TABLE 4: RECOVERY CAPACITIES
|
|
|
| TEMPERATURE RISE - DEGREES °F (°C) |
|
|
| |||||
| Input Rating | Water | 40°F | 50°F | 60°F | 70°F | 80°F | 90°F | 100°F | 110°F | 120°F | 130°F |
MODEL | BTU/Hr. (kW) | Flow | (22.2°) | (27.7°) | (33.3°) | (38.8°) | (44.4°) | (50°) | (55.5°) | (61.1°) | (66.7°) | (72.2°) |
GW - 1000 | 990,000 (290.1) | GPH | 2520 | 2016 | 1680 | 1440 | 1260 | 1120 | 1008 | 916 | 840 | 775 |
|
| LPH | 9526 | 7620 | 6350 | 5443 | 4763 | 4234 | 3810 | 3462 | 3175 | 2930 |
GW - 1300 | 1,300,000 (380.9) | GPH | 3309 | 2647 | 2206 | 1891 | 1655 | 1471 | 1324 | 1203 | 1103 | 1018 |
|
| LPH | 12508 | 10006 | 8339 | 7148 | 6256 | 5560 | 5005 | 4547 | 4169 | 3848 |
GW - 1500 | 1,500,000 (439.5) | GPH | 3818 | 3055 | 2545 | 2182 | 1909 | 1697 | 1527 | 1388 | 1273 | 1175 |
|
| LPH | 14432 | 11548 | 9620 | 8248 | 7216 | 6415 | 5772 | 5247 | 4812 | 4442 |
GW - 1850 | 1,850,000 (542.0) | GPH | 4709 | 3767 | 3139 | 2691 | 2355 | 2093 | 1884 | 1712 | 1570 | 1449 |
|
| LPH | 17800 | 14239 | 11865 | 10172 | 8902 | 7912 | 7122 | 6471 | 5935 | 5477 |
GW - 2100 | 2,100,000 (615.3) | GPH | 5345 | 4276 | 3564 | 3055 | 2673 | 2376 | 2138 | 1944 | 1782 | 1645 |
|
| LPH | 20204 | 16163 | 13472 | 11548 | 10104 | 8981 | 8082 | 7348 | 6736 | 6218 |
GW - 2500 | 2,490,000 (729.6) | GPH | 6338 | 5071 | 4225 | 3622 | 3169 | 2817 | 2535 | 2305 | 2113 | 1950 |
|
| LPH | 23958 | 19168 | 15971 | 13691 | 11979 | 10648 | 9582 | 8713 | 7987 | 7371 |
TABLE 5: PUMPING PERFORMANCE GUIDE
|
|
| GB |
|
| |||||||
| 20 Deg. F Rise | 30 Deg. F Rise | 40 Deg. F Rise | Maximum Flow Rate | Minimum Flow Rate | |||||||
| GPM | GPM | GPM | GPM | Deg. F | GPM | Deg. F | |||||
MODEL |
| Head |
| Head |
| Head |
| Head | Rise |
| Head | Rise |
GB - 1000 | 83 | 5.1 | 55 | 2.7 | 41.6 | 1.5 | 154 | 12.2 | 11 | 42 | 1.5 | 40 |
GB - 1300 | 109 | 7.2 | 72.8 | 4.2 | 54.6 | 3.2 | 154 | 14.5 | 14 | 55 | 3.2 | 40 |
GB - 1500 | 126 | 10.1 | 84 | 6.3 | 63 | 4.3 | 154 | 16.3 | 17 | 64 | 4.3 | 40 |
GB - 1850 | 154 | 18.5 | 103.6 | 10.1 | 77.7 | 6.4 | 154 | 18.5 | 20 | 78 | 6.4 | 40 |
GB - 2100 | n/a | n/a | 117.6 | 14.5 | 88 | 8.3 | 154 | 21.3 | 23 | 89 | 8.3 | 40 |
GB - 2500 | n/a | n/a | 139.4 | 18.5 | 104.6 | 11.6 | 154 | 23.2 | 28 | 105 | 11.6 | 40 |
Note: GW models (GB optional) are equipped with pumps capable of handling 50 equivalent feet (15.2 m) of normal pipe fittings.
FOREWORD
Detailed installation diagrams are in this manual. These diagrams will provide the installer with a reference of materials needed and a suggested method of piping. IT IS NECESSARY THAT ALL WATER AND GAS PIPING, AND THE ELECTRICAL WIRING BE INSTALLED AND CONNECTED AS SHOWN IN THE DIAGRAMS.
CHECK DIAGRAMS THOROUGHLY BEFORE STARTING INSTALLATION TO AVOID POSSIBLE ERRORS AND MINIMIZE TIME AND MATERIALS COST. SEE FIGURES 1 THROUGH 5 AND TABLES 1, 2, AND 3.
This design complies with the current edition of ANSI
MAKE SURE THE GAS ON WHICH THE BOILER WILL OPERATE IS THE SAME AS THAT SPECIFIED ON THE BOILER RATING PLATE.
The boiler installation must conform to these instructions and the local code authority having jurisdiction. In the absence of local codes, the installation must comply with the latest editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electrical Code, NFPA 70 or CAN/CSA B149.1, and CSA 2 C22.1. The former is available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH 44131, and both documents are available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
4