Section 2 | Installation Instructions |
|
|
Electrical Service
GENERAL
!Warning
All wiring must conform to local, state and national codes.
VOLTAGE
The maximum allowable voltage variation is ±10% of the rated voltage at ice machine
Important
Observe correct polarity of incoming line voltage.
Fuse/Circuit Breaker
A separate fuse/circuit breaker must be provided for each ice machine. Circuit breakers must be H.A.C.R. rated (does not apply in Canada).
MINIMUM CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select the wire size of the electrical supply. (Minimum circuit ampacity is not the ice machine’s running amp load.)
!Warning
The ice machine must be grounded in accordance with national and local electrical codes.
S Series Ice Machines (* indicates preliminary data)
The wire size (or gauge) is also dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician.
ELECTRICAL REQUIREMENTS
Refer to Ice Machine Model/Serial Plate for voltage/ amperage specifications.
Ice Machine | Voltage Phase |
| Water Cooled | ||
Maximum Fuse/Circuit |
| ||||
Cycle | Minimum Circuit Amps | ||||
| Breaker |
| |||
|
|
|
| ||
| 40 |
| 22.1 | ||
S1800 | 20 |
| 12.0 | ||
| 230/1/50 | 40 |
| 20.5 |
Part Number |