Refrigeration System | Section 7 |
|
|
ANALYZING DISCHARGE PRESSURE DURING FREEZE OR HARVEST CYCLE
Procedure
1. Determine the ice machine operating conditions:
Air temp. entering condenser | ______ |
Air temp. around ice machine | ______ |
Water temp. entering sump trough | ______ |
2.Refer to Operating Pressure Chart for ice machine being checked.
Use the operating conditions determined in step 1 to find the published normal discharge pressures.
Freeze Cycle _______ | Harvest Cycle _______ |
Freeze Cycle Discharge Pressure High Checklist
3. Perform an actual discharge pressure check.
| Freeze Cycle | Harvest Cycle |
| PSIG (kPa) | PSIG (kPa) |
Beginning of Cycle | __________ | __________ |
Middle of Cycle | __________ | __________ |
End of Cycle | __________ | __________ |
4.Compare the actual discharge pressure (step 3) with the published discharge pressure (step 2).
The discharge pressure is normal when the actual pressure falls within the published pressure range for the ice machine’s operating conditions.
Possible Cause |
| Check/Correct |
Improper installation |
| See “Installation/Visual Inspection Checklist” |
Restricted condenser water flow |
| Low water pressure [20 psi (138 kPa) min.] |
|
| High inlet water temperature (90°F/32.2°C max.) |
|
| Dirty condenser |
|
| Dirty/defective water regulating valve |
|
| Water regulating valve out of adjustment |
Improper refrigerant charge |
| Overcharged |
|
| |
|
| Wrong type of refrigerant |
Other |
| |
|
| High side refrigerant lines/component restricted (before |
Freeze Cycle Discharge Pressure Low Checklist |
|
Possible Cause | Check/Correct |
Improper installation | See “Installation/Visual Inspection Checklist” |
Improper refrigerant charge | Undercharged |
| Wrong type of refrigerant |
Water regulating valve | Out of adjustment |
| Defective |
Other |
NOTE: Do not limit your diagnosis to only the items listed in the checklists.
Part Number |