Code Index Error Code IndexStored Error Code For Code Index #9 Exiting SELECTService SET Mode  Page Degrees F Procedure for Checking Thermostat SensorsReplacement Parts List for Powered Direct Vent Models Section XII Parts List150,00 and 199,999 BTU/HR. Models 3 Vent KIT Vent KIT Components and Optional Condensate TEEModels Over 200,000 BTU/HR Vent KIT Common 3 and 4 Vent KIT Page Section XIV Notes