K-Tec MT2000 manual Quickstart Procedure cont’d, Verify Proper Power-Up

Page 10

4.1Quickstart Procedure (cont’d)

 

 

 

URV= 20mA

 

 

 

 

 

LRV = 4 mA

 

300 in. / 7620 mm

 

 

 

 

 

0 in. / 0 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LTP = 6”

CFG

 

 

 

 

 

HTP = 288”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2100

2565

 

 

13272

 

 

Raw Counts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK = 210

Figure 4.1

4.2Verify Proper Power-Up

Apply power to the transmitter and verify that the display comes up and is active. The display update rate is approxi- mately 4 seconds. The current draw should under no case exceed 21 mA and, in the event of a problem, refer to trouble-shooting section.

4.3Setting the 4mA and 20 mA Points Using the Pushbutton Menu

The LCD Display (Figure 4-2) option offers a menu driven setup that uses the UP, DOWN and SELECT pushbut- tons. Refer to the menu diagram (following this section) for navigation and selection instructions.

Note: The default factory setup is such that the instrument measures liquid level; i.e. the display will indicate a num- ber equal to the sensor length when the level is at the top of the vessel, and will indicate a zero when the vessel is empty.

Setting the 4mA point:

Under the CAL menu, go to the LRV (Lower Range Value) menu option. Press SELECT to change the value (in En- gineering Units) for which the 4mA point is to be set. With the default factory setup, LRV is typically set to or near zero engineering units.

Setting the 20mA point:

Under the CAL menu, go to the URV (Upper Range Value) menu option. Press SELECT to change the value (in Engineering Units) for which the 20mA point is to be set. With the default factory setup, URV is typically set to or near the actual probe length.

Note: The above steps do not require changing the level in the vessel.

Title

Engineering Units or

Calibration Mode

 

4 digit Display

Electronics LCD Display

Figure 4.2

10

UP

 

Button

SELECT

 

Button

DOWN

 

Button

 

MT2000-0200-01 Rev f (10-2007) DCN0160

Image 10
Contents Guided Wave Radar Level Transmitter Table of Contents List of Figures AppendicesIntroduction Storage Information Ambient TemperatureOverview Measurement cycle consists of the followingDirect Reflect Mode standard cont’d Ultra Low Dielectric ULD Measure MethodInstallation Mounting RequirementsMT2000 Guided Wave Radar Guidelines Factory Default ConfigurationShortening of Probe URV = Probe Length LRV = 0 in. / 0 mmCommissioning WiringQuickstart Procedure MT2000 Guided Wave Radar Guidelines cont’dVerify Proper Power-Up Quickstart Procedure cont’dSetting the 4mA and 20 mA Points Using the Pushbutton Menu LCD Menu Operation Calibration MenuDetailed Configuration Parameters Direct Mode Blanking Menu Threshold Level Parameter THV and Gain Setting GSAdvanced Parameter Settings Threshold Level Parameter THV and Gain Setting GS cont’dL1O Advanced Parameter Settings cont’d KO & KG= H * Sqrt DC H + L Ultra Low Dielectric ULD Mode ConfigurationDC = I + H L / H2 Setting the DAC trim Ultra Low Dielectric ULD Mode Configuration cont’dAdvanced Output Configuration DAC TrimFigure6 4mA & 20mA Calibration Using Actual Level Input Bench Calibration of the 4mA & 20mA PointsReversing The Output Action Using Actual Level Input Jumper Switch SettingsPossible Symptoms Troubleshooting InformationValid Current Loop Outputs Honeywell DE Output Option Possible Symptoms cont’dElectronics Module Replacement Interoperability and Conformance ClassHart Communicator Hart Protocol Interface OptionOperating Modes CompatibilityGlossary of Terms LRVAppendices Appendix a Sensor TrimConfiguration 2 Hidden Menu END CFG MenuTMP Appendix C Linearization To access the linearization tableSetting up Linearization Table Points To clear the linearization tableAppendix D Interface Applications MT2000 InterfacePrerequisites Use and setup of the oscilloscope for the MT2000Scope Settings Channel a Channel BAppendix F CE Certificate of Conformity Appendix G Exida Certificate MT2000-0200-1 Rev f 10-2007 DCN0160 MT2000-0200-01 Rev f 10-2007 DCN0160 MT2000-0200-1 Rev f 10-2007 DCN0160 10a Appendix I Mounting Configurations3a, 3b 10bAppendix J Warranty Statement Year Warranty for