Maytag 99043751D Venting Requirements, Cabinet Dimensions, Cold Weather Installations, Makeup Air

Page 5

Cabinet Dimensions

30" (76.2 cm) or 36" (91.4 cm) min. cabinet opening width

18" (45.7 cm) min. 24" (61.0 cm) suggested max. bottom of range hood to cooking surface

13" (33 cm)

cabinet depth

18" (45.7 cm) min. clearance upper cabinet to countertop

36" (91.4 cm) base cabinet height

Venting Requirements

Cold Weather Installations

An additional back draft damper should be installed to minimize backward cold air flow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.

The break should be as close as possible to where the vent system enters the heated portion of the house.

Makeup Air

Local building codes may require the use of makeup air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale. Consult your HVAC professional for specific requirements in your area.

Venting Methods

Vent system can terminate either through the roof or wall. Use 3¹⁄₄" x 10" (8.3 x 25.4 cm) with a maximum recommended vent length of 35 ft (10.7 m) or 6" (15.2 cm) round vent with a maximum length of 50 ft (15.2 m) for vent system.

NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that greatly reduce performance.

Roof Venting

Wall Venting

A

D

 

A

 

 

B

 

B

D

 

 

 

 

 

C

 

C

 

 

 

 

(Vented Models Only)

Vent system must terminate to the outdoors, except for non- vented (recirculating) installations.

Do not terminate the vent system in an attic or other enclosed area.

Do not use a 4" (10.2 cm) laundry-type wall cap.

Use a 6" (15.2 cm) or a 3¹⁄₄" x 10" (8.3 x 25.4 cm) round metal vent. Rigid metal vent is recommended. Plastic or metal foil vent is not recommended.

The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.

For the most efficient and quiet operation:

Use no more than three 90° elbows.

Make sure there is a minimum of 24" (61 cm) of straight vent between the elbows if more than 1 elbow is used.

Do not install 2 elbows together.

Use clamps to seal all joints in the vent system.

The vent system must have a damper. If roof or wall cap has a damper, do not use damper supplied with the range hood.

Use caulking to seal exterior wall or roof opening around the cap.

A. 6" (15.2 cm) round vent or a 3¹⁄₄" x 10" (8.3 x 25.4 cm) vent through roof

B. Round vent: use 6" (15.2 cm) round damper (purchased separately)

C. 18" (45.7 cm) to 24" (61.0 cm) above cooking surface

D. Roof cap

A. 6" (15.2 cm) round vent or a 3¹⁄₄" x 10" (8.3 x 25.4 cm) vent through the wall

B. 3¹⁄₄" x 10" (8.3 x 25.4 cm) vent through the wall

C. 18" (45.7 cm) to 24" (61.0 cm) above cooking surface

D. Wall cap

5

Image 5
Contents Range Hood Table of Contents Range Hood SafetyImportant Safety Instructions Location Requirements Installation RequirementsTools and Parts Cold Weather Installations Cabinet DimensionsVenting Requirements Makeup AirCm Vent System Calculating Vent System Length¹⁄₄ x 10 8.3 cm x 25.4 cm Vent System Example vent systemDetermine Wiring Hole Location Installation InstructionsElectrical Requirements Prepare LocationTo wire through rear wall To wire through topWall Venting To make a 4 x 10½ 10.2 cm x 26.7 cm rectangle in the wallFor Power Supply Installations Install Range HoodFor vented model installations only Range Hood USE Complete InstallationMake Electrical Connection Range Hood ControlsRange Hood Care CleaningU.S.A CanadaThis limited warranty does not cover Whirlpool Corporation Major Appliance WarrantyVotre sécurité et celle des autres est très importante Sécurité DE LA Hotte DE CuisinièreImportantes Instructions DE Sécurité Outillage et pièces Exigences DinstallationExigences demplacement Exigences concernant l’évacuation Installations pour régions à climat froidAir dappoint Méthodes dévacuationCalcul de la longueur du circuit dévacuation Spécifications électriquesSystème de décharge de 6 15,2 cm Système de décharge de 3¹⁄₄ x 10 8,3 cm x 25,4 cmPréparation de lemplacement Instructions DinstallationDéterminer lemplacement du trou de passage du câble PréparationCâblage à travers le mur arrière Cm x 25,4 cm Décharge à travers le toitDécharge à travers le mur Couverte Installation de la hotteSoulever la hotte sous le placard et déterminer sa position Installer une lampe à incandescence de 75 watts maximum Achever linstallationRaccordement électrique Raccordement par câblage directUtilisation DE LA Hotte DE Cuisinière Commandes de la hotte de cuisinièreEntretien DE LA Hotte NettoyageGarantie DES Gros Appareils Ménagers Whirlpool Corporation Assistance OU ServiceAu Canada Si vous avez besoin de pièces de rechangeW10112419D