4.3.1LCD Menu Operation
The LCD display is menu driven, uses the UP, DOWN, and SELECT pushbuttons for navigation.
•Press UP or DOWN to scroll through menu options.
•Press SELECT to select a menu option.
•When changing a variable use SELECT to move between signs or digits. When all digits flash an invalid value has been entered; press SELECT to continue
POWER UP
| ||
LL1 | Liquid Level 1 | |
L1C1 | Level 1 Current | |
(Press SELECT to exit | ||
MAIN MENU |
|
|
SET | Enter Setup Menu | |
LL1 | Liquid Level 1 | |
L1C | Level 1 Current | |
DE | Output % |
|
SETUP MENU |
| |
CAL | Enter Calibration Menu | |
CFG | Enter Configuration Menu | |
END | Exit Setup Menu | |
LINEARIZATION MENU |
| |
O01 | Output Point 1 | |
O02 | Output Point 2 | |
O20 | Output Point 20 | |
LIN SAVE | Save Linearization Table | |
LIN LOAD | Load Linearization Table | |
LIN RSET | Reset Linearization Table | |
END | Exit Linearization Menu |
CALIBRATION MENU
LRV Set Lower Range Value (at 4mA Point)
URV Set Upper Range Value (at 20mA point)
DMP Set Damping Value (.1 to 36 Sec)
DAC TRIM † Enter DAC Trim Menu
LIN MENU Enter Linearization Menu
END Exit Calibration Menu
CONFIGURATION MENU
DE Menu (if ordered)
EUN Set Engineering Units (In, ft, mm, cm, m or %)
L1O Set Level 1 Offset
KO Module Offset
KG Module Gain
THV Threshold Voltage
RC(1) Raw Counts3
BLK Blanking Value
GS Gain Settings
LCH Latching Settings
DRC Downward Restriction Count
ALD Alarm Delay
END Exit Configuration Menu
DE Menu (optional)2 | CONFIGURATION MENU 2 | *To access this menu see | ||
|
|
|
| "Setting LTP & HTP" |
DE ON/OFF | Turn DE output ON | RNG | Range Setting |
|
DB ON/OFF | Extended Information | LTP | Lower Trim Point |
|
END | Exit DE Menu | HTP | High Trim Point |
|
| To LL1 | END | Exit Configuration Menu 2 | |
|
|
1.Press DOWN & SELECT together for 4mA trim or UP & SELECT together for 20 mA trim
2.Available on DE output models only.
11 |