VII. ELECTRICAL SUPPLY
WARNING
Authorized supplier personnel normally accomplish the connections for the ventilation system, electric supply, and gas supply, as arranged by the customer. Following these connections, the
NOTE: All aspects of the electrical supply connection must comply with current IEC/CEE requirements and with all applicable local, national, and international codes.
Check the oven serial plate before making any electric supply connections. Electric supply connections must agree with data on the oven serial plate. The location of the serial plate is shown in Figure
A fused disconnect switch or a main circuit breaker (customer furnished) MUST be installed in the electric supply line for each oven cavity. The circuit breaker/disconnect must have 3mm contact gaps breaking all poles of the supply. It is recommended that this circuit breaker/disconnect have lockout/tagout capability.
The supply conductors are to be
The oven requires a ground connection to the oven ground screw located in the electrical junction box. (The box is shown in Figure
SECTION 2 - INSTALLATION
A.Additional Information - Gas Ovens
All electric supply connections are made via the electrical junction box on the rear of the oven, shown in Figure
B.Additional Information - Electric Ovens
A cutout in the back wall of the machinery compartment provides access to the electrical supply connections. See Figure
C.Connection
Refer to the wiring diagram inside the machinery compartment, or in Section 5 of this Manual, to determine the correct connections for the electrical supply lines. Connect the supply as indicated on the wiring diagram.
If required by national or local codes, connect an equipotential ground wire to the lug next to the symbol. The equipotential ground connection must meet all applicable national and lo- cal code requirements.
ENGLISH
VIII. GAS SUPPLY
CAUTION
DURINGPRESSURETESTINGNOTEONEOFTHEFOLLOW- ING:
1.The oven and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressure in excess of 3.45 kPa.
2.The oven must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 3.45 kPa.
3.If incoming pressure is over 50mbar, a separate regu- lator MUST be installed in the line BEFORE the individual shutoff valve for the oven.
WARNING: To prevent damage to the control valve regu- lator during initial turn- on of gas, it is very important to open the manual shutoff valve very slowly.
After the initial gas
Figure 2-14 - Utility Connection Locations
Electrical
Junction Box
Gas ovens:
19mm pipe for
gas utility connection
Electric ovens:
Cutout for electrical
connection
11