Manitowoc Ice S1800 service manual Cooling Tower Applications, Water Supply, Water Inlet Lines

Page 15

Section 2

Installation Instructions

 

 

Water Supply and Drain Requirements

WATER SUPPLY

Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.

Important

If you are installing a Manitowoc Arctic Pure™ water filter system, refer to the Installation Instructions supplied with the filter system for ice making water inlet connections.

WATER INLET LINES

Follow these guidelines to install water inlet lines:

Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)

If water pressure exceeds the maximum recommended pressure, obtain a water pressure regulator from your Manitowoc distributor.

Install a water shut-off valve for both the ice making and condenser water lines.

Insulate water inlet lines to prevent condensation.

!Caution

Do not apply heat to water valve inlet fitting. This will damage plastic valve body.

DRAIN CONNECTIONS

Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:

Drain lines must have a 1.5 inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.

The floor drain must be large enough to accommodate drainage from all drains.

Run separate bin and ice machine drain lines. Insulate them to prevent condensation.

Vent the bin and ice machine drain to the atmosphere. Do not vent the condenser drain on water-cooled models.

Cooling Tower Applications

A water cooling tower installation does not require modification of the ice machine. The water regulator valve for the condenser continues to control the refrigeration discharge pressure.

It is necessary to know the amount of heat rejection, and the pressure drop through the condenser and water valves (inlet and outlet) when using a cooling tower on an ice machine.

Water entering the condenser must not exceed 90°F (32.2°C).

Water flow through the condenser must not exceed 5 gallons (19 liters) per minute.

Allow for a pressure drop of 7 psi (48 kPA) between the condenser water inlet and the outlet of the ice machine.

Water exiting the condenser must not exceed 110°F (43.3°C).

