K-Tec MT2000 manual Configuration 2 Hidden Menu, END CFG Menu

Page 24

The sensor trim is now complete and the LRV has been set to equal 0 and URV has been set to the value of HTP. If other LRV and URV are desired, then proceed to the CAL menu and change LRV and URV accordingly.

If the level cannot be moved, the transmitter must be removed for re-trimming. Please contact the factory before trimming to confirm the procedure to follow. Should the trim be suspected of being corrupted, please consult the fac- tory. The transmitter can be brought back to the factory calibration conditions by performing a “3 Button Reset”. This is accomplished by simultaneously pressing “UP”, “DOWN” and “SELECT”. This action is generally recom- mended as a “last resort” prior to returning the transmitter to the factory for analysis, repair (if needed) and re- calibration.

9.2APPENDIX B: Additional Special Functions in the CFG2 (Hidden) Menu

These functions are accessed by pressing the ‘UP’ and ‘DOWN’ buttons together, when the LCD display is on ‘END’ at the end of the CFG menu. Enter the Sensor Trim menu and scroll down to access the following func- tions:

Configuration 2 (Hidden) Menu

SAT

UP/DOWN

Arrow

END (CFG MENU)

RNG - Range

LTP - Low Trim Point

HTP - High Trim Point

LTC - Low Trim counts

HTC - High Trim counts

TMP - Module Temperature

SOR - Signal Out of Range

ALRM

LRM - Low Range Margin

LRS - Low Range mA

SAT

END

Select

LL1 - Liquid Level 1

(Main Menu)

Figure 9.2

24

MT2000-0200-01 Rev f (10-2007) DCN0160

Image 24
Contents Guided Wave Radar Level Transmitter Table of Contents List of Figures AppendicesIntroduction Ambient Temperature OverviewStorage Information Measurement cycle consists of the followingDirect Reflect Mode standard cont’d Ultra Low Dielectric ULD Measure MethodInstallation Mounting RequirementsFactory Default Configuration Shortening of ProbeMT2000 Guided Wave Radar Guidelines URV = Probe Length LRV = 0 in. / 0 mmWiring Quickstart ProcedureCommissioning MT2000 Guided Wave Radar Guidelines cont’dQuickstart Procedure cont’d Verify Proper Power-UpSetting the 4mA and 20 mA Points Using the Pushbutton Menu LCD Menu Operation Calibration MenuDetailed Configuration Parameters Direct Mode Blanking Menu Threshold Level Parameter THV and Gain Setting GSThreshold Level Parameter THV and Gain Setting GS cont’d Advanced Parameter SettingsL1O Advanced Parameter Settings cont’d KO & KGUltra Low Dielectric ULD Mode Configuration = H * Sqrt DC H + LDC = I + H L / H2 Ultra Low Dielectric ULD Mode Configuration cont’d Advanced Output ConfigurationSetting the DAC trim DAC TrimFigure6 4mA & 20mA Calibration Using Actual Level Input Bench Calibration of the 4mA & 20mA PointsReversing The Output Action Using Actual Level Input Jumper Switch SettingsTroubleshooting Information Possible SymptomsValid Current Loop Outputs Possible Symptoms cont’d Electronics Module ReplacementHoneywell DE Output Option Interoperability and Conformance ClassHart Protocol Interface Option Operating ModesHart Communicator CompatibilityGlossary of Terms LRVAppendices Appendix a Sensor TrimConfiguration 2 Hidden Menu END CFG MenuTMP To access the linearization table Setting up Linearization Table PointsAppendix C Linearization To clear the linearization tableAppendix D Interface Applications MT2000 InterfaceUse and setup of the oscilloscope for the MT2000 Scope Settings Channel aPrerequisites Channel BAppendix F CE Certificate of Conformity Appendix G Exida Certificate MT2000-0200-1 Rev f 10-2007 DCN0160 MT2000-0200-01 Rev f 10-2007 DCN0160 MT2000-0200-1 Rev f 10-2007 DCN0160 Appendix I Mounting Configurations 3a, 3b10a 10bAppendix J Warranty Statement Year Warranty for