K-Tec Shortening of Probe, MT2000 Guided Wave Radar Guidelines, Factory Default Configuration

Page 8

3.2Shortening of Probe

The MT2000 single probe can be cut to length prior to installation. The MT2000 default factory configuration pro- vides a measurement in engineering units with a zero referenced to the bottom of the sensing probe. The top of the probe yields a measurement equal to the probe length (Figure 3.2).

20 mAdc

Probe Length

URV = Probe Length

LRV = 0 in. / 0 mm

4 mAdc

0 in. / 0mm

Factory Default Configuration

1.The default factory setup is with the instrument meas- uring “level”; This means that the display will indicate a number equal to the sensor length when the level is at the top of the vessel. When the vessel is empty it will indicate zero.

2.If readout in “level measurement units” is not desir- able, engineering units can be set to percentage (%). This will provide the readout in percentage of total level, referenced to the 4 mA and 20 mA points (LRV and URV).

3.If percentage (%) tank level readout is not desirable, proceed to Sensor Trim Section (Appendix A).

Figure 3.2

If the probe is shortened, the unit will indicate the distance as if the level was at the place where the probe was cut off as the lowest value, and read the change in EUN correctly FROM THAT POINT— to the URV.

Example: MT2000 was shipped (and trimmed) with a 10ft. probe. The probe was shortened by removing 3ft. leav- ing the total length at 7.0 ft. If the transmitter was installed with no further correction, the transmitter display (LL1) will indicate 3.0 ft. with the level at the end of the probe and 10ft. with the level at the top (a change of 7ft.). To set the transmitter to transmit 4 – 20 mA over the length of the probe, the following settings would need to be entered in the CAL menu:

LRV = 3.0 ft and URV = 10.0 ft.

If this is not desirable, one of the following can be done:

1.Change EUN = %. The level will now be shown (LL1) as 0.0% to 100.0%. (Note: LRV = 3.0 ft.; URV = 10.0 ft. in this example.)

2.Enter L1O = -3.0 ft. The unit will now display 0.0 ft to 7.0 ft for the above 7.0 ft level change. LRV and URV must be set (LRV = 0.0 ft., URV = 7.0 ft.) accounting for the offset, matching the display (0.0 to 7.0 ft).

3.Re–trim the unit to the actual sensor length – see Sensor Trim Section (Appendix A).

3.3MT2000 Guided Wave Radar Guidelines

These guidelines are not absolute limits but rather limits that will ensure optimum performance and ease of configu- ration:

Cable sensor probe is preferred over rigid rod.

Cables in tube or Pipe:

Use P11 (3/16” DIA) cable.

In 3” Pipe: 10 Ft. Max cable without spacers, longer cable with spacer every 10 ft.

In 1.5” or 2” pipe: 7 ft. max cable without spacers, longer cable with spacer every 5 ft.

Three spacer sizes available for 1.5”, 2”, or 3” sch 160 pipe.

Two spacer materials available, Teflon and ceramic (above 400°F).

8

MT2000-0200-01 Rev f (10-2007) DCN0160

Image 8
Contents Guided Wave Radar Level Transmitter Table of Contents List of Figures AppendicesIntroduction Ambient Temperature OverviewStorage Information Measurement cycle consists of the followingDirect Reflect Mode standard cont’d Ultra Low Dielectric ULD Measure MethodInstallation Mounting RequirementsFactory Default Configuration Shortening of ProbeMT2000 Guided Wave Radar Guidelines URV = Probe Length LRV = 0 in. / 0 mmWiring Quickstart ProcedureCommissioning MT2000 Guided Wave Radar Guidelines cont’dSetting the 4mA and 20 mA Points Using the Pushbutton Menu Quickstart Procedure cont’dVerify Proper Power-Up LCD Menu Operation Calibration MenuDetailed Configuration Parameters Direct Mode Blanking Menu Threshold Level Parameter THV and Gain Setting GSL1O Threshold Level Parameter THV and Gain Setting GS cont’dAdvanced Parameter Settings Advanced Parameter Settings cont’d KO & KGDC = I + H L / H2 Ultra Low Dielectric ULD Mode Configuration= H * Sqrt DC H + L Ultra Low Dielectric ULD Mode Configuration cont’d Advanced Output ConfigurationSetting the DAC trim DAC TrimFigure6 4mA & 20mA Calibration Using Actual Level Input Bench Calibration of the 4mA & 20mA PointsReversing The Output Action Using Actual Level Input Jumper Switch SettingsValid Current Loop Outputs Troubleshooting InformationPossible Symptoms Possible Symptoms cont’d Electronics Module ReplacementHoneywell DE Output Option Interoperability and Conformance ClassHart Protocol Interface Option Operating ModesHart Communicator CompatibilityGlossary of Terms LRVAppendices Appendix a Sensor TrimConfiguration 2 Hidden Menu END CFG MenuTMP To access the linearization table Setting up Linearization Table PointsAppendix C Linearization To clear the linearization tableAppendix D Interface Applications MT2000 InterfaceUse and setup of the oscilloscope for the MT2000 Scope Settings Channel aPrerequisites Channel BAppendix F CE Certificate of Conformity Appendix G Exida Certificate MT2000-0200-1 Rev f 10-2007 DCN0160 MT2000-0200-01 Rev f 10-2007 DCN0160 MT2000-0200-1 Rev f 10-2007 DCN0160 Appendix I Mounting Configurations 3a, 3b10a 10bAppendix J Warranty Statement Year Warranty for