Part Number 80-1634-3

2-5

Image 15
Contents Service Manual Personal Injury Potential Read These Before ProceedingTable of Contents Table of Contents Section Ice Machine Operation Section MaintenanceSection Before Calling For Service Section Refrigeration System Table of Contents Section Electrical SystemTable of Contents Self-Contained Water-Cooled How to Read a Model NumberModel Numbers Ice Cube SizesGeneral Information Section Accessories Model/Serial Number Location Section General Information Model/Serial Number LocationWarranty Coverage General Ice Machine DimensionsWidth, Depth, and Height Dimensions Electrical and AuCS DimensionsSeries Heat of Rejection Ice Machine Air Conditioning Installation Instructions Section Location of Ice MachineIce Machine Heat of Rejection S1800M Water-CooledElectrical Requirements Section Installation Instructions Electrical ServiceVoltage Minimum Circuit AmpacitySelf Contained ICE Machine 230/1/50 For United Kingdom OnlySelf Contained ICE Machine 115/1/60 or 208-230/1/60 Self Contained ICE Machine 208-230/3/60Drain Connections Cooling Tower ApplicationsWater Supply Water Inlet LinesCondenser Installation Instructions SectionTypical Water Supply Drain Installation Water Supply and Drain Line SIZING/CONNECTIONSSection Installation Instructions Installation Check List Potential Personal Injury Situation AuCS Automatic Cleaning SystemComponent Identification Section Ice Machine OperationInitial START-UP or START-UP After Automatic SHUT-OFF Ice Machine Operation Section Sequence Of OperationAutomatic SHUT-OFF 7. Automatic Shut-Off Safety TimersHarvest Sequence 5. Water Purge HarvestIce Thickness Check Ice Machine Operation Section Operational ChecksWater Level ICE Thickness CheckHarvest Sequence Water Purge Water Purge AdjustmentThis page Intentionally Left Blank Ice Machine Operation SectionAlphaSan→ Exterior CleaningIce Machine Inspection Water-Cooled Condenser Water Regulating ValveSachet Replacement Procedure Maintenance Section GuardianInstallation Sachet Replacement FrequencyStep Section Maintenance Interior Cleaning and SanitizingCleaning Procedure Model Amount of CleanerMaintenance Section Sanitizing ProcedureSolution Type Water Mixed With Sanitizer Solution Type Water Mixed With Removal of Parts for CLEANING/SANITIZINGWater Curtain Water Curtain Removal Ice Thickness ProbeIce Thickness Probe Removal Water Distribution Tube Water TroughWater Distribution Tube Removal Water Level Probe Water PumpWater Pump Removal Water Dump Valve Dump Valve DisassemblyDrain Line Check Valve Evaporator Tray RemovalWater Inlet Valve Maintenance Section Removal from Service/Winterization Pry Open the Water Regulating Valve AUCS→ AccessorySELF-CONTAINED WATER-COOLED ICE Machines Problem Possible Cause To Correct ChecklistSafety Limit Feature Before Calling For Service SectionEnergized Parts Charts Section Electrical SystemSELF-CONTAINED WATER-COOLED Models Self-Contained Water Purge SELF-CONTAINED ModelsInitial Start-Up or Start-Up After Automatic Shut-Off Water PurgeRefrigeration System Start Up 5 Seconds Toggle Switch Refrigeration System START-UPSelf-Contained Refrigeration System Start-Up Self-Contained Pre-Chill Self-Contained Models Electrical System SectionFreeze Sequence PRE-CHILLToggle Switch Bin Switch Control Board Relays FreezeSelf-Contained Freeze Self-Contained Models Harvest Sequence Harvest Automatic Shut-Off Automatic SHUT-OFFSelf-Contained Automatic Shut-Off Wiring Diagram Legend Section Electrical System Wiring DiagramsControl Board S1800 SELF-CONTAINED 1 PhaseS1800 SELF-CONTAINED 3 Phase Main Fuse SpecificationsCheck Procedure BIN SwitchWater Curtain Removal Notes SymptomsDiagnostic Aids Continuity TestDetermine if the Compressor is Seized Compressor Electrical DiagnosticsCheck Resistance Ohm Values Check Motor Windings to GroundPtcr Diagnostics What is a PTCR?Compressor Start Sequence During Start-Up First .25 1.0 Seconds Troubleshooting PTCR’sWHY a Good Ptcr MAY Fail To Start the Compressor Model Automatic Shut-Off and RestartPart Number Checking the PtcrManitowoc Ptcr Model Manitowoc Cera-Mite RoomRelay Operation Check Diagnosing Start ComponentsCapacitor RelaySwitch Setting Terminals Ohm Reading ICE/OFF/CLEAN Toggle SwitchControl Board Electronic Control BoardInputs Safety LimitsHarvest Light Freeze Time LOCK-IN FeatureIce Thickness Probe Cleaning HOW the Probe WorksMonitoring of Harvest Light Correction Diagnosing ICE Thickness Control CircuitryFreeze Cycle Circuitry Water Inlet Valve Safety SHUT-OFFElectrical System Section Water Level Control Circuitry Water Level Probe LightProblem Water Trough Overfilling During Freeze Cycle Diagnosing Water Level Control CircuitryWait until the freeze cycle starts On or OFF Step Check Self Contained 1 Phase with Terminal Board Freeze Cycle Refrigeration Sequence SELF-CONTAINED Water -COOLED ModelsRefrigeration System Section S1800 SELF-CONTAINED Tubing Schematic General Times are in minutes Before Beginning ServiceWeights are in pounds ICE Production CheckINSTALLATION/VISUAL Inspection Checklist Water System ChecklistPossible Problem Corrective Action ICE Formation Pattern Extremely Thin at Evaporator OutletNormal Ice Formation No Ice Formation Extremely Thin at Evaporator InletSafety Limits Safety Limit IndicationAnalyzing Why Safety Limits May Stop the Ice Machine Possible Cause Check/Correct Safety Limit NotesSection Refrigeration System Analyzing Discharge Pressure During Freeze or Harvest Cycle ProcedureFreeze Cycle Discharge Pressure High Checklist Freeze Cycle Discharge Pressure Low ChecklistAnalyzing Suction Pressure During Freeze Cycle Step Example Using SY1004A Model Ice MachineFreeze Cycle Suction Pressure Low Checklist Freeze Cycle Suction Pressure High ChecklistHarvest Valve Temperature Check General Harvest Valve AnalysisFindings Comments Discharge Line Temperature Analysis General Column 3 TXV Flooding Final AnalysisColumn 1 Harvest Valve Leaking Column 2 LOW CHARGE/TXV StarvingModels Dual Expansion Valve Ice Machine Model Number Refrigeration System Operational Analysis TablesHigh Pressure CUT-OUT Hpco Control Operating Pressures S1800 SeriesSelf-Contained Water-Cooled Cycle Times Hour Ice ProductionConnections SELF-CONTAINED RECOVERY/EVACUATIONCharging Connections Self-Contained Charging ProceduresDetermining Severity Of Contamination System Contamination CLEAN-UPSevere System Contamination Cleanup Procedure Mild System Contamination Cleanup ProcedureSection Refrigeration System 10. Using Pinch-Off Tool Drier End Part Model Connection Size Number FILTER-DRIERSTotal System Refrigerant Charges Series Version Charge S1800M48 oz Recycle RecoverNew Product Specifications Refrigerant DefinitionsReclaimed Refrigerant Recovered or Recycled RefrigerantRefrigerant RE-USE Policy New RefrigerantHFC Refrigerant Questions and Answers This page Intentionally Left Blank Page Attend a Manitowoc Factory Service School